Emerson XEV02D Installing And Operating Instructions Download Page 2

1592019030 XEV02D GB r1.2 04.06.2015 

XEV02D 

2/4 

Alarm reset is automatic and happens as soon as control exceeds value set in parameter 

dSL

.  

If 

oA1=CPr

, the regulation always re-starts after expiring both anti-short cycle timers 

2on

 (minimum 

time  between  two  consecutive  compressor  activations)  and 

2oF

  (minimum  time  between  one 

compressor stop and next start-up).  
Press any key to deactivate the buzzer at any time. 

5. FRONT PANEL

To  display  and  to  modify  the  set  point.  In  programming  mode  it  selects  a 
parameter or it confirms a value 
Keep it pressed for 3 sec to enter the information menu 
In programming mode it slides the codes of the parameters or it increases their 
values 
Keep it pressed for 3 sec to enter the information menu 

In  programming  mode  it  slides  the  codes  of  parameters  or  it  decreases  their 
values. 
To enter the alarms archive menu 
Keep it pressed for 3 sec to switch OFF and ON the device (if 

A2F=oFF

KEYS COMBINATIONS 

To lock or to unlock the keyboard

 

To enter programming mode 

To exit from various menu 

To erase the alarm database (when into alarm menu) 

5.1

 

XEV01D LEDS 

On display there are some luminous dots. Their meaning is described in the following table: 

LED 

MODE 

Function 

ON 

Low temperature alarm 

ON 

High temperature alarm (DLT alarm) 

BLINKING 

TRIAC output is working 

RS 

BLINKING 

Serial communication is working 

kPA 

ON 

Units of measurement in dakPA 

°C, °F, 

bar, PSI 

ON 

Units of measurement in °C, °F, bar or PSI 

sec 

ON 

Units of measurement in seconds 

ON 

Alarm active 

6. USER INTERFACE

6.1

 

ACCESS THE VARIABLES MENU 

Keeping  the 

UP

  key  pressed  for  3  sec  when  in  normal  operation  mode  (variables  display)  with 

U2F=viS

, grants access to variables’ quick display menu. Press the 

SET

 key to switch from displaying 

the variable’s label to its value, and vice-versa. The variables displayed in sequence are: cycle time of 
digital  modulating  (

tdG

  label)  expressed  in  seconds,  regulation  input  in  percentage  (

irP

  label), 

regulation input expressed as analogical value (

iAn

 label), P2 probe input (

P2

 label), valve regulation 

output  in  percentage  (

PEr

  label),  the  used  machine  configuration  (

CtY

  parameter),  the  parameter 

indicating any change on critical parameters (

Mod

). In addition to these, the firmware release date can 

be read by using par. 

FYr

 (year), 

FMn

 (month) and 

FdY

 (day). 

Scroll the variables inside the menu by pressing the 

UP

 and 

DOWN

 keys. Whatever position you are 

in, press the 

SET+UP

 keys or waiting for the 60 sec time-out to expire without pressing any key to exit 

the quick display menu. 

NOTES:

  

-

Cycle time 

tdG

 is indicated in seconds with “sec” LED on 

-

Values display in percentage go from 0.0% to 100.0% 

-

The temperature is displayed with its units of measurement

-

This procedure is possible when 

t1F

U2F

 or 

d2F=viS

6.2

 

PROGRAMMING CYCLE TIME tdG 

Keep  the 

SET

  button  pressed  for  3  sec  to  gains  access  to  the  digital  modulating  menu  time  (

tdG

 

parameter).  The  display  will  show  the 

tdG

  label  once  accessed.  Press  the 

SET

  key  to  switch  to 

parameter’s  value.  Menu  exit  is  for  time-out  (60  sec  without  pressing  any  key)  or  by  pressing  the 

SET+UP

 keys again. 

6.3

 

HOW TO: ENTERING “PR1” PARAMETER MENU 

To access the “Pr1” level menu: 
1.

Keep both 

SET+DOWN 

buttons pressed for 3 sec.

2.

The instruments will show the first parameter present in the “Pr1” menu.

6.4

 

ACCESS TO “PR2” PARAMETER MENU 

To access to “Pr2” menu: 

1.

Enter the “Pr1” menu 

2.

Select “Pr2” parameter and press 

SET

.

3.

The “

PAS

” label will be shown, then “

0—

” with 0 blinking. 

Insert “

321

” password through 

UP 

and 

DOWN 

buttons,

 

then press 

SET

 to confirm.

6.5

 

CHANGE A PARAMETERS VALUE 

To change any parameter value, follow this procedure: 
1.

Enter the Programming mode by keeping the 

SET+DOWN

 buttons pressed for 3 sec.

2.

Select the required parameter.

3.

Press the 

SET

 button to display the value.

4.

Use 

UP 

or 

DOWN

 to change the value.

5.

Press 

SET

 to store the new value and move to the following parameter.

To exit: press 

SET+UP

 or wait for 30 sec without pressing any button. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

7. PARAMETER LIST

REGULATION 

oA1 

Digital  output  1  configuration:

 

nu

=not  used; 

ALr

=alarm  output; 

CPr

=compressor 

output; 

dmd

=do not use it. 

oA2 

Digital output 2 configuration (open collector output):

 

nu

=not used; 

ALr

=alarm.

 

oP1 

Digital output 1 polarity: oP

=open

; CL

=closed.

 

oP2 

Digital output 2 polarity: oP

=open

; CL

=closed.

 

tbA 

Alarm output deactivation (only if oAx=ALr): n

=not permitted;

 Y

=permitted

bEn 

Buzzer (software) management: on

=buzzer active;

 oFF

=buzzer disabled.

 

P2C 

Temperature  probe  configuration  (it  depends  on  the  hardware):  nu

=not  used;

 

Pt1

=PT1000;

 ntC

=NTC10k probe;

 n86=

NTC86k probe.

 

o2 

Probe P2 calibration: 

-12 to 12°C; -21 to 21°F

 

PA4 

Analogue input at 4mA or 0V: 

(0 to 100%) set the percentage value relative to the 

minimum analog input. 

P20 

Analogue input at 20mA or 10V:

 (0 to 100%) set the percentage value relative to the 

maximum analog input.

 

Sut 

Start up time: 

(0.0 to 25.5 sec) valve activation time before starting the regulation. 

tdG 

Modulation time interval: 

6 to 40 sec.

 

2on 

Minimum delay between two DG compressor start-ups: 

0 to 255 min 

2oF 

Delay between DG compressor switch-off and start-up: 

0 to 999 sec 

odo 

Power on regulation delay:

 (0 to 999 sec) the regulation starts after this delay 

dSL 

Lower limit for control signal (in percentage):

 0 to 100%

 

Si0 

Minimum analogue input value (in percentage):

 0 to 100%

 

Si1 

Maximum analogue input value (in percentage):

 0 to 100%

 

PMi 

Minimum load (in percentage):

 0 to 100%

 

PMA 

Maximum load (in percentage):

 0 to 100%

 

DISPLAY 

Lod 

Default  displayed  variable:  PEr

=TRIAC  output  activation  in  percentage; 

Ain

=analogue input value in percentage;

 P2

=temperature measured form probe P2.

 

CF 

Units of measurement for temperature: °C

=Celsius;

 °F

=Fahrenheit.

 

rES 

Temperature resolution (valid only if CF=°C): in

=integer;

 dE

=decimal.

 

DIGITAL INPUTS 

i1F 

Digital  input  1  configuration  (voltage  free  contact):  nP

=disabled; 

EAL

=external 

alarm; 

bAL

=block alarm; 

onF

=regulation enabled. 

i2F 

Digital  input  2  configuration  (powered  input):  nP

=disabled; 

EAL

=external  alarm; 

bAL

=block alarm; 

onF

=regulation enabled. 

i1P 

Digital input 1 polarity: oP

=open

; CL

=closed. 

i2P 

Digital input 2 polarity: oP

=open

; CL

=closed. 

ALARMS 

ALL 

Low temperature alarm: 

(-30 to 200°C; -22 to 392°F) this alarm blocks the regulation. 

A manual reset required. 

dLL 

Low temperature alarm activation delay: 

0 to 999 sec 

dLt 

Discharge line temperature:

 (-30 to 200°C; -22 to 392°F) value used for compressor 

block and alarm output activation. 

dth 

Differential:

 (0 to 99.9°C; 0 to 999°F) used to restart the compressor after any DLT 

alarm. 

dLd 

DLT alarm activation delay:

 0 to 999 sec 

Summary of Contents for XEV02D

Page 1: ...LARM CONTROL TRIP DLT alarm is generated when DLT probe P2 temperature is T dLt Until alarm delay time dLd is active the total compressor capacity will be limited to Cdd If alarm delay time dLd is disabled or elapsed General alarm LED and digital output set as alarm oAx ALr is activated If a digital output is set as compressor output oA1 CPr this is also deactivated If a digital output is set as d...

Page 2: ...essed for 3 sec 2 The instruments will show the first parameter present in the Pr1 menu 6 4 ACCESS TO PR2 PARAMETER MENU To access to Pr2 menu 1 Enter the Pr1 menu 2 Select Pr2 parameter and press SET 3 The PAS label will be shown then 0 with 0 blinking Insert 321 password through UP and DOWN buttons then press SET to confirm 6 5 CHANGE A PARAMETERS VALUE To change any parameter value follow this ...

Page 3: ...on max stored value is 19h59min 12 1 ALARMS ARCHIVE ERASING All saved alarms can be deleted by keeping the ALARM SET key pressed for 5 sec when into ALARM MENU The display will show the rSt label flashing for 3 sec and then the default display visualization will be restored Lod variable NOTE All saved alarms can be also deleted via special MODBUS command 13 DISPLAY MESSAGES Mess Cause Outputs A02 ...

Page 4: ...in 5 Pr1 2oF Delay between DG compressor switch off and start up 0 to 999 sec 120 Pr1 odo Power on regulation delay 0 to 999 sec 5 Pr1 dSL Lower limit for control signal in percentage 0 function disabled 0 to 100 0 Pr2 Si0 Minimum input value in percentage 0 to 100 0 Pr2 Si1 Maximum input value in percentage 0 to 100 100 Pr2 PMi Minimum load in percentage 0 to 100 0 Pr2 PMA Maximum load in percent...

Reviews: