87
Reference Manual
00809-0300-4750, Rev CA
Advanced Configuration Functionality
March 2016
Advanced Configuration Functionality
Alarm level
The
alarm level
configuration will drive the transmitter to preset values if an alarm occurs.
There are two options:
Rosemount Alarm and Saturation Values (see table
for specific values)
NAMUR-Compliant Alarm and Saturation Values (see
for specific values)
AO diagnostic alarm
There are diagnostics that, when under active conditions, do not drive the analog output to
alarm level. The
AO diagnostic alarm
menu enables selection of these diagnostics to be
associated with an analog alarm. If any of the selected diagnostics are active, it will cause
the analog output to go to the configured alarm level. For a list of diagnostic alarms that can
be configured to drive an analog alarm, see
.
LOI menu path
Field Mount: Detailed Setup, Output Config, Analog, Alarm Level
Wall Mount: AUX. FUNCTION
Traditional Fast Keys
1, 4, 2, 1, 8 or 1, 4, 2, 6
Device dashboard
2, 2, 9, 5, 2
Table 5-1. Rosemount Values
Level
4-20 mA saturation
4-20 mA alarm
Low
3.9 mA
3.75 mA
High
20.8 mA
22.5 mA
Table 5-2. NAMUR Values
Level
4-20 mA saturation
4-20 mA alarm
Low
3.8 mA
3.5 mA
High
20.5 mA
22.6 mA
LOI menu path
Field Mount: Detailed Setup, Output Config, Analog, AO Diag
Alarm
Wall Mount: AUX. FUNCTION
Traditional Fast Keys
1, 4, 2, 1, 9
Device dashboard
2, 2, 5, 9
Table 5-3. Analog Alarm Diagnostic Options
Diagnostic
LOI menu path
Fast Keys
Description
Empty Pipe
(1)
Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Empty Pipe
1, 4, 2, 1, 9, 1
Drive to an alarm state when
empty pipe is detected.
Reverse Flow
Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Reverse
Flow
1, 4, 2, 1, 9, 2
Drive to an alarm state when
reverse flow is detected.
Summary of Contents for Rosemount 8750W
Page 2: ......
Page 96: ...84 Reference Manual 00809 0300 4750 Rev CA Operation March 2016 Operation ...
Page 168: ...156 Reference Manual 00809 0300 4750 Rev CA Maintenance March 2016 Maintenance ...
Page 214: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 202 Wiring Diagrams ...
Page 218: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 206 Wiring Diagrams ...
Page 219: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 207 Wiring Diagrams ...
Page 220: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 208 Wiring Diagrams ...
Page 222: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 210 Wiring Diagrams ...
Page 223: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 211 Wiring Diagrams ...
Page 224: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 212 Wiring Diagrams ...
Page 225: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 213 Wiring Diagrams ...
Page 227: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 215 Wiring Diagrams ...
Page 228: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 216 Wiring Diagrams ...
Page 229: ...Wiring Diagrams March 2016 Reference Manual 00809 0300 4750 Rev CA 217 Wiring Diagrams ...
Page 263: ......