21
RSTi-EP CPE200 Series Controllers Quick Start Guide
GFK-3109B
Controller Start-up
Required Components
•
EPXCPE200 controller
•
Power for this equipment this equipment shall be provided by one
or two independent power supplies that provide an SELV source
with a minimum 32 V dc listed fuse with 10A max rating for each
independent power rail. The 4-pole pluggable terminal block for the
power input and output terminal block header located on the front
is installed on the connection frame that is shipped with the
package. This mating connector accepts wire sizes 26 to 16 AWG
(0.361 mm to 1.29mm). Strip the insulation from the lines to a
length of approx. 0.4 in ± 0.04 in (10 mm ± 1 mm), (even if you are
using wire-end ferrules. If you use wire-end ferrules with plastic
collars, strip the wires to 0.5 in ± 0.04 in (12 mm ± 1 mm). To insert
fine stranded wires without wire-end ferrules, the pusher must be
pressed in with a screwdriver and released to latch the wire
•
The temperature rating for copper wire: 80 °C. Wiring should be
stripped before connecting to the mating connector and cannot
exceed 30
m in length
•
A DIN rail, typically mounted in an enclosure
•
A computer running PAC Machine Edition (PME) configuration and
programming software. PME Version 10
.
00.0.9413.
Ethernet cable for connecting the programming computer running
PME to the EPXCPE controller.