Hysteresis for Output-2
(It is visible only in FREQUENCYMETER / TACHOMETER Function)
It defines hysteresis for Output-2. It is used if Output-2 is non-latched.
It can be adjusted from to
Output-2 Pulse Time
Output-1 Pulse Time
Output-2 Operation Form
Output-1 Operation Form
Output-1 Normally non-energised
Output-1 Normally energised
Output-2 Normally non-energised
Output-2 Normally energised
It determines how long Output-2 will be active.
It can be adjusted from 0000.00 to 0099.99 seconds.
If it is 0000.00 second, then it operates indefinitely.
For details, refer to the section where output functions are
defined
It determines how long Output-1 will be active.
It can be adjusted from 0000.00 to 0099.99 seconds.
If it is 0000.00 second, then it operates indefinitely.
For details, refer to the section where output functions are
defined
Start of the Controlling
(It is accessible only in FREQUENCYMETER/TACHOMETER
functions)
Control is started when the unit is energised.
Control is started when count value reaches to SET1 value
Outputs are controlled according to this parameter
Control is started when count value reaches to SET2 value.
Only Ch-A input performs in Frequencymeter / Tachometer function.