SI-PROFINET RT User Guide
37
Issue Number: 2
Saf
ety
In
M
El
G
A
Pa
ra
Dia
gnos
G
Module error codes
If the option module detects an internal error during operation, it will force a trip on the
drive and provide a sub-trip string for a clearer definition of the trip. The table below
shows the possible module error codes.
Trip
Description
SlotX HF
The drive has detected that an option module is present but is unable
to communicate with it due to a hardware fault.
SlotX Error
User trip generated by the option module
SlotX Not Fitted This trip will occur if a drive slot was previously configured with an
option module but on power up, no option module was detected.
SlotX Different
This trip will occur if a drive slot was previously configured with an
option module but on power up, a different option module was
detected. Replacing the option module with another one of the same
ID number will not initiate this trip.
The trip will also occur if an option module is installed to a previously
unused slot.
Value
Text
Description
200
Software Fault
Software Fault
201
BG Overrun
Background task overrun
202
Firmware Invalid
Invalid firmware for hardware version
203
Drive Unknown
Unknown drive type
204
Drive Unsupported
Unsupported drive type
205
Mode Unknown
Unknown drive mode
206
Mode Unsupported
Unsupported drive mode
207
FLASH Error
Corrupted Non-volatile FLASH
208
Database Init
Database initialization error
209
File System Init
File system initialization error
210
Mem Allocation
Memory allocation error
211
Filesystem Error
File system error
212
Config Save
Configuration file save error
213
Over Temperature
Overheated
214
Drive Timeout
the drive has not responded within watchdog period
215
eCMP Comms Error
eCMP communication failure
216
TO eCMP Slot1
eCMP communication to slot 1 timeout
217
TO eCMP Slot2
eCMP communication to slot 2 timeout
218
TO eCMP Slot3
eCMP communication to slot 3 timeout
219
Reserved Reserved
220
Reserved Reserved
221
Factory Settings
Missing factory settings
222
Functional Test
Functional test failure
223
Config Restore
Configuration file restore error
224
Self Test Error
Power on self test error
225
Runtime Config
Runtime configuration error