OUTPUT ADDRESSES
Min
Max
Default
Unit
CH-1 ALARM OUT
Channel-1 Alarm Output Status
40
Address
00001
-
-
-
-
CH-2 ALARM OUT
Channel-2 Alarm Output Status
00002
-
-
-
-
CH-3 ALARM OUT
Channel-3 Alarm Output Status
00003
-
-
-
-
CH-4 ALARM OUT
Channel-4 Alarm Output Status
00004
-
-
-
-
CH-5 ALARM OUT
Channel-5 Alarm Output Status
00005
-
-
-
-
CH-6 ALARM OUT
Channel-6 Alarm Output Status
00006
-
-
-
-
CH-7 ALARM OUT
Channel-7 Alarm Output Status
00007
-
-
-
-
CH-8 ALARM OUT
Channel-8 Alarm Output Status
00008
-
-
-
-
GEN. ALR. OUT
General Alarm Output Status
00009
-
-
-
-
GEN.PREALR.OUT General Pre-Alarm Output Status
00010
-
-
-
-
PROCESS VALUES ADDRESSES
Min
Max
Default
Unit
CH-1 P. VALUE
Channel-1 Process Value
Address
30001
-
-
-
O
C
CH-2 P. VALUE
Channel-2 Process Value
30002
-
-
-
O
C
CH-3 P. VALUE
Channel-3 Process Value
30003
-
-
-
O
C
CH-4 P. VALUE
Channel-4 Process Value
30004
-
-
-
O
C
CH-5 P. VALUE
Channel-5 Process Value
30005
-
-
-
O
C
CH-6 P. VALUE
Channel-6 Process Value
30006
-
-
-
O
C
CH-7 P. VALUE
Channel-7 Process Value
30007
-
-
-
O
C
CH-8 P. VALUE
Channel-8 Process Value
30008
-
-
-
O
C
Note-2:
Process values are can be readed with modbus function-4 (read input register). Because of the
process values are displayed on LCD screen with point, the reading values from modbus is 10 times than
the real values.
Note-1:
Outputs status are can be readed with modbus function-1 (read coils).
Device’s response for modbus function-1 is always 2 byte data although the modbus function request less
than 9 outputs port.
8.1. Output Addresses
8.2. Process Values Addresses
8. Modbus Addresses