EMKO DT-9910 Instruction Manual Download Page 2

Not :

If the wrong password is entered, the device turns to the main operation screen.

If no operation is performed in programming mode for 10 seconds, the device turns to the
main operation screen automatically.

i

6

T

P

T

T

P

SET

T - 9910

8

4.1 Enter Programming Mode, Change and Save the Hidden Parameters

The main operation screen 

Programming Mode
    Entering Screen

Program  Button is
pressed and password
screen appears.

Program           buton is pressed
for 3 seconds,the  programming 
mode login screen is shown on 
the display.

Password Entering Screen

Enter password with increament and
decreament buttons.

Password Entering Screen

Confirm password with
RESET button

Programming screen

If program  button is pressed,
parameter  value is accessed.

BUTTON DESCRIPTIONS

5

4.6 ESM-3712-C Soðutma Kontrol CihazýÇýkýþ Çalýþma Grafikleri

3.

if necessary this parameter, the value is added tank temperature.

4.2.

Range : 1°C to+10 °C

7

Heater Set Setting Parameter (Default = 0)

Range:0 to +90 °C

Heater Set Hysteresis Parameter (Default = 4)

Range :0 to +10

ON

OFF

Set

HSt

Zaman

HSt

Zaman

Set + Hst

Description of The Front Panel

Program parameters

Freezing  prevent  parameter(Default= 4)

Range : -10 to +10 °C
if collector temperature less than this value ,Pump output is activated. 
   

Hysteresis Parameter

Pump 
output

Temperature
      value

Boiler temperature Offset parameter (Default = 0)

Range : -10°C to +10 °C

Collector temperature Offset parameter (Default = 0)

if necessary this parameter, the value is added collector temperature.

Range : -10°C to +10 °C

  This value is added heater set parameter. 

If temperature is less than this parameter value, the heater output will be on.
Otherwise the heater  output will be off.

Prevent freezing
     parameter 

Prevent freezing
parameter  value

The value can be changed with
increament and decreament buttons.

Programming screen

Prevent freezing
     parameter 

If program  button is pressed,
parameter  value is accessed.

Tank MaximumTemperature Parameter(Default=60)

Collector MinimumTemperature Parameter(Default=10)

Programming Mode Accessing Password 

It is used for accessing to the programming mode. It can be adjusted from ‘0’ to ‘999’.
If  the value equals to  '0',the program does not enter password entry programming menu  

Freezing  prevent  parameter

Parameter is changed with increament
and decreament buttons

Range:0 to +95 °C
This parameter is used to avoid tank overheating , all controller disabled for safety.
Temperature output becomes active when the value falls below two degrees .If tank
temperature becomes maximum temperature,the screen starts blinking.

Range:0 to +95 °C
When the temperature of the collector decreases less than this parameter ,differantial 
control is disabled and pump closed. if the temperature becomes  greater  3 ° C than 
this parameter, differantial control is activated again.

Not: Freeze protection and temperature parameters is not affected by this parameter 

This message gives sensor error or not connected.Controller stops and can not see 
sensor value.  CLL led does not blink for collector sensor error.TNK led does not blink for 
tank sensor error. 

In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude around
set value changes according to controlled
system. For reducing oscillation period of
temperature value, a threshold zone is formed
below or around set value and this zone is
named hysteresis.

T

T

P

T

CLL TNK

CFR PMP

SET

T - 9910

1

2

3

4

5

6

7

8

9 10

PRG

HTR

11 12

T

CLL TNK

CFR PMP

PRG

HTR

T

T

P

SET

T - 9910

T

CLL TNK

CFR PMP

PRG

HTR

1.Program Button        :

 The program button is used to  change the set value in prrogram

menu.When pressed  for 10 seconds  to enter the program menu ,Less than 10 seconds
to acces the setting value .

2.Decreament Button  :

 It is used to decrease the setting  parameters in programming mode.

3.Increament Button   :

 It is used to increase  the setting  parameters in programming mode.

4.SET Button               : 

When setting this value is used to save the set values. Also on  the 

main screen,push this button so  can see  values of temperature sensors. 

5.   T   Led(Green)        :

 Setting the value to set the screen lights up as long overdue.

6.   T   Led (Red)          : 

If The LED lights on, the temperature difference is shown

on the main Operation screen.

7.CLL     Led                 :

 if temperature of collector  shown on the display,the light is on.

8.TNK     Led                :

 if temperature of tank shown on the display,the light is on.

9.PRG     Led                :

 Entering the program menu the led starts blinking.

10.CFR   Led                 :

 if collector temperature less than collector value which  is set on 

the program menu for to prevent freezing on the Collector, the light is on and Pump output is 
activated. 

11.PMP  Led                :

  if pump output is active,the light is on.  

12.HTR  Output           :

  If heater output is active, the light is on.        

Differential Controller

Differential  Controller

Differential Controller