XW10L 

2/5 

LED 

MODE 

FUNCTION 

 

ON 

An alarm is occurring 

  ON 

Continuous cycle is running 

  ON 

Energy saving enabled 

 

ON Light 

on 

  ON 

Auxiliary relay on 

°C/°F  ON Measurement 

unit 

°C/°F  Flashing Programming 

phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

n

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

n

 key again or by waiting 5s the normal display will be restored. 

5.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

o

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

 

By pressing the 

o

 key again or by waiting 5s the normal display will be restored. 

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt 
message will be displayed) 

2.

 

To confirm the operation the “rSt” message starts blinking and the normal temperature will be 
displayed. 

6.

 

MAIN FUNCTIONS 

6.1

 

HOW TO SEE THE SET POINT 

 

1.

 

Push and immediately release the SET  key: the display will show the 
Set point value; 

2.

 

Push and immediately release the SET key or wait for 5 seconds to  

display the probe value again. 

6.2

 

HOW TO CHANGE THE SET POINT 

1.

 

Push the SET key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

4.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.3

 

HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows:  
1.

 

Enter the Programming mode by pressing the Set + 

n

 keys for 3s (the “°C” or “°F” LED starts 

blinking). 

2.

 

Select the required parameter. Press the “SET” key to display its value 

3.

 

Use “UP” or “DOWN” to change its value. 

4.

 

Press “SET” to store the new value and move to the following parameter. 

To exit: Press SET + UP or wait 15s without pressing a key. 
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.4

 

THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.4.1  HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the Set + 

n

 keys for 3s (the “°C” or “°F” LED starts 

blinking). 

2.

 

Released the keys, then push again the Set+

n

 keys for more than 7s. The Pr2 label will be 

displayed immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU. 

3.

 

Select the required parameter. 

4.

 

Press the “SET” key to display its value 

5.

 

Use 

or 

n

 to change its value. 

6.

 

Press “SET” to store the new value and move to the following parameter. 

To exit: Press SET + 

or wait 15s without pressing a key. 

NOTE1: if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys 
pushed till the Pr2 message is displayed.  
NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.4.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” 
(user level) by pressing “SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

6.5

 

HOW TO LOCK THE KEYBOARD 

1. 

 

Keep pressed for more than 3 s the UP +  DOWN keys. 

2. 

 

The “POF” message will be displayed and the keyboard will be locked. At this point it will be 
possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.6

 

TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

 keys, till the “Pon”  message will be 

displayed. 

6.7

 

THE CONTINUOUS CYCLE 

It can be activated by holding the “

o

” key pressed for about 3 seconds. The compressor operates to 

maintain the “ccS” set point for the time set through the “CCt” parameter. The cycle can be 
terminated before the end of the set time using the same activation key “

o

” for 3 seconds. 

 

6.8

 

THE ON/OFF FUNCTION 

 

 

With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF” 
message is displayed. In this configuration, the regulation is disabled.  
To switch the instrument on, push again the ON/OFF key. 

 

WARNING: Loads connected to the normally closed contacts of the relays are always 

supplied and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

REGULATION 
Hy Differential
: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN 

is Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set 
point. 

LS  Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. 
US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum value for set point. 
Ot  Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of 

the thermostat probe. 

P2P  Second probe presence: n= not present; y= present. 
OE Second probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of the 

second probe. 

P3P  Third probe presence (P3): n= not present:, the terminals 13-14 operate as digital input.; y= 

present:, the terminals 13-14  operate as third probe. 

O3 Third probe calibration  (P3): (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the third probe. 

P4P Fourth probe presence: (n = Not present; y = present). 
o4  Fourth probe calibration: (-12.0

12.0°C) allows to adjust possible offset of the fourth probe. 

OdS Outputs activation delay at start up: (0÷255min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter.  

AC  Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the 

following restart. 

AC1 2

nd

 compressor delay at start up (0÷255s) Used only if oA3 = cP2 Time interval between the 

switching on of the first compressor and the second one. 

rtr  Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 = P2 ): it 

allows to set the regulation according to the percentage of the first and second probe, as for the 
following formula (rtr(P1-P2)/100 + P2). 

CCt Compressor ON time during continuous  cycle: (0.0÷24.0h; res. 10min) Allows to set the 

length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be 
used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: (-50÷150°C) it sets the set point used during the continuous 

cycle. 

COn Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With COF=0 compressor is always active. 

