background image

Supply 

Voltage

(VAC)

Heater 

Watts

 (W)

Max. Ambient 

Temperature

100 - 240

100 - 400

Electrical Housing

149 °F/65 °C

Regulator Body

185 °F/85 °C

44-6800 Series

DOPSM2019X012

4

All Rights Reserved.

June 2019

        WARNING

sure the vent outlet is not obstructed by rain, snow, ice, 

vegetation, insects, birds, etc. Do not interconnect vent 

lines; use separate lines if more than one vent is needed.

• 

Do not locate regulators, valves or accessories controlling 

flammable fluids near open flames or any other source of 

ignition.

• 

Some fluids when burning do not exhibit a visible flame. 

Use  extreme  caution  when  inspecting  and/or  servicing 

systems using flammable fluids to avoid death or serious 

injury to personnel. Provide a device to warn personnel of 

these dangerous conditions.

• 

Many gases can cause suffocation. Make certain the area 

is well ventilated. Provide a device to warn personnel of 

lack of Oxygen.

• 

Never  use  oil  or  grease  on  these  regulators  unless 

recommended  as  specified  in  Operations  and  Service 

procedures.  Oil  and  grease  are  easily  ignited  and  may 

combine violently with some fluids under pressure.

• 

Have  emergency  equipment  in  the  area  if  toxic  or 

flammable fluids are used.

• 

Upstream filters are recommended for use with all fluids.

• 

Do not bleed system by loosening fittings.

• 

Prevent  icing  of  the  equipment  by  removing  excess 

moisture from the gas.

• 

Always  use  proper  thread  lubricants  and  sealants  on 

tapered pipe threads.

Installation, Operations and Maintenance

Assembly & installation drawings, Bill of Materials, and parts 

lists for your product may be obtained by contacting TESCOM. 

TESCOM will provide these by email, fax or mail. Your local 

TESCOM representative can provide additional assistance. Be 

sure to have your complete model number ready. See back page 

for  contact  information  for  the  TESCOM  location  closest  to 

you.

3.1 General Information

TESCOM  44-6800E  Series  Electrically  Heated  Vaporizing 

diaphragm-sensed pressure reducing regulators are specifically 

engineered  for  applications  requiring  dependable  pressure 

regulation.  These  regulators  are  especially  appropriate  for 

installations where high system pressures (up to 6000 psi) must 

be reduced to levels suitable for actuating low pressure (0 psig/0 

bar to 500 psig/35 bar) instruments and related equipment.

In  addition,  the  44-6800E  Series  “Vaporizing”  regulator  is 

designed to offset the effects of the Joule-Thompson cooling 

effect that occurs when there is a pressure drop in a gas. It can 

also be used to vaporize a liquid into a gas in some applications.

The  electrical  board  inside  the  housing  powers  an  electrical 

heater  that  indirectly  heats  the  process  media. This  heater  is 

controlled by the electrical board for temperatures ranging from 

122 

F/50 

C to 752 

F/400 

C. There is a thermocouple within 

the  heater  core  to  provide  temperature  feedback.  There  is  a 

secondary  thermal  device,  thermal  cut  off  (TCO),  within  the 

regulator assembly.

3.1.1. Operating Parameters/Special Conditions For 

Safe Use

Maximum Inlet Pressure:

3,500 psig / 241 bar / 24,132 kPa Standard

6,000 psig / 414 bar / 41368 kPa Optional

Maximum Outlet Pressure:

500 psig / 34 5 bar / 3,448 kPa

Outlet Pressure Ranges:

0-25, 0-50, 0-100, 0-250, 0-500 psig

0-17, 0-34, 0-69, 0-172, 0-345 bar

0-172, 0-345, 0-690, 0-1724, 0-3448 kPa

Design Proof Pressure

150% maximum rated

Leakage

Internal: Bubble-tight

External: Designed to meet ≤ 2x10-8 atm cc/sec He

Voltage

100 - 240 VAC, 50/60 Hz, 400W at 240VAC, 100W at 120VAC

Full Load Amps:

2.0 Amps at 240VAC, 1.1 Amps at 120 VAC*

*Controller has 3 Amp fuse rated for 350 VAC

Flow Capacity:

CV = 0.02 - Standard

Refer to catalog and part number for options.

All cables, cable glands and conductors need >95 °C 

rating.

For integral applications the electronics enclosure 

must engage the regulator assembly by at least 5 full 

threads made wrench tight.

3.2. Installation

3.2.1. Installation Precautions

Make sure that the components and materials used 

in the fluid handling system are compatible with the 

fluid  and  have  the  proper  pressure  rating.  Failure 

to do so can result in death, serious injury and/or 

property damage.

A regulator is not intended to be used as a shutoff 

device.  When  the  regulator  is  not  in  use,  the  inlet 

Summary of Contents for Tescom 44-6800 Series

Page 1: ...l Rights Reserved Do not attempt to select install use or maintain this product until you have read and fully understood this manual 44 6800 Series 44 6800E Series Electrically Heated Vaporizing Regulator Operations Service Manual ...

Page 2: ...mation 4 3 1 1 Operating Parameters Special Conditions For Safe Use 4 3 2 Installation 4 3 2 1 Installation Precautions 4 3 3 Operation 5 3 3 1 Regulator Adjustment 5 3 3 2 Heater Temperature Controller Status 5 3 4 Maintenance and Repair Service 7 3 4 1 Repair Service 7 3 4 2 Mechanical Pressure Regulator Function 7 3 4 3 Electric Heater Function 9 4 Certifications and Warranty 10 4 1 Hazardous L...

Page 3: ...ironment codes Clearly establish flow direction of the fluid before installation of regulators valves and accessories It is the responsibility of the user to install the equipment in the correct direction Remove pressure from the system before tightening fittings gauges or components Never turn regulator or valve body Instead hold regulator or valve body and turn fitting nut Take precautions befor...

Page 4: ...plications requiring dependable pressure regulation These regulators are especially appropriate for installations where high system pressures up to 6000 psi must be reduced to levels suitable for actuating low pressure 0 psig 0 bar to 500 psig 35 bar instruments and related equipment In addition the 44 6800E Series Vaporizing regulator is designed to offset the effects of the Joule Thompson coolin...

Page 5: ... 50 to 400 C 122 to 752 F See Figure 2 NOTICE Should the thermocouple fail the analog output would read greater than 25 mA and no electrical power will be supplied to the heating element Disconnect power and check wiring j Adjust the temperature with the TRIM1 potentiometer TRIM1 potentiometer located on the electrical board provides a 270 of adjustment The temperature set point range is from 50 C...

Page 6: ... shipped separately from the regulator assembly Extra wire is provided Connectors J4 and J2 from the regulator assembly must be attached to the corresponding control board terminals For integral applications the electronics enclosure must engage the regulator assembly by at least 5 full threads made wrench tight J4 J5 J2 J1 ...

Page 7: ...Component Selection a Consider the total system design when selecting a component for use in a system b The user is responsible for assuring all safety and warning requirements of the application are met through his her own analysis and testing c TESCOM may suggest material for use with specific media upon request Suggestions are based on technical compatibility resources through associations and ...

Page 8: ...t B NOTE Upper portion of regulator includes spring button C load spring D back up plate E and diaphragm F Review correct drawing to ensure that all parts have been disassembled d Thevalvepartscannowberemovedfromtheregulator body by turning the seat retainer G counterclockwise until it is free of the regulator body Mechanical Reassembly The regulator is reassembled in the reverse order of disassem...

Page 9: ...embly drawing and bill of materials for the regulator and heater will be needed to complete maintenance procedures The assembly drawing and bill of materials are separate from this manual and available by contacting TESCOM see last page for TESCOM contact information To avoid personal injury property damage or equipment damage caused by sudden release of pressure or explosion of accumulated gas do...

Page 10: ...amb L 85 C DO NOT INSULATE ONLY USE PROVIDED MOUNTING METHODS 70174303 CL I DIV 1 GRP B C D CL II DIV I GRP E F G T3 CL I ZONE 1 AEx db IIB H2 T3 Gb ZONE 21 AEx tb IIIC T200 C Db SINGLE SEAL SEAL REQUIRED WITHIN 450MM 18 in OF THE ENCLOSURE UN SCELLEMENT DOIT ETRE INSTALLE A MOINS DE 450 MM DU BOITER 0344 G 11 2 G Ex db IIB H2 T3 Gb Ex tb IIIC T200 C Db SIRA 19ATEX1062X Ex db IIB H2 T3 Gb Ex tb II...

Page 11: ...d by the Equipment II 2GD Ex db IIB H2 T3 Gb Ex tb IIIC T200 C Db Approved by the following notified body Sira Certification Service Unit 6 Hawarden Industrial Park Hawarden CH5 3US United Kingdom Harmonized Standards EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 On behalf of the above named company I declare that to which this declaration relates is in conformity with the provisions of the...

Page 12: ...the firmware of services or repair or replace F O B point of manufacture that portion of the goods or firmware found by Seller to be defective or refund the purchase price of the defective portion of the goods services All replacements or repairs necessitated by inadequate maintenance normal wear and usage unsuitable power sources or environmental conditions accident misuse improper installation m...

Page 13: ...on com www tescom com MIDDLE EAST AFRICA PO Box 17033 Jebel Ali Free Zone South Zone 2 Dubai UAE T 971 4 811 8443 F 971 4 886 5465 mea tescom emerson com www tescom com DOPSM2019X012 TESCOM Corporation 2015 All Rights Reserved TESCOM is a business unit of Emerson Process Management Regulator Technologies Inc Trademarks are property of divisions of Emerson Process Management The contents of this pu...