5/5
Label
Name Range
Value Level
ALd Temperature alarm delay
0
255 min
15 Pr2
dAO Delay of temperature alarm at start up
0
23h e 50’
1,3 Pr2
AP2 Probe for temperat. alarm of condenser
nP; P1; P2; P3; P4
P4 Pr2
AL2 Condenser for low temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
-40 Pr2
AU2 Condenser for high temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
110 Pr2
AH2 Differ. for condenser temp. alar. recovery [0,1°C ÷ 25,5°C] [1°F ÷ 45°F]
5 Pr2
Ad2 Condenser temperature alarm delay
0 ÷ 254 (min.) , 255=nU
15 Pr2
dA2 Delay of cond. temper. alarm at start up
0.0 ÷ 23h 50’
1,3 Pr2
bLL
Compr. off for condenser low
temperature alarm
n(0) - Y(1)
n Pr2
AC2
Compr. off for condenser high
temperature alarm
n(0) - Y(1)
n Pr2
tbA Alarm relay disabling
n=no; y=yes
y Pr2
oA3 Third relay configuration
ALr = alarm; dEF = do not select
it; Lig =Light; AUS =AUX;
onF=always on; Fan= do not
select it; db = neutral zone; cP2
= second compressor; dF2 = do
not select it; HES = night blind
Lig Pr2
AoP Alarm relay polarity (oA3=ALr)
oP; cL
cL Pr2
i1P Digital input polarity (13-14)
oP=opening;CL=closing
cL Pr1
i1F Digital input 1 configuration (13-14)
EAL, bAL, PAL, dor; dEF; Htr,
AUS
dor Pr1
did Digital input alarm delay (13-14)
0÷255min
15 Pr1
i2P Digital input polarity (13-19)
oP=opening;CL=closing
cL Pr2
i2F Digital input configuration (13-19)
EAL, bAL, PAL, dor; dEF; Htr,
AUS
EAL Pr2
d2d Digital input alarm delay (13-19)
0÷255min
5 Pr2
Nps Number of activation of pressure switch
0 ÷15
15 Pr2
odc Compress status when open door
no; Fan; CPr; F_C
F-c Pr2
rrd Regulation restart with door open alarm
n – Y
y Pr2
HES Differential for Energy Saving
(-30°C÷30°C) (-54°F÷54°F)
0 Pr2
Adr Serial address
1÷247
1 Pr2
PbC Kind of probe
Ptc; ntc
ntc Pr2
onF on/off key enabling
nu, oFF; ES
oFF Pr2
dP1 Room probe display
--
- Pr2
dP2 Second probe display
--
- Pr2
dP3 Third probe display
--
- Pr2
dP4 Fourth probe display
--
- Pr2
rSE Real set point
actual set
- Pr2
rEL Software release
--
1.8 Pr2
Ptb Map code
--
Pr2