Program Parameters for Generator Application
Program Parameters for Pump (Fire Pump) Applications
1 - When the -BATTERY applied to Rem. start input (terminal-11),
the engine start cranking. (leave key switch “1” position)
2 - When the +BATTERY applied to +BAT input (terminal-3),
the engine start cranking. (leave key switch “1” position)
0 - Disable. The start / stop buton is used. (leave key switch “1” position)
Prog No
Parameter Name
Unit
Limits
Default
P 00
Application Selection (Generator, Pump, Fire Pump)
GEn, PUP, FPU
GEn
P 01
P 02
P 04
P 06
P 07
P 08
P 09
Frequency Lower Limit
Frequency Upper Limit
-
Hz.
Hz.
30.0 - 75.0
30.0 - 75.0
47.0
53.0
Horn Duration
Sec.
0= Cont. 1 - 999
30
Nominal Alternator Frequency
Hz.
30.0 - 75.0
50.0
Nominal Speed
Rpm
500 - 5000
1500
Stop/Fuel Solenoid Selection
-
StoP - FUEL
FUEL
Stop Solenoid Energising Time
Sec.
1 - 99
20
Crank Disconnect on Gen. Frequency
Hz.
25.0 - 75.0
30.0
P 10
Crank Disconnect on Charge Alternator Voltage
-
diS - EnAb
diS
P 11
Crank Disconnect on Oil Pressure
-
diS - EnAb
EnAb
P 12
Number of Starting Attempts
Number 1 - 10
3
P 13
Starting Attempt Duration
Sec.
5 - 99
5
P 14
Oil Pressure Bypass Time
Sec.
0 - 99
30
Safety On Delay
P 15
Sec.
0 - 99
10
Frequency Fault Control Delay
Sec.
0.0 - 10.0
3.0
P 16
P 17
Engine Running Time Value & New Engine Running Time
Hour
0 - 9999
0
Remote Start Selection:
P 18
P 19
Conf. Out Type:
0 - Alarm Out
2 - Preheat Out
-
diS
-
0 - 2
1
1 - Horn Out
P 20
Conf. Input 1
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
P 21
Conf. Input 2
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
Password
0 - 9999
0
-
P 03
P 05
0 - 5
0
0 - 5
0
-
-
0= diS 1 - 2
Prog No
Parameter Name
Unit
Limits
Default
P 00
Application Selection (Generator, Pump, Fire Pump)
GEn, PUP, FPU
PUP
P 06
P 08
P 09
-
Stop/Fuel Solenoid Selection
-
StoP - FUEL
FUEL
Stop Solenoid Energising Time
Sec.
1 - 99
20
P 10
Crank Disconnect on Charge Alternator Voltage
-
diS - EnAb
diS
P 11
Crank Disconnect on Oil Pressure
-
diS - EnAb
EnAb
P 12
Number of Starting Attempts
Number 1 - 10
3
P 13
Starting Attempt Duration
Sec.
5 - 99
5
Oil Pressure Bypass Time
Sec.
0 - 99
30
Safety On Delay
P 15
Sec.
0 - 99
10
P 16
P 17
Engine Running Time Value & New Engine Running Time
Hour
0 - 9999
0
P 18
P 19
Conf. Out Type
0 - Alarm Out
2 - Preheat Out
-
diS
-
0 - 2
1
1 - Horn Out
Conf. Input 1
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
Conf. Input 2
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
P 05
0 - 5
0
0 - 5
0
-
-
0= diS 1 - 2
Horn Duration
Sec.
0= Cont. 1 - 999
30
P 20
P 21
5 - Engine stop, observation while engine running
Password
0 - 9999
0
-
1 - When the -BATTERY applied to Rem. start input (terminal-11),
the engine start cranking. (leave key switch “1” position)
2 - When the +BATTERY applied to +BAT input (terminal-3),
the engine start cranking. (leave key switch “1” position)
0 - Disable. The start / stop buton is used. (leave key switch “1” position)
Remote Start Selection:
2
Manual and Remote Start Unit with Key Switch, 72x72 DIN Size