![Emerson Rosemount 8700 Series Quick Installation Manual Download Page 31](http://html.mh-extra.com/html/emerson/rosemount-8700-series/rosemount-8700-series_quick-installation-manual_101037031.webp)
Quick Installation Guide
00825-0100-4727, Rev CC
January 2013
Rosemount 8700 Series
30
Table 11. Electrical Data
Rosemount 8705 and 8711 Sensors
Coil excitation circuit:
40 V, 0,5 A, 20 W maximum
Electrode circuit:
in type of explosion protection intrinsic safety EEx ia IIC, U
i
= 5 V, l
i
= 0.2 mA,
P
i
= 1 mW, U
m
= 250 V
Table 12. Relation between ambient temperature, process temperature, and temperature class
(1)
(1)
This table is applicable for E1 and KD approval codes only.
Meter Size (Inches)
Maximum Ambient Temperature
Maximum Process
Temperature
Temperature
Class
1
/
2
149 °F (65 °C)
239 °F (115 °C)
T3
1
149 °F (65 °C)
248 °F (120 °C)
T3
1
95 °F (35 °C)
95 °F (35 °C)
T4
1
1
/
2
149°F (65 °C)
257 °F (125 °C)
T3
1
1
/
2
122 °F (50 °C)
140 °F (60 °C)
T4
2
149 °F (65 °C)
257 °F (125 °C)
T3
2
149 °F (65 °C)
167 °F (75 °C)
T4
2
104 °F (40 °C)
104 °F (40 °C)
T5
3 - 4
149 °F (65 °C)
266 °F (130 °C)
T3
3 - 4
149 °F (65 °C)
194 °F (90 °C)
T4
3 - 4
131 °F (55 °C)
131 °F (55 °C)
T5
3 - 4
104 °F (40 °C)
104 °F (40 °C)
T6
6
149 °F (65 °C)
275 °F(135 °C)
T3
6
149 °F (65 °C)
230 °F (110 °C)
T4
6
149 °F (65 °C)
167 °F (75 °C)
T5
6
140 °F (60 °C)
140 °F (60 °C)
T6
8-60
149 °F (65 °C)
284 °F (140 °C)
T3
8-60
149 °F (65 °C)
239 °F (115 °C)
T4
8-60
149 °F (65 °C)
176 °F (80 °C)
T5
8-60
149 °F (65 °C)
149 °F (65 °C)
T6
4727_revCC_QIG.fm Page 30 Thursday, January 10, 2013 6:08 PM
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com