EMKO EAOM-3 Series Manual Download Page 2

Program Parameters for Generator Application

Program Parameters for Pump (Fire Pump) Applications

1 - When the -BATTERY applied to Rem. start input (terminal-11), 
     the engine start cranking. (leave key switch “1” position)
2 - When the +BATTERY applied to +BAT input (terminal-3),
     the engine start cranking. (leave key switch “1” position)

0 - Disable. The start / stop buton is used. (leave key switch “1” position)

Prog No

Parameter Name

Unit

Limits

Default

P 00

Application Selection (Generator, Pump, Fire Pump)

GEn, PUP, FPU

GEn

P 01
P 02

P 04

P 06
P 07
P 08
P 09

Frequency Lower Limit
Frequency Upper Limit

-
Hz.
Hz.

30.0 - 75.0
30.0 - 75.0

47.0
53.0

Horn Duration

Sec.

0= Cont.   1 - 999

30

Nominal Alternator Frequency

Hz.

30.0 - 75.0

50.0

Nominal Speed

Rpm

500 - 5000

1500

Stop/Fuel Solenoid Selection

-

StoP - FUEL

FUEL

Stop Solenoid Energising Time

Sec.

1 - 99

20

Crank Disconnect on Gen. Frequency

Hz.

25.0 - 75.0

30.0

P 10

Crank Disconnect on Charge Alternator Voltage

-

diS - EnAb

diS

P 11

Crank Disconnect on Oil Pressure

-

diS - EnAb

EnAb

P 12

Number of Starting Attempts

Number 1 - 10

3

P 13

Starting Attempt Duration

Sec.

5 - 99

5

P 14

Oil Pressure Bypass Time

Sec.

0 - 99

30

Safety On Delay

P 15

Sec.

0 - 99

10

Frequency Fault Control Delay

Sec.

0.0 - 10.0

3.0

P 16

P 17

Engine Running Time Value & New Engine Running Time

Hour

0 - 9999

0

Remote Start Selection:

P 18

P 19

Conf. Out Type:

0 - Alarm Out

2 - Preheat Out

-

diS

-

0 - 2

1

1 - Horn Out

P 20

Conf. Input 1
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running

P 21

Conf. Input 2
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running

Password

0 - 9999

0

-

P 03

P 05

0 - 5

0

0 - 5

0

-

-

0= diS   1 - 2

Prog No

Parameter Name

Unit

Limits

Default

P 00

Application Selection (Generator, Pump, Fire Pump)

GEn, PUP, FPU

PUP

P 06
P 08
P 09

-

Stop/Fuel Solenoid Selection

-

StoP - FUEL

FUEL

Stop Solenoid Energising Time

Sec.

1 - 99

20

P 10

Crank Disconnect on Charge Alternator Voltage

-

diS - EnAb

diS

P 11

Crank Disconnect on Oil Pressure

-

diS - EnAb

EnAb

P 12

Number of Starting Attempts

Number 1 - 10

3

P 13

Starting Attempt Duration

Sec.

5 - 99

5

Oil Pressure Bypass Time

Sec.

0 - 99

30

Safety On Delay

P 15

Sec.

0 - 99

10

P 16

P 17

Engine Running Time Value & New Engine Running Time

Hour

0 - 9999

0

P 18

P 19

Conf. Out Type

0 - Alarm Out

2 - Preheat Out

-

diS

-

0 - 2

1

1 - Horn Out

Conf. Input 1
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running
5 - Engine stop, observation while engine running
Conf. Input 2
0 - Only horn temporary, observation continuously
1 - Only horn permanent, observation continuously
2 - Engine stop, observation continuously
3 - Only horn temporary, observation while engine running
4 - Only horn permanent, observation while engine running

P 05

0 - 5

0

0 - 5

0

-

-

0= diS   1 - 2

Horn Duration

Sec.

0= Cont.   1 - 999

30

P 20
P 21

5 - Engine stop, observation while engine running

Password

0 - 9999

0

-

1 - When the -BATTERY applied to Rem. start input (terminal-11), 
     the engine start cranking. (leave key switch “1” position)
2 - When the +BATTERY applied to +BAT input (terminal-3),
     the engine start cranking. (leave key switch “1” position)

0 - Disable. The start / stop buton is used. (leave key switch “1” position)

Remote Start Selection:

2

Manual and Remote Start Unit with Key Switch, 72x72 DIN Size

Summary of Contents for EAOM-3 Series

Page 1: ...unit will stop the engine The module will check the alarms aftersafety on timer is expired Under one of this fault conditions the module will stop the engine Over speed generator application Under spe...

Page 2: ...n continuously 2 Engine stop observation continuously 3 Only horn temporary observation while engine running 4 Only horn permanent observation while engine running 5 Engine stop observation while engi...

Page 3: ...t EN 61000 6 2 EMC generic immunity standard for industrial equipment Electrical Safety EN 61010 1 safety requirements for electrical equipment for measurement control and laboratory use Supply Voltag...

Page 4: ...T FUEL CONF O CHARGE GEN D W L BAT BAT BAT 5 6 7 4 2 3 1 8 9 10 11 BAT CONF INPUT 1 LOW OIL PRES HIGH TEMP 10A 28VDC 10A 28VDC 10A 28VDC BAT CONF INPUT 2 OR REMOTE START P16 1 REM INPUT GND TX RX RS 2...

Page 5: ...4 7 13 CONF OUT c 1 8 CONF INPUT 2 11 PREHEAT BAT 10A 28VDC 10A 28VDC 10A 28VDC c OR ALARM 3 BAT CHARGE GENERATOR 2 c 1 Connect the unit as shown in the appropriate diagram above Be sure to connect t...

Page 6: ...N 12 CHARGE GEN D W L B FUSE 1 40 A 40 A BATTERY BAT STARTER BATTERY NEGATIVE MUST BE GROUNDED START RELAY SOLENOID RELAY CONF INPUT 1 HIGH TEMPERATURE LOW OIL PRESSURE HORN 9 5 6 10 1 2 4 7 13 CONF...

Page 7: ......

Page 8: ...HOMETER 0 1mA FUSE D W L B START RELAY FUEL SOLE LOW OIL PRESSURE HIGH TEMPERATURE AUXILIARY SHUTDOWN 8 11 10 9 7 6 5 4 2 3 1 12 14 L1 N 13 15 OFF RUN START KEYSWITCH 16 AUX 2 INPUT ONLY STP TYPES BAT...

Page 9: ...0A BATTERY BATTERY OUT MAX 1A STARTER CHARGE GEN TACHOMETER 0 1mA D W L B START RELAY FUEL SOLE LOW OIL PRESSURE HIGH TEMPERATURE AUXILIARY SHUTDOWN 8 11 10 9 7 6 5 4 2 3 1 12 14 13 15 OFF RUN START K...

Page 10: ......

Reviews: