Block Information
37
Block Information
January 2018
Reference Manual
00809-0100-4377, Rev CA
Block errors
The table below lists conditions reported in the BLOCK_ERR parameter.
Modes
The resource block supports two modes of operation as defined by the MODE_BLK parameter:
Automatic (Auto)
The block is processing its normal background memory checks.
Out of service (OOS)
The block is not processing its tasks. When the resource block is in OOS, all blocks within the resource (device) are forced
into OOS. The BLOCK_ERR parameter shows Out of Service. In this mode, changes can be made to all configurable
parameters. The target mode of a block may be restricted to one or more of the supported modes.
Table B-2. BLOCK_ERR Conditions
Number Name and description
0
Other
1
Block Configuration Error: A feature in CYCLE_SEL is set that is not supported by CYCLE_TYPE.
3
Simulate Active: This indicates that the simulation jumper is in place. This is not an indication that the I/O blocks are using
simulated data.
6
Device needs maintenance soon
7
Input failure/process variable has bad status
9
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory.
10
Lost Static Data: Static data that is stored in non-volatile memory
has been lost.
11
Lost NV Data: Non-volatile data that is stored in non-volatile memory
has been lost.
13
Device Needs Maintenance Now
14
Power Up: The device was just powered-up.
15
OOS: The actual mode is out of service.
Summary of Contents for Rosemount 752 FOUNDATION
Page 2: ......
Page 6: ...6 Reference Manual 00809 0100 4377 Rev CA Title Page January 2018 Title Page ...
Page 8: ...2 Reference Manual 00809 0100 4377 Rev CA Introduction January 2018 Introduction ...
Page 28: ...22 Reference Manual 00809 0100 4377 Rev CA Configuration January 2018 Configuration ...
Page 47: ......