Type Y696

4

  4.  To remotely vent the regulator, remove the vent 

(key 56) and install obstruction-free tubing or piping 

into the 1/4 in. NPT vent tapping. Provide protection 

on a remote vent by installing a screened vent cap 

into the remote end of the vent pipe.

  5.  If continuous operation of the system is required 

during inspection or maintenance, install a 

three-valve bypass around the regulator.

  6.  Vapor recovery regulators are used to maintain 

a constant inlet (blanket) pressure with the outlet 

flowing to a system whose pressure is lower than 

that at the inlet. The vapor recovery regulators 

are not intended to be used as an ASME certified 

relief device for overpressure protection. They 

are to be used as part of a gas blanketing system 

to control the outflow of blanketing gas under 

normal conditions and to collect tank vapors for 

the vapor disposal or reclamation system. You 

should provide alternate methods of emergency 

overpressure protection.

Startup and Adjustment

!

WARnIng

To avoid personal injury, property 

damage or equipment damage caused 

by bursting of pressure containing 

parts or explosion of accumulated 

gas, never adjust the control spring to 

produce an outlet pressure higher than 

the upper limit of the outlet pressure 

range of that particular spring. If the 

desired outlet pressure is not within 

the range of the control spring, install 

a spring of the proper range according 

to the Diaphragm and Spring case Area 

section of the maintenance procedure.

With installation completed, the regulator can be 

placed in operation by slowly opening the upstream 

and downstream block valves, if used, while using 

gauges to monitor pressure.
The regulator has been adjusted at the factory to 

provide approximately the pressure requested. The 

range of allowable pressure settings is stamped on the 

spring casing nameplate. If a pressure setting beyond 

the stamped range is required, install a spring with the 

desired range by following the procedures for changing 

the spring and diaphragm in the Maintenance section. 

To adjust the pressure setting, perform the following 

steps (key numbers are referenced in Figure 3):
  1. Remove the closing cap (key 3).
  2.  Turn the adjusting screw (key 2) either clockwise 

to increase control pressure or counterclockwise to 

decrease control pressure. The regulator will go into 

immediate operation. To ensure correct operation 

always use a pressure gauge to monitor the vapor 

recovery pressure when making adjustments.

  3. Replace the closing cap (key 3).

Shutdown

First close the nearest upstream shutoff valve and 

then close the nearest downstream shutoff valve to 

vent the equipment properly. Next, open the vent 

valves on both the upstream and downstream sides of 

the regulator. All pressure between the shutoff valves 

is released through the open vent valves.

Maintenance

Regulator parts are subject to normal wear and 

must be inspected and replaced as necessary. The 

frequency of inspection and replacement of parts 

depends upon the severity of service conditions 

or the requirements of local, state and federal 

regulations. Due to the care Emerson™ takes in 

meeting all manufacturing requirements (heat treating, 

dimensional tolerances, etc.), use only replacement 

parts manufactured or furnished by Fisher.
Key numbers are referenced in Figure 3.

!

WARnIng

To avoid personal injury, property damage 

or equipment damage caused by sudden 

release of pressure, isolate the regulator 

from all pressure and cautiously release 

trapped pressure from the regulator 

before attempting disassembly.

Body Area

This procedure is for gaining access to the disk 

assembly, orifice, body gasket and split ring. All 

pressure must be released from the regulator, before 

the following steps can be performed.

Summary of Contents for Y696

Page 1: ...rnal registration requiring no downstream control line It is used to sense increase in vessel pressure and vent excessive internal vessel pressure to an appropriate vapor recovery disposal or reclamations system Principle of Operation The Type Y696 is used to maintain a constant inlet blanket pressure with the outlet flowing to a system whose pressure is lower than that at the inlet When vessel pr...

Page 2: ...tions section lists maximum pressures temperatures and other specifications Specifications for a given regulator as it originally comes from the factory are stamped on the spring case nameplate Body Size and End Connection Style 1 See Table 1 Maximum Allowable Inlet and Outlet Pressure 2 15 psig 1 0 bar Control Pressure Ranges See Table 2 Pressure Registration Internal or External Spring Case and ...

Page 3: ...material Apply pipe compound only to the male pipe threads 2 Install the regulator using a straight run of pipe the same size or larger as the regulator body as shown in Figure 2 Flow through the regulator body is indicated by the flow arrow cast on the body If a block valve is required install a full flow valve between the regulator and the blanketed vessel For proper operation the regulator shou...

Page 4: ...ge of allowable pressure settings is stamped on the spring casing nameplate If a pressure setting beyond the stamped range is required install a spring with the desired range by following the procedures for changing the spring and diaphragm in the Maintenance section To adjust the pressure setting perform the following steps key numbers are referenced in Figure 3 1 Remove the closing cap key 3 2 T...

Page 5: ...s to the control spring diaphragm and lever assembly stem All pressure must be released from the diaphragm case assembly before the following steps can be performed To Change the Control Spring 1 Remove the closing cap key 3 and turn the adjusting screw key 2 counterclockwise until all compression is removed from the control spring key 1 2 Remove the adjusting screw key 2 and the upper spring seat...

Page 6: ...pertinent information stamped on the nameplate Specify the complete 11 character part number from the following parts list when ordering replacement parts Parts List In this parts list parts marked NACE are intended for corrosion resistant service as detailed in the NACE International Standards MR0175 and MR0103 Type Y696 Regulator Figure 3 Key Description Part Number 1 Control Spring Plated steel...

Page 7: ...Type Y696 7 Figure 3 Type Y696 Assembly Section A A 43B0679 29 50 51 56 75 21 22 6 7 8 9 20 13 11 19 17 16 28 27 47 46 14 41 40 5 24 4 3 2 35 1 30 23 25 38 A A ...

Page 8: ...res 28008 France Tel 33 2 37 33 47 00 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 TESCOM Emerson Process Management Tescom Corporation USA Headquarters Elk River Minnesota 55330 2445 USA Tels 1 763 241 3238 1 800 447 1250 Europe Selmsdorf 23923 Germany Tel 49 38823 31 287 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9499 For further information visit www fisherregulato...

Reviews: