6 – 5
Section 6 • Instrument Calibration
Blower Package PLC Operation Manual •Vilter/Emerson • 35391BLP
The Other Analog Device Calibration Screen allows the
user to calibrate additional 4-20mA input devices.
4-20mA devices that can be calibrated:
• Main Motor Amperage
• Main Motor VFD Speed
CALIBRATE AN ADDITIONAL INSTRUMENT
To calibrate an additional instrument, proceed with the
following steps.
1. Enter the raw mA range (typically 4-20mA).
2. Enter the Span of the transmitter.
3. Enter minimum scale value in “XDCR Min” and full
scale value for “XDCR Max.”
Other Analog Device Calibration
Figure 6-5. Other Analog Calibration Screen
Summary of Contents for Vilter PLC
Page 1: ...Blower Package PLC Operation manual ...
Page 2: ......
Page 10: ...Blank TOC Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 18: ...1 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 30: ...3 2 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 34: ...4 4 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 42: ...5 8 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 48: ...6 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 54: ...7 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 62: ...9 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 68: ...10 6 Blank Blower Package PLC Operation Manual Vilter Emerson 35391BLP ...
Page 117: ......