www.enviromaster.com
Side Discharge Condensers
10
INSTALLATION INSTRUCTIONS
9. Refer to Charts on page 12 to “fine
tune” the refrigerant charge to meet
your conditions.
REFRIGERANT PROCESSING
COMPLETE PIPING CONNECTIONS
IMPORTANT NOTES:
1. To find the charge adjustment and system charge for any evaporator and tubing length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Line Adjustment
2. Round to the nearest ounce and allow for gauges and hoses.
8. Charge to proper weight, charge
based on feet of interconnect (tables
starting on page 10).
S1C REFRIGERANT CHARGE TABLE
CONDENSER
EVAPORATOR PAIRING
LINE CHG/FT
FACTORY CHARGE
S1CA9
CACA12
.25 oz.
37 oz.
S1CA2
CACA12
.25 oz.
40 oz.
S1CA8
CACA24
.56 oz.
51 oz.
S1CA4
CACA24
.56 oz.
65 oz.
S1CA3
CACA36
.56 oz.
72 oz.
S1CA6
CACA36
.56 oz.
90 oz.
S1CA9
WLHA09
.25 oz.
37 oz.
S1CA2
WLHA12
.25 oz.
40 oz.
S1CA8
WLHA24
.56 oz.
51 oz.
S1CA4
WLHA24
.56 oz.
65 oz.
S1CA3
WLCA30
.56 oz.
72 oz.
S1CA6
WLCA36
.56 oz.
90 oz.
S1H (HEAT PUMP) REFRIGERANT CHARGE TABLE
CONDENSER
EVAPORATOR PAIRING
LINE CHG/FT
FACTORY CHARGE
S1HA9
WLHA09
.25 oz.
41 oz.
S1HA2
WLHA12
.25 oz.
44 oz.
S1HA8
WLHA24
.56 oz.
53 oz.
S1HA4
WLHA24
.56 oz.
67 oz.
Note:
Charging should be done with a dial-a-charge or weighed in with a scale.
S2C
Shown
S1C
Shown
Summary of Contents for S1C