11 – 10
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
Trip Message
Cause(s)
Notes
(T021) Trip: Blower 1 - High
Discharge Pressure
Blower 1 Discharge Pressure ex-
ceeds "Discharge Pressure" High Trip
Setpoint
(T022) Trip: Blower 1 - Low Suction
Pressure
Blower 1 Suction Pressure falls below
"Suction Pressure" Low Trip Setpoint
(T023) Trip: Blower 1 - High Phase A
Temperature
Phase A Motor Winding Temperature
exceeds Motor Winding
Temperature High Trip Setpoint
Active if Displaying Motor Winding
Temperatures
(T024) Trip: Blower 1 - High Phase B
Temperature
Phase B Motor Winding Temperature
exceeds Motor Winding
Temperature High Trip Setpoint
Active if Displaying Motor Winding
Temperatures
(T025) Trip: Blower 1 - High Phase C
Temperature
Phase C Motor Winding Temperature
exceeds Motor Winding
Temperature High Trip Setpoint
Active if Displaying Motor Winding
Temperatures
(T026) Trip: Blower 1 - High ODE
Bearing Temperature
Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Trip Setpoint
Active if Displaying Motor Bearing
Temperatures
(T027) Trip: Blower 1 - High DE
Bearing Temperature
Opposite Drive End Motor Bearing
Temperature exceeds Motor Bearing
Temperature High Trip Setpoint
Active if Displaying Motor Bearing
Temperatures
(T028) Trip: Blower 1 - High Motor
Amps
Blower 1 Motor Amps exceeds
"Motor Amps" High Trip Setpoint
(T029) Trip: Blower 1 - Low Oil
Pressure (Pressure Switch)
Blower 1 Actual Speed is not within
1% of commanded speed.
Active if Oil Pressure safety switch is
installed.
(T030) Trip: Blower 1 - VFD Faulted
Fault Contact on Blower 1 VFD is
open indicating Drive Fault
(T031) Trip: Blower 1 Shunt Trip
Blower 1 Motor was detected to be
running when not commanded to
run - Supplemental Shutdown out-
put is energized.
(T032) Trip:
(T033) Trip:
(T034) Trip:
(T035) Trip: Blower 1 - Oil Pump
Fault
Blower 1 external oil pump is com-
manded to run but running con
fi
r-
mation is not received.
(T036) Trip:
(T037) Trip:
(T038) Trip:
(T039) Trip:
(T040) Trip: Blower 2 - High
Discharge Temperature
Blower 2 Discharge Temperature
exceeds "Discharge Temperature"
High Trip Setpoint
(T041) Trip: Blower 2 - High
Discharge Pressure
Blower 2 Discharge Pressure ex-
ceeds "Discharge Pressure" High Trip
Setpoint
Summary of Contents for Vilter PLC
Page 1: ...Blower Package PLC Operation manual ...
Page 2: ......
Page 10: ...Blank TOC Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 18: ...1 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 30: ...3 2 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 34: ...4 4 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 42: ...5 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 48: ...6 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 54: ...7 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 62: ...9 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 68: ...10 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 117: ......