1592021021 XC1008-1011-1015D GB A5 r.1.5A 12.10.2009 XC1008-1011-1015D 64/66
Nome
XC
1008
D
XC
1011
D
XC
1015
D
Level Description
Range
2Q10
-
50
50
Pr1
Safety value for Analog output 2
0 ÷ 100 (%)
2Q11
-
0
0
Pr1
Regulation delay after exit from neutral
zone
0 ÷ 255 (sec)
2Q12
-
60
60
Pr1
Analog output 2 rise time
0 ÷ 255 (sec)
2Q13
-
10
10
Pr1
Analog output 2 permanency before
load activation
0 ÷ 255 (sec)
2Q14
-
2
2
Pr1
Analog output 2 decreasing delay
0 ÷ 255 (sec)
2Q15
-
5
5
Pr1
Analog output 2 decreasing time
0 ÷ 255 (sec)
2Q16
-
5
5
Pr1
Analog output 2 permanency before
load off
0 ÷ 255 (sec)
2Q17
-
5
5
Pr1
Analog output 2 decreasing time after
load off
0 ÷ 255 (sec)
2Q18
-
4.0
4.0
Pr1
Regulation band width 2
0.10÷25.00bar; 0.0÷25.0°C; 1÷250 PSI;
1÷250°F;10÷2500 KPA
2Q19
-
350
350
Pr1
Integral time 2
0÷999s; with 0 integral action excluded
2Q20
-
0.0
0.0
Pr1
Band offset 2
-12.0÷12.0°C -12.00 ÷ 12.00BAR, -
120÷120°F, -120÷120PSI; -1200÷1200KPA
2Q21
-
4.0
4.0
Pr1
Anti reset wind-up 2
0.0÷99.0 °C; 0÷180°F; 0.00÷50,00bar;
0÷725PSI; 0÷5000kPA
2Q23
-
0
0
Pr1
Minimum capacity of inverter 2
0÷99%; with 0 function excluded
2Q24
-
255
255
Pr1
Maximum time at minimum capacity of
inverter 2
1÷255min
2Q25
-
2
2
Pr1
Time at maximum capacity of inverter 2 1÷255min
3Q1
4.20mA 4.20mA 4.20mA
Pr1
Analog outputs 3-4 setting
4.20 mA (0) - 0.10 V (1)
3Q2
nu
nu
nu
Pr1
Analog output 3 function
FREE – CPR - CPR2 - FAN - FAN2 - INVF1 -
INVF2 - nu
3Q3
Pbc3
Pbc3
Pbc3
Pr1
Probe for analog output 3
Pbc3(0); Pbc4(1); used with 3Q2 = 0
3Q4
0.0
0.0
0.0
Pr1
Lower limit for analog output 3
-1÷100.00 bar; -15÷750PSI; -50÷150°C; -
58÷302°F;
3Q5
100.0
100.0
100.0
Pr1
Upper limit for analog output 3
-1÷100.00 bar; -15÷750PSI; -50÷150°C; -
58÷302°F;
3Q6
30
50
50
Pr1
Minimum value for analog output 3
0 ÷ 100 (%)
3Q7
40
50
50
Pr1
Analog output 3 value after fan start
3Q6 ÷ 100 %
3Q8
40
70
70
Pr1
Analog output 3 value after fan off
3Q6 ÷ 100 %
3Q9
40
50
50
Pr1
Exclusion band start value 3
3Q7 ÷ 100 %
3Q10
40
50
50
Pr1
Exclusion band end value 3
3Q9 ÷ 100 %
3Q11
50
50
50
Pr1
Safety value for Analog output 3
0 ÷ 100 (%)
3Q12
0
0
0
Pr1
Regulation delay after exit from neutral
zone
0 ÷ 255 (sec)
3Q13
60
60
60
Pr1
Analog output 3 rise time
0 ÷ 255 (sec)
3Q14
10
10
10
Pr1
Analog output 3 permanency before
load activation
0 ÷ 255 (sec)
3Q15
0
0
0
Pr1
Analog output 3 decreasing delay
0 ÷ 255 (sec)
3Q16
150
15
15
Pr1
Analog output 3 decreasing time
0 ÷ 255 (sec)
3Q17
10
5
5
Pr1
Analog output 3 permanency before
load off
0 ÷ 255 (sec)
3Q18
5
5
5
Pr1
Analog output 3 decreasing time after
load off
0 ÷ 255 (sec)
3Q19
4.0
4.0
4.0
Pr1
Regulation band width 3
0.10÷25.00bar; 0.0÷25.0°C; 1÷250 PSI;
1÷250°F;10÷2500 KPA
3Q20
500
500
500
Pr1
Integral time 3
0÷999s; with 0 integral action excluded
3Q21
0.0
0.0
0.0
Pr1
Band offset 3
(-12.0÷12.0°C -12.00 ÷ 12.00BAR, -
120÷120°F, -120÷120PSI; -1200÷1200KPA
3Q22
4.0
4.0
4.0
Pr1
Anti reset wind-up 3
0.0÷99.0 °C; 0÷180°F; 0.00÷50,00bar;
0÷725PSI; 0÷5000kPA
3Q24
0
0
0
Pr1
Minimum capacity of inverter 3
0÷99%; with 0 function excluded