Configurable Failure Input-1 (P31)
Configurable Failure Input-2 (P32)
Configurable Failure Input-3 (P33)
A contact closure to 0V on any of these inputs causes the horn to sound for the period
programmed by Horn Duration (P08) and lights the appropriate indicator on the panel. The unit
can be programmed to respond in one of four ways:
0.
Indication is unlatched-the LED flashes and horn is sounding while the input is 0V. If the input
is not 0V the led will cancel flashing and horn sound.
1.
Indication is latched when the input is 0V then, the led flashes and horn is sounding then stays
on until the Reset button is pressed.
2.
This is the same as 1 but in addition the engine is stopped.
3.
Contactor releaser. It is valid only if the load transfer permit output is selected in configuration
outputs 1 and 2.
5.1.14 Configurable Inputs
Configurable Output-1 (P35)
Configurable Output-2 (P36)
When active, this output provides battery voltage (12V
Z
or 24V
Z
) and can be programmed in
one of fourteen different ways:
0.
Alarm output. Active when any fault is reported. It can be used for either audible or visual
alert.
1.
Engine running. Active while the engine is running
2.
Load transfer permitted. This output is active while engine is start to run and Control on Delay
(P26) expired and Alternator output voltage is between Alternator Voltage Upper Limit
(P00) and
Alternator Voltage Lower Limit (P01)
. This output can be used to control a contactor that transfers
the load to the alternator once the generator set is up and running.
3.
Preheat function. On starting the output is active for time period defined in Preheat Time (P09)
prior to running the starter motor.
4.
Over speed
5.
High temperature
6.
Low oil pressure
7.
8.
9.
10.
11.
12.
13.
Maintenance due
Failed to start
Over / under speed
Voltage failure
Charging failure
Low battery value
Weak battery
Use this option to change the Operator password. This password allows access to the
parameters from Alternator Voltage Lower Limit (P00) to Preheat Time (P09) and Operator
Password ( P37).
Use this option to change the Technician password. It allows access to the all parameters from
Alternator Voltage Lower Limit (P00) to Technician Password (P38).
5.1.15 Configurable Outputs
5.1.16 Operator Password (P37)
5.1.17 Technician Password (P38)
27