9
27
-JNJU4XJUDI4FUUJOH
$MPTF0QFO-JNJU4XJUDI$BN4FUUJOH
̷
AOLS
̷
ACLS
̷
OLS
̷
CLS
15-1-1
Confirm that the power is off.
Pull lever located on the side of the ACTUATOR to
engage the manual override handwheel.
Rotate the handwheel counter clockwise to fully close
the ACTUATOR / valve.
15-1-2
Lossen the closed limit switch cam set screw as shown.
Rotate cam in the close / clockwise direction and engage
the switch lever to actuate the switch
If auxillary limit switches are included in the ACTUATOR,
then set the corresponding auxillary switch at this time.
15-1-3
Firmly re-tighten the cam set screw.
15-1-4
To set the open limit switch, follow the same proceedure as above except that the rotation will be
counter clockwise using the open limit switch cam.
AOLS
Dry Contact Open Limit Switch
Dry Contact Close Limit Switch
Open Limit Switch
Close Limit Switch
ACLS
OLS
CLS
.PUJPOJODPOUSPMT