Equipment Use
Electrical control equipment for generating sets
Housing & Mounting
72 mm x 72 mm x 52 mm
Panel Cut-out
68 mm x 68 mm
Protection
NEMA4X (IP30 at front panel, IP20 at rear side)
Weight
Approximately 0.5 kg
Environmental Rating
Standard, indoor at an altitude of less then 2000 meters with non-condensing humidity
Operating / Storage Temperature -25ºC to +70ºC / -40ºC to +85ºC
Operating / Storage Humidity
90% max. (Non-condensing)
Installation Over Voltage Cat.
II appliances, portable equipment
Pollution Degree
II, Normal office or workplace, non-conductive pollution
Mode of Operation
Continuous
EMC
EN-61000-6-4, EMC generic emission standard for industrial equipment
EN-61000-6-2, EMC generic immunity standard for industrial equipment
Electrical Safety
EN-61010-1, safety requirements for electrical equipment for measurement, control and
laboratory use
Supply Voltage(
Z
)
Cranking Dropouts
Battery voltage can be 0V
Z
for max. 100msn during cranking (battery voltage should be
at least nominal voltage before cranking)
Failure Indicators
Status Indicators
Relay Outputs
8 - 32 V
Z
0.5%
Alternator Frequency Range
From generator voltage
Generator Speed Measurement
Start relay (10A@28V
Z
)
Fuel relay (10A@28V
Z
)
Conf. Out relay (10A@28V
Z
)
Failed to engine start
High engine temperature
Low oil pressure
Speed failure
Battery charge failure
General failure
Hz./RPM
Engine running time
Engine start
Engine stop
Frequency Meas. Accuracy
15,6 to 99,9 Hz (15 to 300 VL-N
V
RMS)
Specifications
3
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size