2

SPECIFICATIONS 

ELECTRICAL RATINGS [@ 77°F (25°C)]:
  Input Voltage: 
25 VAC 50/60 Hz
  Max. Input Current @ 25 VAC: 0.45 amp
    Relay Load Ratings:

Valve Relay:  1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Current:   2.0 amp @ 80 VAC
Inducer Relay:    2.2 FLA–3.5 LRA @ 120 VAC
Circulator Relay: 14.5 FLA–25.0 LRA @ 120 VAC

  Flame Current Requirements:

Minimum current to insure flame detection: 0.25 µa DC*
Maximum current for non-detection: 0.1 µa DC*
Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe lead
OPERATING TEMPERATURE RANGE:

TIMING SPECIFICATIONS

(All times are in seconds, unless noted otherwise

Event

Definition

50A66-843

Pre-Purge

The period of time intended to allow for the dissipation of any unburned 
gas or residual products of combustion at the beginning of a furnace 
operating cycle prior to initiating ignition

15

Trial for Ignition 
Period (TFI)

The period of time between initiation of gas flow and the action to 
shut off the gas flow in the event of failure to establish proof of the 
supervised ignition source or the supervised main burner flame.

4

Ignition Activation 
Period (IAP)

The period of time between energizing the main gas valve and 
deactivation of the ignition means prior to the end of TFI

4

Retries

The additional attempts within the same thermostat cycle for ignition 
when the supervised main burner flame is not proven within the first 
trial for ignition period.

4 times

Valve Sequence 
Period

Valve sequence period equals 4 seconds trial for ignition period x 
(1 initial try + 2 retries) + 12 seconds.

20

Interpurge

The period of time intended to allow for the dissipation of any unburned 
gas or residual products of combustion between the failed trial for 
ignition and the retry period.

15

Post-Purge

The period of time intended to allow for the dissipation of any unburned 
gas or residual products of combustion at the end of a furnace burner 
operating cycle. Post-purge begins at the loss of flame sense.

5

Lockout Time

ANSI standard rated module timing.

250

Heat Delay-To-Fan-On

The period of time between proof of the supervised main burner flame 
and the activation of the blower motor at Heat speed.

45

Heat Delay-To-Fan-Off*

The period of time between the loss of a call for heat and the 
deactivation of the blower motor at Heat speed.

60/

90/120/180

Cool Delay-To-Fan-On

The period of time after a thermostat demand for cool before energizing 
the circulator blower motor at Cool speed.

2

Cool Delay-To-Fan-Off*

The period of time between the loss of a call for cool and the 
deactivation of the blower motor at Cool speed.

2/

45

Ignitor Warm-up

The length of time allowed for the igniter to heat up prior to the initiation 
of gas flow.

20

Auto Reset

After one (1) hour of internal or external lockout, the control will auto-
matically reset itself and go into an auto restart purge for 60 seconds.

60 minutes

Humidifier

Yes

Electronic Air Cleaner

Yes

*This time will vary depending on option switch position. The control is factory set at 90 seconds HEAT 

delay-to-fan-off and 45 seconds COOL delay-to-fan-off. See OPERATION section for further information

  -40° to 175°F (-40° to 80°C)
HUMIDITY RANGE:
  
5% to 93% relative humidity (non-condensing)
MOUNTING:
  Surface mount multipoise
Timing Specs: (@ 60 Hz**)

 

maximum

Flame Establishing Time: 

0.8 sec

Flame Failure Response Time: 

2.0 sec

**At 50 Hz, all timing specifications should be increased 

by 20%

Gases Approved: Natural, Manufactured, Mixed, Liquified 
Petroleum, and LP Gas Air Mixtures are all approved for use.

Summary of Contents for White-Rodgers 21D83M-843

Page 1: ...act with water dripping spraying rain etc If the control has been in direct contact with water replace the control Label all wires before disconnection when servicing controls Wiring errors can cause improper and dangerous operation Route and secure wiring away from flame SHOCK HAZARD Disconnect electric power before servicing Ensure proper earth grounding of appliance Ensure proper connection of ...

Page 2: ...idual products of combustion between the failed trial for ignition and the retry period 15 Post Purge The period of time intended to allow for the dissipation of any unburned gas or residual products of combustion at the end of a furnace burner operating cycle Post purge begins at the loss of flame sense 5 Lockout Time ANSI standard rated module timing 250 Heat Delay To Fan On The period of time b...

Page 3: ...cement 50A66 843 ignition control board over the holes marked A in figure 1 Insert the replacement control stand off fasteners into the holes in the mounting panel 6 Insert the four provided stand off fasteners into the back of the mounting panel in the holes marked B in figure 1 Insert the replacement control board assembly into the existing holes in the control box or blower panel 7 Insert provi...

Page 4: ...ue transformer wire Optional 4 blue wire provided for transformers that have a quick connect terminal 6 Connect the provided 9 pin to 12 pin wiring harness to the unit 9 pin connector 7 Connect the provided 4 pin to 6 pin wiring harness to the unit 6 pin connector 8 Connect the yellow wire from position 6 on the 12 pin connector to the yellow transformer wire 9 Connect GND wire to equipment ground...

Page 5: ...te with the 50A66 843 s adap tive ignition routine to ensure the most efficient ignitor temperature At the end of the ignitor warm up time both valves in the gas valve are opened Flame must be detected within 4 seconds If flame is detected the delay to fan on period begins After the delay to fan on period ends the circulator fan is energized at heat speed If there is an optional electronic air cle...

Page 6: ...out or a shorted or open condition in the flame probe circuit will be sensed within 2 seconds The gas valve will de energize andthecontrolwillrestarttheignitionsequence Recycles will begin and the burner will operate normally if the gas supply returns or the fault condition is corrected before the last ignition attempt Otherwise the control will go into system lockout If the control has gone into ...

Page 7: ...ng and verify furnace is grounded properly Slow flash Off Flame sensed with gas valve de energized Verify the gas is operating and shutting down prop erly Flame in burner assembly should extinguish promptly at the end of the cycle Check orifices and gas pressure On Slow flash Open rollout switch Verify continuity through rollout switch circuit On On Module internal fault condition Module contacts ...