CH  Type of action: CL = cooling; Ht = heating. 
DISPLAY 
CF Temperature measurement unit: 
  °C=Celsius;  °F=Fahrenheit. WARNING: When the 

measurement unit is changed the SET point and the values  of the parameters Hy, LS, US, Ot, 
ALU and ALL have to be checked and modified if necessary). 

rES  Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display. 
Lod Instrument display: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by the 

instrument: P1 = Thermostat probe; P2 = Second probe; P3 = Third probe(only for model with 
this option enabled); P4 = Fourth probe, SET = set point;  dtr = percentage of visualization. 

rEd  X- REP display (optional): (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by 

X- REP: P1 = Thermostat probe; P2 = Second probe; P3 = Third probe(only for model with this 
option enabled); P4 = Fourth probe, SET = set point;  dtr = percentage of visualization. 

dLy Display delay: (0 ÷20.0m; resul. 10s) when the temperature increases, the display is updated 

of 1 °C/1°F after this time. 

dtr  Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = 

P1, 0 = P2 ): if Lod = dtr it allows to set the visualization according to the percentage of the 
first and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 

AUXILIARY THERMOSTAT CONFIGURATION (terms. 1-3) – OA3 = AUS 
ACH  Kind of regulation for auxiliary relay
Ht = heating; CL = cooling 
SAA  Set Point for auxiliary relay: (-50,0÷110,0°C; -58÷230°F) it defines the room temperature set 

point  to switch auxiliary relay. 

SHy Differential for auxiliary output: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for 

auxiliary output set point.  
With ACH = cL AUX Cut in is SAA + SHy; . AUX Cut  out is SAA 
With ACH = Ht AUX Cut in is SAA - SHy; . AUX Cut out  is SAA 

ArP  Probe selection for auxiliary: nP = no probe, the auxiliary relay is switched only by button; P1 

Probe 1 (Thermostat probe); P2 = Probe 2 (second probe); P3 = Probe 3 (display probe); P4 
Probe 4 fourth probe. 

Sdd  Auxiliary relay off during defrost: n = the auxiliary relay operates during defrost. 
 y 

the auxiliary relay is switched off during defrost. 

ALARMS 
ALP  Probe selection for alarm
: nP = no probe, the temperature alarms are disabled; P1 = Probe 1 

(Thermostat probe); P2 = Probe 2 (second probe); P3 = Probe 3 (display probe); P4 = Fourth 
probe. 

ALC  Temperature alarms configuration: (Ab; rE) 
 

Ab= absolute temperature: alarm temperature is given by the ALL or ALU values.  rE = 
temperature alarms are referred to the set point. Temperature alarm is enabled when the 
temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

Summary of Contents for XW10L

Page 1: ...e reaches the set point value again Time Temper Compr SET ON In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF 3 3 CH HT HEATING APPLICATION Time Temper Heating ON SET SET HY Time The Hy value is automatically set under the Set Point If the temperature decreases and reaches set point minus differential the regulation output is ac...

Page 2: ...s the set point LS Minimum set point 50 C SET 58 F SET Sets the minimum value for the set point US Maximum set point SET 110 C SET 230 F Set the maximum value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to adjust possible offset of the thermostat probe P2P Second probe presence n not present y present OE Second probe calibration 12 0 12 0 C 120 120 F allows to adjust...

Page 3: ...PS activation in the did time is reached switch off and on the instrument to restart normal regulation odc Compressor status when open door no Fan normal CPr F_C Compressor OFF rrd Outputs restart after doA alarm no outputs not affected by the doA alarm yES outputs restart with the doA alarm HES Temperature increase during the Energy Saving cycle 30 0 C 30 0 C it sets the increasing value of the s...

Page 4: ...arm CA with i1F PAL recovers only by switching off and on the instrument 14 3 OTHER MESSAGES Pon Keyboard unlocked PoF Keyboard locked noP In programming mode none parameter is present in Pr1 On the display or in dP2 dP3 dP4 the selected probe is nor enabled 15 TECHNICAL DATA Housing self extinguishing ABS Case facia 38x185 mm depth 76mm Mounting panel mounting in a 150x31 mm panel cut out with tw...

Page 5: ...second compressor dF2 do not select it HES night blind Lig Pr2 AoP Alarm relay polarity oA3 ALr oP cL cL Pr2 i1P Digital input polarity 13 14 oP opening CL closing cL Pr1 i1F Digital input 1 configuration 13 14 EAL bAL PAL dor dEF Htr AUS dor Pr1 did Digital input alarm delay 13 14 0 255min 15 Pr1 i2P Digital input polarity 13 19 oP opening CL closing cL Pr2 i2F Digital input configuration 13 19 E...

Reviews: