It is possible with the field test, to activate/deactivate the loads to carry out functional tests on the
controller.
▶ Access the
[ACC]
parameter by pressing the key , and then .
▶ When
[ACC]
appears, press . You will see [0].
▶ Press to control the outputs
[55]
or to control the inputs
▶ Press to control the outputs or to control the inputs.
Control Outputs:
▶
Short press on
: Triggers output 1 - Compressor
▶
Short press on
: Activates output 2 - Defrost
▶
Short press on
: Activates output 3 - Fan
▶
Short press on
: Activates buzzer
It is not possible to activate more than one output at the same time
Press for 2s to exit the function
Display Inputs:
▶
Quick touch in
: displays instantaneous value of S1
▶
Quick touch in
: displays instantaneous value of S2
▶
Quick touch in
: displays instantaneous value of S3/Digital
Notes:
- Press for 2 seconds at any time to exit the mode and restart the controller;
- Simultaneously press the to return to the selection menu between controlling the outputs or display inputs
+
11
USER
MANUAL
TEMPERATURE CONTROLLER
STORM
ST
201
Min
Máx
4
0 (NO)
-
0 (NO)
P44
Turn off the control functions
2
0
-
0
P45
Function lock mode
13
0 (OFF)
-
0 (OFF)
P42
Function of digital input 1 / Sensor S3
20
-20.1 (OFF)
ºC
0
P43
Evaporator temperature S2 indication [offset]
105
-50
ºC
-50
P38
Low ambient temperature alarm (S1)
999
0 (NO)
min
0 (NO)
P39
Alarm inhibition time by temperature
999
0 (NO)
min
0 (NO)
P40
Time of open door to given an alarm
1 (ON)
0 (NO)
-
0 (OFF)
P41
Enabling the Buzzer (0-OFF / 1-ON)
60
15
seg
15
P46
Function blocking time
(NO)
(YES)
ºC
0 (NO)
-
-
-
P48
NFC blocking
P49
Temperature Unit, Operation Mode and Function Lock
Selection
Sensor
Temperature
P47
SFG (default)
Heating | Cooling
NTC/10K/B (25/85) 3950K 1%
SCL
Heating | Cooling
NTC/10K/B (25/100) 3988K 1%
SEP
Heating | Cooling
NTC/10K/B(25/85) 3435K 1%
TABLE 3
6. FIELD TEST
Unit
Standard
Parameter
Description