background image

5

GRILLE

26"

24-13/16"

D

C

6"

23-5/16"

A

B

3/4"

FRAME 

ASSEMBLY

REAR VIEW OF GRILLE AND CABINET

TRANSITION

20

APPROX.

DUCT

3 UNITS

UNIT OPENING

1 UNIT

TRANSITION TO CABINET

Figure 10

ALLOW ROOM FOR

GRILLE TO 

SWING OUT

CELL

GRILLE

WALL

(OR CEILING)

CABINET

Figure 9

Figure 8

MECHANICAL INSTALLATION

MECHANICAL INSTALLATION

MECHANICAL INSTALLATION

MECHANICAL INSTALLATION

MECHANICAL INSTALLATION

Remember that allowance must be made for the grille
to swing down so that the cell can be removed by
pulling it straight out of the cabinet. (Figure 9).

DUCT WORK CONNECTION

DUCT WORK CONNECTION

DUCT WORK CONNECTION

DUCT WORK CONNECTION

DUCT WORK CONNECTION

If the duct work to be used is larger or smaller than the
recommended framing sizes, a transition should be
installed between the duct work and the air cleaner to
insure maximum filtering efficiency. The expansion or
contraction rate of the transition should not exceed the
ratio of 1 to 3. (See figure 10.)

Once the duct connection to the framing is completed,
the air cleaner frame (cabinet) may be inserted into the
framing cavity.

Before inserting the cabinet, one of the three knock-
outs (figure 15) should be removed for insertion of the
120 VAC input wiring.

After properly positioning the cabinet, it may be fas-
tened to the framing either by using the mounting holes
in the inside walls of the cabinet or the mounting holes
in the front flanges of the unit.

DIM.

DIM.

DIM.

DIM.

DIM.

1000 CFM

1000 CFM

1000 CFM

1000 CFM

1000 CFM

1400 CFM

1400 CFM

1400 CFM

1400 CFM

1400 CFM

2000 CFM

2000 CFM

2000 CFM

2000 CFM

2000 CFM

A

16-15/16

23-7/8

28-7/8

B

9-7/16

16-7/16

21-7/16

C

18-7/16

25-3/8

30-3/8

D

19

26

31

Refer to page 2 for model numbers
and CFM cross references.

Summary of Contents for White Rodgers TTW1000

Page 1: ...r Cleaner Air Cleaner Air Cleaner Air Cleaner Please read and familiarize yourself with the contents of this manual before Please read and familiarize yourself with the contents of this manual before Please read and familiarize yourself with the contents of this manual before Please read and familiarize yourself with the contents of this manual before Please read and familiarize yourself with the ...

Page 2: ...serious personal injury or death injury or death injury or death injury or death injury or death 2 Follow a regular service and maintenance schedule for efficient operation 3 Unit must run for one full hour after installation This will allow the collecting cells to reach peak efficiency Table of Contents Table of Contents Table of Contents Table of Contents Table of Contents Rules for Safe Install...

Page 3: ...t on floor 3 Release two knurled screws Fig 2 at upper edge of grille open grille and slide it out of hinges at bottom by moving it to the left 4 Rotate two screen retainer latches either left or right to clear screen Lift screen out 5 Remove three screws one at each end and one at center of electrical enclosure cover and remove cover Dirt laden air enters the unit from the room It passes through ...

Page 4: ... or low wall installa tions or in the ceiling It can be used with any type of forced air heating or cooling system In most cases return air ducts are located just inside the wall or ceiling grille When the air cleaner is flush mounted it will extend through the wall cutout and into the return air duct If the return air duct is located at a distance from the wall or ceiling extend a connecting duct...

Page 5: ...be installed between the duct work and the air cleaner to insure maximum filtering efficiency The expansion or contraction rate of the transition should not exceed the ratio of 1 to 3 See figure 10 Once the duct connection to the framing is completed the air cleaner frame cabinet may be inserted into the framing cavity Before inserting the cabinet one of the three knock outs figure 15 should be re...

