Table 3. 

Combined Overpressure and Underpressure Shutoff (OPSO and UPSO) Spring Ranges

Principle of Operation

VSX4 and VSX8 Series Controller

The pressure measuring element of the controller consists 

of a diaphragm that senses downstream pressure. The 

downstream pressure is controlled by the regulator. The 

overpressure shut-off spring and under-pressure shut-off 

spring exerts force on the top side of the diaphragm.
When the downstream pressure increases above the 

Overpressure Shutoff (OPSO) setting, the diaphragm 

moves up.
When the downstream pressure decreases below the 

Underpressure Shutoff (UPSO) setting, the diaphragm 

moves down.

Both of these actions result in the rotation of the cam and 

the release of the reset pin.
The valve plug spring then pushes the valve plug against 

the regulator port, stopping the flow of gas. The reset 

button is then used to reset (relatch) the controller 

(refer to the Resetting Procedure section for detailed 

resetting instructions).

Standard downstream pressure registration for the 

controller is external; however, internal sensing line is made 

available by removing the downstream sense blocking 

screw, installing a 1/4 NPT plug in the control line port and 

removing the downstream control line.

aCCUraCY grOUP (ag)

P

d

 < 35 mbar / 0.507 psig

35 mbar / 0.507 psig ≤ P

d

 

< 60 mbar / 0.87 psig

60 mbar / 0.87 psig ≤ P

d

 

< 100 mbar / 1.5 psig

P

d

 ≥ 100 mbar / 1.5 psig

AG

min

30

15

10

5

AG

max

10

10

Note: Stable inlet pressure AG

min

 = AG 10 (P

d

 < 60 mbar / 0.87 psig) and AG 5 (P

d

 > 60 mbar / 0.87 psig), AG

max

 = AG 5

Table 4.

 Controller Accuracy in Accordance to EN 14382

SLaM SHUT DEViCE

Type

inlet Pressure

Under Pressure  

Shut-off (UPSO)

UPSO Spring

Over Pressure  

Shut-off (OPSO)

OPSO Spring

Set range

Part number

Spring Color

Set range  

Over UPSO Setpoint

Part number

Spring Color

bar

psig

mbar

psig

mbar

psig

VSX4L 

VSX8L

8.6

125

7 to 11

ERAA05835A0

White

30 to 44

GF02167X012

Black

7 to 15

32 to 44

7 to 30

3 to 12 in. w.c.

41 to 44

16 to 18 in. w.c.

40 to 76

16 to 29 in. w.c.

GF02168X012

Brown

10 to 75

4 in. w.c. to  

1.1 psig

T14169T0012

Blue

 48 to 74

19 in. w.c. to 1.1 psig

 50 to 122

20 in. w.c. to 1.8 psig

GF02169X012

Red

25 to 160

10 in. w.c. to 

2.3 psig

T14170T0012

Silver

83 to 221

1.2 to 3.2

GF02170X012

Orange

100 to 500

1.5 to 7.3

FA142869X12

Orange Stripe

114 to 261

1.7 to 3.8

179 to 386

2.6 to 5.6

GF02171X012

Pink

241 to 565

3.5 to 8.2

GF02172X012

Green

100 to 750

1.5 to 10.9

T14171T0012

Olive

460 to 932

6.7 to 13.5

GF02173X012

Silver

16

232

7 to 30

3 to 12 in. w.c.

ERAA05835A0

White

40 to 55

16 to 22 in. w.c.

GF02167X012

Black

45 to 76

18 to 30 in. w.c.

GF02168X012

Brown

10 to 75

4 in. w.c. to  

1.1 psig

T14169T0012

Blue

50 to 80

20 in. w.c. to 1.1 psig

62 to 132

25 in. w.c. to 1.9 psig

GF02169X012

Red

25 to 160

10 in. w.c. to 

2.3 psig

T14170T0012

Silver

83 to 221

1.2 to 3.2

GF02170X012

Orange

100 to 500

1.5 to 7.3

FA142869X12

Orange Stripe

114 to 261

1.6 to 3.8

179 to 386

2.6 to 5.6

GF02171X012

Pink

241 to 565

3.5 to 8.2

GF02172X012

Green

100 to 750

1.5 to 10.9

T14171T0012

Olive

460 to 932

6.7 to 13.5

GF02173X012

Silver

VSX4H 

VSX8H

16

232

500 to 2000

7.3 to 29.0

FA142869X12

Orange Stripe

1050 to 1570

15.2 to 22.8

GF02171X012

Pink

1250 to 2300

18.1 to 33.4

GF02172X012

Green

500 to 2800

7.3 to 40.6

T14171T0012

Olive

2100 to 3750

30.5 to 54.4

GF02173X012

Silver

 

 - 

Not available for North America.

VSX4 and VSX8 Series

4

Summary of Contents for VSX4 Series

Page 1: ...aintenance procedures performed by unqualified personnel may result in improper adjustment and unsafe operations which may result in equipment damage or personal injury The VSX4 and VSX8 Series controller do not activate in response to fire seismic and lightning events Figure 1 VSX4 and VSX8 Series Controller Introduction Scope of the Manual This Instruction Manual provides installation adjustment...

Page 2: ...ccording to PED Standards 20 to 66 C 4 to 150 F Non PED 30 to 66 C 22 to 150 F 2 Casing Material Aluminum Response Time ta 1 second Resetting Trip Mechanism Manually after Fault Rectification Position Indicator Extended stem visible in center of reset button Pressure Registration Internal or External European EN Reference Standard EN 14382 Approximate Shipping Weight 1 4 kg 3 1 lbs Options Wire Se...

Page 3: ...38 to 500 2 0 to 7 3 GF02172X012 Green 221 to 760 3 2 to 11 0 GF02173X012 Silver 400 to 1450 5 8 to 21 0 GF04353X012 Yellow VSX4H VSX8H 16 232 400 to 1100 5 8 to 16 0 GF02171X012 Pink 580 to 2000 8 4 to 29 0 GF02172X012 Green 900 to 3000 13 1 to 43 5 GF02173X012 Silver 1600 to 5500 23 2 to 79 8 GF04353X012 Yellow Figure 3 Nameplate for Explosive Atmosphere if ATEX Assembled Table 1 Directive ATEX ...

Page 4: ...LAM SHUT DEVICE Type Inlet Pressure Under Pressure Shut off UPSO UPSO Spring Over Pressure Shut off OPSO OPSO Spring Set Range Part Number Spring Color Set Range Over UPSO Setpoint Part Number Spring Color bar psig mbar psig mbar psig VSX4L VSX8L 8 6 125 7 to 11 ERAA05835A0 White 30 to 44 GF02167X012 Black 7 to 15 32 to 44 7 to 30 3 to 12 in w c 41 to 44 16 to 18 in w c 40 to 76 16 to 29 in w c GF...

Page 5: ...f OPSO Adjusting Screw Underpressure Shutoff UPSO Adjusting Screw Underpressure Shutoff UPSO Spring OVERPRESSURE Shutoff OPSO Spring ERAA10261 AA VSX8 SERIES DIAPHRAGM Cam Reset button Reset pin Valve plug Valve plug spring Downstream sense BLOCKING SCREW Overpressure Shutoff OPSO Adjusting Screw Underpressure Shutoff UPSO Adjusting Screw Underpressure Shutoff UPSO Spring OVERPRESSURE Shutoff OPSO...

Page 6: ...nstallation Instructions Note The VSX4 and VSX8 Series can be rotated 360 for easy installation and maintenance Install use and maintain in accordance to all applicable codes and standards Before proceeding to installation Ensure that the controller is compatible with the gas being regulated Check for damage that might have occurred during shipment Check for and remove any dirt or foreign material...

Page 7: ...Typical Installation Pu Pd D 4 x D Minimum Regulator Regulator Sense line Slam Shut Device Slam Shut Device Sense line RESET TRIP CLEARANCE 25 1 REMOVAL CLEARANCE 45 1 8 SPRING REMOVAL CLEARANCE 80 3 1 146 5 8 Ø 118 4 6 28 1 1 147 5 8 VSX4 and VSX8 Series 7 ...

Page 8: ...ot pull pinch or carry the VSX8 Series by the cable of contact reed Unsuitable handling of cable can damage the reed contact Description and Recommendations This electrical contact is a limit switch contact based on the reed contact principle The actuation takes place through a permanent magnet The operation of the electrical contact may be affected by magnetic materials Initial commissioning is d...

Page 9: ...pply adhesive 1 1 Adhesives must be selected such that they meet the temperature requirements 26 107 54 52 TORQUE 0 7 N m 6 2 IN LBS TORQUE 4 TO 8 N m 3 TO 6 IN LBS 30 4a 4e 105 96 A TORQUE 0 3 TO 0 55 N m 2 7 TO 4 8 IN LBS TORQUE 0 7 N m 6 2 IN LBS 106 1 VSX4 and VSX8 Series 9 ...

Page 10: ...ownstream control Line connection 23 Manual Shut Off Button Procedure For Vsx4 And Vsx8 Series Figure 10 Controller Manual Bypass 47 30 Figure 11 Relatching the Controller Mechanism 30 Figure 12 Repositioning the Reset Button 26 VSX4 and VSX8 Series 10 ...

Page 11: ...ng a screwdriver press the manual shut off button key 23 to manually trip the controller Manual Reset Procedure Figures 10 to 13 for VSX4 and VSX8 Series Caution Equipment installed downstream of the controller can be damaged if the following procedure for resetting the controller is not followed This equipment includes the integral controller regulator configurations Note An OPSO spring must be p...

Page 12: ...change registration from Internal to External and Spring and Diaphragm Replacement as described below All other internal disassembly requires special tooling and should be done only at the factory for example the cam and reset pin assembly key 4 Figure 15 Warning Only parts manufactured by Emerson should be used for repairing the VSX4 and VSX8 Series Slam shut Device Valve Plug Disk Replacement Wa...

Page 13: ...cedure Unscrew and remove the closing cap key 3 Using a flathead screwdriver unscrew and remove the OPSO adjusting screw key 43 OPSO spring key 41 maximum washer key 42 Unscrew and remove the UPSO adjusting screw key 40 mini washer key 103 and UPSO spring key 38 Using a 10 mm 3 8 in wrench unscrew and remove the eight spring case screws key 16 and associated nuts key 12 and then remove the spring ...

Page 14: ...ty nut H M6 1 FA404550X12 FA404550X12 FA404550X12 FA404550X12 32 Diaphragm Support Not Shown 1 GF01934X012 GF01934X012 38 Spring Mini 1 See Table 3 See Table 3 See Table 3 See Table 3 40 Adjustable Screw Mini 1 ERAA05947A0 ERAA05947A0 ERAA05947A0 ERAA05947A0 41 Spring Maxi 1 See Tables 2 and 3 See Tables 2 and 3 See Tables 2 and 3 See Tables 2 and 3 42 Maxi washer 1 GF01925X012 GF01925X012 GF01925...

Page 15: ...7 IN LBS torque 5 7 TO 6 2 N m 50 TO 55 IN LBS torque 0 3 TO 0 55 N m 2 7 TO 4 8 IN LBS ERCA02667 apply lubricant 1 L1 MULTI PURPOSE PTFE LUBRICANT L2 ANTI SEIZE LUBRICANT 1 Lubricants must be selected such that they meet the temperature requirements torque 0 3 to 0 55 N m 2 7 TO 4 9 IN LBS 13 8 1 28 29 47 44 9 10 15 VSX4 SERIES MANUAL BUTTON 23 24 25 22 20 21 Figure 15 Controller Assembly VSX4 an...

Page 16: ...min Regulators emerson com Emerson Automation Solutions The distinctive swirl pattern cast into every actuator casing uniquely identifies the regulator as part of the Fisher brand Commercial Service Regulator family and assures you of the highest quality engineering performance and support traditionally associated with Fisher and Tartarini regulators Visit www fishercommercialservice com to access...