Table 3-2: Results of a Successful Flame Simulator Test
Component
Action
Notes
0-20 mA
Turns to 20 mA
For a few seconds and then
returns to 4 mA
Alarm relay
Activated
For a few seconds and then
returns to Normal
Auxiliary relay
Activated
For a few seconds and then
returns to Normal
Fault relay
Remains active during the test
LED
Red, steady
The detector is now ready for operation.