34
SI-PROFINET RT User Guide
Issue Number: 2
This parameter defines the time period in which the module must receive a cyclic data
frame from the controller before any specified action is performed. Default timeout
value is 100 ms and it is over-written by the controller when a connect request is
received.
This parameter defines the action to take when no cyclic message frame is received
within the time period specified by the timeout value in Pr
S.05.009
. All possible values
are shown in the table below.
S.05.009
Timeout
Minimum
1
Maximum
10000
Default
100
Units
ms
Type
16 Bit volatile
Update Rate
Connect request from
controller
Display Format
None
Decimal Places
0
Coding
RW, PT, BU
S.05.010
Timeout Action
Minimum
0
Maximum
4
Default
4
Units
Type
8 Bit User Save
Update Rate
Module reset /
initialization
Display Format
Text
Decimal Places
0
Coding
RW, BU
Value Text
Description
0
Trip
Trip drive with corresponding trip
1
SendFaultValues Send configured fault values to output mappings
2
Clear output
PLC output parameter will have their values set to zero
3
Hold last
Hold the last value in output parameters
4
No action
No action