29
Reference Manual
00809-0100-4377, Rev CA
Troubleshooting
January 2018
Troubleshooting
4.4
Resource block
This section describes error conditions found in the Resource block. Read
determine the appropriate corrective action.
Block errors
lists conditions reported in the BLOCK_ERR parameter.
Table 4-2. Resource Block BLOCK_ERR Messages
Table 4-3. Resource Block Extended Status (FD_EXTENDED_ACTIVE_1) with Recommended Action
Messages
Condition Name and Description
Other
Simulate active: this indicates that the simulation switch is in place. this is not an indication that the i/o
blocks are using simulated data.
Memory failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Device needs maintenance now
Out of service: the actual mode is out of service.
Condition name
Recommended action
LOI error
1. Restart processor
2. Check display connection
3. Call service center
Manufacturing Block integrity error
1. Restart processor
2. Call service center
NV integrity error
1. Restart processor
2. Call service center
ROM integrity error
1. Restart processor
2. Call service center