Page 6: ...re 11 3 Carefully saw out wall or ceiling area exactly as marked Remember the frame flange is only 3 4 inch wide It will not cover an oversize or irregular cutout 4 Figures 12 13 and 14 show several possible situations that will be apparent when the cutout is finished With standard stud spacing you will run into either one or two studs They must be cut and the section removed at air cleaner locati...

Page 7: ... codes For this reason specific wiring instructions are not given The color coding of wires out of the junction box are white 120V or red 220V and black They should be matched to wires of the same color from electrical power source figure 18 Connect ground wire from power source directly to the green grounding wire provided in the junction box area This Thru The Wall electronic air cleaner may be ...

Page 8: ... cell should point inward b Insert cell at the top and engage retaining pins figure 19 into their respective cell retaining slots then slide cell outward until retaining pins are at bottoms of slots c Allow cell to swing inward at the bottom pushing slightly until it clicks over the safety spring clip at bottom center of cabinet d Continue to push cell inward at bottom until it latches into the sp...

Page 9: ...ay occur when the cell has become loaded with dirt and needs washing or when still damp after washing The presence or absence of this sound normally does not mean that the unit is defective MAINTENANCE MAINTENANCE MAINTENANCE MAINTENANCE MAINTENANCE WASHING CELL AND SCREEN WASHING CELL AND SCREEN WASHING CELL AND SCREEN WASHING CELL AND SCREEN WASHING CELL AND SCREEN NOTE NOTE NOTE NOTE NOTE For t...

Page 10: ...ng contaminants Dirt and Smoke particles The residue on the collecting plates of an electronic air cleaner is black indicating it is removing dirt from the air stream After installing an air cleaner you may notice white dust typically long linty particles or fibers from carpets cotton materials or drapery fabrics This material is not collected by the air cleaner because it does not contain the irr...

Page 11: ...llowing procedures will The following instructions are for use by qualified personnel WARNING The following procedures will The following instructions are for use by qualified personnel WARNING The following procedures will expose hazardous live parts Disconnect electrical power to air cleaner before proceeding expose hazardous live parts Disconnect electrical power to air cleaner before proceedin...

Page 12: ...12 REPLACEMENT REPLACEMENT REPLACEMENT REPLACEMENT REPLACEMENT PARTS DIAGRAM PARTS DIAGRAM PARTS DIAGRAM PARTS DIAGRAM PARTS DIAGRAM 1 or 1 3 2 5 7 6 9 5 10 11 8 120V 220V ...

Page 13: ...ng Wire F843 0775 F843 0775 F843 0775 7 Pre Filter F121 0232 F121 0233 F121 0234 8 Screw with Washer F870 0026 F870 0026 F870 0026 9 Grille F831 0095 F831 0096 F831 0097 10 Charcoal Filter F121 0235 F121 0236 F121 0237 Manual 37 6365 37 6365 37 6365 Not Shown Parts List for Electronic Air Cleaner TTW Parts List for Electronic Air Cleaner TTW Parts List for Electronic Air Cleaner TTW Parts List for...

Page 14: ...SCHEDULE WASH REMINDER SCHEDULE WASH REMINDER SCHEDULE WASH REMINDER SCHEDULE A regular washing schedule is necessary to ensure proper efficiency A thorough washing once every month will be adequate for most installations More or Less frequent washing may be necessary on some installations where there is new carpeting plaster dust or excessive cigarette smoke etc See page 9 for maintenance and ins...

Page 15: ...15 ...

Page 16: ...tronic Air Cleaner Although White Rodgers does not extend a warranty directly to consumers White Rodgers does extend a warranty to Wholesalers and Original Equipment Manufacturers who use White Rodgers Products To obtain more information about how your Wholesaler or Original Equipment Manufacturer s warranty may benefit you please contact your Wholesaler or Original Equipment Manufacturer Sincerel...

Reviews: