Quick Installation Guide
00825-0100-4420, Rev DA
July 2009
1420 Wireless Gateway
13
S
TEP
4
CONTINUED
...
Installation of the WL3/WL4 Option:
1. Mount the antenna on a 2-in. (0.05 m) pipe mast using the supplied equipment.
2. Mount the lightning arrestor using the supplied equipment, minimizing the distance
between it and the building egress for optimal lightning protection.
3. Use the LMR-400 coaxial cables to connect the Gateway, lightning arrestor, and
antenna.
4. Seal each connection between the Gateway, lightning arrestor, cables, and antenna with
the weather proof tape.
Any spare lengths of coaxial cable should be placed in 12-in. (0.3 m) coils.
Ensure that the mounting mast and lightning arrestor are grounded in accordance with
local/national electrical codes.
Example of Mounting a Remote Antenna
Ground to Lightning Arrestor
Control/Equipment Room
Remote Antenna
outside of enclosure
Ground to Gateway
Lightning Arrestor
Antenna mounted
6 ft. (2 m) above
obstruction or major
infastructure
0 ft. (0 m)
6 ft. (2 m)
Gateway Inside
the Building
Cable
Cable
Cable
Building Egress