Unidrive M100 / M101 Control User Guide
Issue Number: 1
11.9 Behavior of the drive when tripped
If the drive trips, the output of the drive is disabled so the load coasts to a stop. If any trip occurs, the following read only parameters are frozen until
the trip is cleared. This is to help diagnose the cause of the trip.
If the parameters are not required to be frozen then this can be disabled by setting bit 4 of Pr
10.037
.
Parameter Description
01.001
Frequency reference
01.002
Pre-skip filter reference
01.003
Pre-ramp reference
01.069
Reference in rpm
01.070
Clamped reference
02.001
Post-ramp reference
03.001
Final demand ref
04.001
Current magnitude
04.002
Active current
04.017
Reactive current
05.001
Output frequency
05.002
Output voltage
05.003
Power
05.005
DC bus voltage
07.001
Analog input 1