3. Do not change the battery when an explosive atmosphere is present.
4. Only replace battery with Rosemount Part No. 00G45-9000-0001.
International
I7
IECEx Intrinsic Safety
Certificate:
IECEx BAS 16.0012X
Standards:
IEC 60079-0: 2011, IEC 60079-11: 2011
Markings:
Ex ia IIC T4 Ga, T4 (–40 °C ≤ T
a
≤ +70 °C) IP66/67;
Special Conditions for Safe Use (X):
1. The plastic enclosure may constitute a potential electrostatic ignition
risk and must not be rubbed or cleaned with a dry cloth.
2. The measured capacitance between the equipment enclosure and
metallic inline sensor module is 4.7pF. This must be considered only
when the SPG is integrated into a system where the process
connection is not grounded.
3. Do not change the battery when an explosive atmosphere is present.
4. Only replace battery with Rosemount Part No. 00G45-9000-0001.