1592019030 XEV02D GB r1.2 04.06.2015
XEV02D
4/4
dLn
Number of DLT alarms in dLi hours
before blocking compressor
0 to 15, 0=function
disabled
0
Pr2
dLi
Time interval (in hours) in which to
check dLn number of DLT alarms
0 to 24 hours; 0=function
disabled
0
Pr2
CEd
Maximum compressor capacity (in
percentage) in case of probe error
0 to 100%
100
Pr2
Cdd
Maximum compressor capacity (in
percentage) in case of DLT alarm
and for time dLd
0 to 100%
100
Pr2
CEi
Maximum compressor capacity (in
percentage) in case of regulation
input error
0 to 100%
100
Pr2
dEr
Alarm delay in case of regulation
input/probes reading error
0 to 999 sec
30
Pr2
2on
Minimum delay between two DG
compressor start-ups
0 to 255 min
5
Pr1
2oF
Delay between DG compressor
switch-off and start-up
0 to 999 sec
120
Pr1
odo
Power on regulation delay
0 to 999 sec
5
Pr1
dSL
Lower limit for control signal (in
percentage). 0=function disabled.
0 to 100%
0
Pr2
Si0
Minimum input value in percentage
0 to 100%
0
Pr2
Si1
Maximum input value in percentage
0 to 100%
100
Pr2
PMi
Minimum load in percentage
0 to 100%
0
Pr2
PMA
Maximum load in percentage
0 to 100%
100
Pr2
A2F
ALARM
key
timed
function
configuration (push button timed, 3
sec)
nu; onF
nu
Pr2
Adr
Serial address
1 to 247
1
Pr2
bAU
Baudrate for serial communication
9.6; 19.2
9.6
Pr2
dP1
Analogue control signal (read only)
-
Pr1
dP2
Probe P2 display (read only)
-
Pr1
d1S
Digital input status display (isolated
input)
-
Pr1
d2S
Digital input status display (high
voltage input)
-
Pr1
rEL
Release Firmware (read only)
-
Pr1
Ptb
Parameters table code (read only)
-
Pr1
Pr2
Protected parameters menu access
-
Pr1