RSTi-EP CPE200 Series Controllers Quick Start Guide 

GFK-3109B 

Controller Start-up  

Required Components  

 

EPXCPE200 controller 

 

 

Power for this equipment this equipment shall be provided by one 
or two independent power supplies that provide an SELV source 
with a minimum 32 V dc listed fuse with 10A max rating for each 
independent power rail. The 4-pole pluggable terminal block for the 
power input and output terminal block header located on the front 
is installed on the connection frame that is shipped with the 
package. This mating connector accepts wire sizes 26 to 16 AWG 
(0.361 mm to 1.29mm). Strip the insulation from the lines to a 
length of approx. 0.4 in ± 0.04 in (10 mm ± 1 mm), (even if you are 
using wire-end ferrules. If you use wire-end ferrules with plastic 
collars, strip the wires to 0.5 in ± 0.04 in (12 mm ± 1 mm).  To insert 
fine stranded wires without wire-end ferrules, the pusher must be 
pressed in with a screwdriver and released to latch the wire 

 

 

The temperature rating for copper wire: 80 °C. Wiring should be 
stripped before connecting to the mating connector and cannot 
exceed 30

m in length 

 

 

A DIN rail, typically mounted in an enclosure 

 

 

A computer running PAC Machine Edition (PME) configuration and 
programming software. PME Version 10

.

00.0.9413.

 

 

 

Ethernet cable for connecting the programming computer running 

PME to the EPXCPE controller.  

 

 

Summary of Contents for RSTi-EP CPE200 Series

Page 1: ...intended to be printed in color as a 5 5 width x 6 5 inch length booklet with stapled binding Use high quality glossy 20lb 75 g m paper Print double sided Fold sheet of 8 5 x 11 in two trim length and staple spine The European version can use A4 in place of 8 5 x 11 ...

Page 2: ...RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Dec 2022 ...

Page 3: ...onnectors and Ports 8 DIN Rail Installation 15 Thermal Requirements 20 Controller Start up 21 Required Components 21 Basic Installation Steps 22 LED Behavior During Startup 23 Installation in Hazardous Areas 24 Network Configuration 24 Update Firmware Webpage Password 29 Reset to Factory Defaults 30 Removable Data Storage Device RDSD 31 Periodic Maintenance 32 Additional Information 33 General Con...

Page 4: ...h the carrier for damage incurred during shipment Emerson will fully cooperate with you however should such action be necessary After unpacking the equipment record all serial numbers Serial numbers are required if you should need to contact Customer Care during the warranty period All shipping containers and all packing material should be saved should it be necessary to transport or ship any part...

Page 5: ...2 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Front Panel Description Figure 1 Front Panel View of EPXCPE205 ...

Page 6: ...3 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 2 Front Panel View of EPXCPE210 215 220 240 ...

Page 7: ... Run Outputs Enabled RUN DIS RUN STOP Switch PLC in Run Outputs Disabled STOP RUN STOP Switch PLC in Stop PHY PRES RDSD Physical Presence RDSD Button for Physical Presence actions i e password change RDSD and reset to factory defaults RDSD Single press to perform an upload RDSD Double press to perform a download Is used to initiate Reset to Factory Default Settings µSD Micro SD card Port for the m...

Page 8: ...lled by the PHY There are two LEDs per port one for Link Speed LNK and one for Activity ACT Ethernet LinkSpeed LNK o GREEN indicates 1 Gbps o AMBER indicates 100 Mbps o OFF indicates 10 Mbps currently not supported per spec Ethernet Activity ACT o GREEN indicates Link o BLINKING GREEN indicates activity on the link Figure 2 3 Position Switch RUN EN RUN DIS STOP ...

Page 9: ...g in unison Reset to factory defaults RUN REM IO Green flashing in unison Programmable parts update RUN Green steady The controller is running with I O outputs enabled Green flashing Fatal error blink code during power up Amber steady The controller is running with I O outputs disabled REM IO Green steady All PROFINET devices connected Green flashing Unit is starting up see LED power up sequence A...

Page 10: ...Operation completed successfully Green flashing RDSD download operation in progress Amber flashing RDSD upload operation in progress Red steady The controller is in a Stop Fault state Red flashing RDSD has failed Red flashing If RDSD is not being performed indicates IP conflict detected DUAL LAN EPXCPE205 only Green steady Dual LAN operating mode Off Single LAN operating mode ...

Page 11: ...tors and Ports Ethernet Ports The following tables indicate the default IP address for each ethernet port Important When storing a hardware configuration with a new IP address to the PACSystems controller while connected via Ethernet the connection will succeed and then immediately disconnect because the PACSystems controller is now using a different IP address than the programmer The user must en...

Page 12: ...sk 255 255 255 0 Gateway 0 0 0 0 EPXCPE205 Dual LAN Mode Port 1 Port 2 Default IP Address 192 168 0 100 10 10 0 100 Subnet Mask 255 255 255 0 Gateway 0 0 0 0 Dual LAN Mode is the default configuration for the EPXCPE205 EPXCPE210 215 220 240 Port 1 Port 2 Port 3 Port 4 Default IP Address 10 10 0 100 192 168 0 100 N A Subnet Mask 255 255 255 0 Gateway 0 0 0 0 ...

Page 13: ... 6 TXD Transmit Data 7 CTS Clear to Send 8 RTS Request to Send Power Connectors Supply Supply voltage for system and inputs 20 4 V 28 8 V Supply voltage for outputs 20 4 V 28 8 V Max feed in current for input modules including current for RSTI EP internal 5V DC 1 5A 24V 8 5 A 1 5 A Max feed in current for output modules 10 A Current consumption from system current path ISYS 116 mA Connection data ...

Page 14: ...Connection LEDs PWR LED Green Supply voltage 18Vdc Red At least one current path 18 V 1 Green Input current path supply voltage 17 V D 2 Red Input current path supply voltage 17 V DC 3 Blue Ground 4 Blue Ground 1 Green Output current path supply voltage 17 V DC 2 Red Output current path supply voltage 17 V DC 3 Blue Ground 4 Blue Ground ...

Page 15: ...12 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 3 Power Feed Minimum Current Draw ...

Page 16: ...13 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 4 Power Feed Maximum Current Draw ...

Page 17: ... up to Version 3 0 The card formatting is required to be either FAT or FAT32 with MBR partitioning Insert the card into the slot oriented as described below Apply pressure on it until you feel some resistance The card will latch into place and can then be read by the equipment To remove apply pressure again to eject the card from the slot Figure 5 MicroSD Card Note The MicroSD card needs to be ins...

Page 18: ...rs Quick Start Guide GFK 3109B DIN Rail Installation 1 Begin by releasing the three closed levers located on the top of the CPE200 controller Pull the levers toward the face of the controller to the open position Figure 3 Release Levers ...

Page 19: ...STi EP CPE200 Series Controllers Quick Start Guide GFK 3109B 2 Attach the controller to the DIN rail The controller should rest on the rail but be able to move freely side to side Figure 4 Mount to DIN Rail ...

Page 20: ... Controllers Quick Start Guide GFK 3109B 3 Slide the controller along the DIN rail into place The controller should be in the left most position and rest against a stop block if applicable Figure 5 Slide Controller to the Left ...

Page 21: ...t Guide GFK 3109B 4 Repeat the steps for each of the IO modules Connect the first IO module into connectors on the right side of the controller Each subsequent IO module will connect to the previous module Figure 6 Slide and Connect Each I O Module ...

Page 22: ...Controllers Quick Start Guide GFK 3109B 5 After all the I O modules have been connected mount the protective endplate into the last I O module to protect the exposed connectors Figure 7 Slide the End Plate into the Last Module ...

Page 23: ...20 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Thermal Requirements Figure 14 Minimum Distance Requirements ...

Page 24: ...16 AWG 0 361 mm to 1 29mm Strip the insulation from the lines to a length of approx 0 4 in 0 04 in 10 mm 1 mm even if you are using wire end ferrules If you use wire end ferrules with plastic collars strip the wires to 0 5 in 0 04 in 12 mm 1 mm To insert fine stranded wires without wire end ferrules the pusher must be pressed in with a screwdriver and released to latch the wire The temperature rat...

Page 25: ...EPXCPE to a DIN rail as outlined in section DIN Rail Installation 2 Connect the EPXCPE to the power supply 3 Plug the Ethernet cable from the programmer computer the computer that runs PAC Machine Edition into Port 3 For the EPXCPE205 connect the Ethernet cable to Ports 1 or 2 4 Plug the Ethernet cable for the PROFINET network into Port 1 or Port 2 5 Apply power to the EPXCPE ...

Page 26: ...pply power to the EPXCPE The controllers will require several seconds to power up Power up LED Sequence 1 The CPU s REM IO LED will blink GREEN when the power is applied before turning it off 2 The RUN LED will turn solid GREEN before turning it off 3 The OK LED will turn solid GREEN and remain on Figure 8 LED Illumination Sequence ...

Page 27: ...ormation regarding default IP addresses please consult the section Ethernet Ports EPXCPE205 The EPXCPE205 operating mode can be configured for Single LAN mode or Dual LAN mode The default operating mode is Dual LAN mode Single LAN Mode All protocols including MRP will be supported Dual LAN LED will be OFF Dual LAN Mode LAN 2 port 2 All protocols are supported except PROFINET MRP Dual LAN LED will ...

Page 28: ...25 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 6 Single LAN Mode ...

Page 29: ...26 RSTi EP CPE200 Series Controllers Quick Start Guide GFK 3109B Figure 7 Dual LAN Mode ...

Page 30: ...ries Controllers Quick Start Guide GFK 3109B EPXCPE210 215 220 240 LAN 1 Port 3 Unswitched All protocols are supported except PROFINET LAN 2 Ports 1 and 2 Switched All protocols are supported Figure 8 Network Configuration ...

Page 31: ...roller and IO faults will remain 1 Begin by navigating to the controller web page by entering the IP address of the LAN you are connected to into the web browser 2 At the top right of the page select the Operating Mode tab and select Change Operating Mode 3 Once redirected to the change operating mode page select the operating mode you wish to configure Note if the user selects the operating mode ...

Page 32: ...e GFK 3109B Update Firmware Webpage Password Login to the webpage and select Administrator and follow the process of changing the password The webpage password can be updated while the PLC is in all modes Run IO enabled Run IO disabled Stop or Stop Fault ...

Page 33: ... by pressing the Physical Presence button PHY PRES for 10 seconds The OK LED and RUN LEDs will blink GREEN indicating the Reset to Factory is occurring 2 Release the PHY PRES button 3 Blinking will cease and the board will be reset 4 The following actions will result a Resets the IP addresses to their factory defaults shown in section Ethernet Ports b Resets the Web page firmware password to its d...

Page 34: ...n application may be cloned and copied from one device to another If the USB device in use already has a PACS_folder user program and a single press of the pushbutton occurs a backup of the existing PACS_folder is made PACS_folder_backup and then the upload occurs If the archive already exists on the USB device a new archive will be created and the upload will take place If one needs to restore th...

Page 35: ...initial installation Should the RTC battery fail the CPU date and time will reset to 12 00 AM 01 01 2001 at start up The CPU operates normally with a failed or missing RTC battery however the initial CPU time of day TOD clock information will be incorrect To replace the RTC battery and reset the RTC time refer to the RX3i RSTi EP CPU Reference Manual GFK 2222AS or later Battery required Lithium 3v...

Page 36: ...thernet Communications Station Manager Manual GFK 2225 PACSystems RXi RX3i and RSTi EP Controller Secure Deployment Guide GFK 2830 PACSystems RX3i and RSTi EP CPU Programmer s Reference Manual GFK 2950 PACSystems HART Pass Through User Manual GFK 2929 PACSystems RX3i PROFINET IO Controller User Manual GFK 2571 PROFINET I O Devices Secure Deployment Guide GFK 2904 PACSystems DNP3 Outstation User Ma...

Page 37: ...1 Your request should include i the name of the covered binary ii the version number of the product containing the covered binary iii your name iv your company name if applicable and v your return mailing and email address This offer is valid for three 3 years after the date of the last distribution of this particular version of this product For any code in this product covered by version 3 of the...

Page 38: ... Reserved We reserve the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson product remains solely with the purchaser 2022 Emerson Electric Co ...