Quick Start Guide

00825-0100-4520, Rev AC

February 2019

Rosemount

 520 Level Transmitter

00825-0100-4520_RevAC.fm  Page 1  Thursday, February 7, 2019  10:16 AM

Summary of Contents for Rosemount 520

Page 1: ...Quick Start Guide 00825 0100 4520 Rev AC February 2019 Rosemount 520 Level Transmitter 00825 0100 4520_RevAC fm Page 1 Thursday February 7 2019 10 16 AM ...

Page 2: ...codes and practices Review approvals section of the Rosemount 520 Reference Manual for any restrictions associated with a safe installation Before connecting a HART based communicator in an explosive atmosphere make sure the instruments in the loop are installed in accordance with intrinsically safe or non incentive field wiring practices Electrical shock can result in death or serious injury Avoi...

Page 3: ...isted pair of wires Multidrop installation requires consideration of the update rate necessary from each transmitter the combination of transmitter models and the length of the transmission line For more information reference Connect wiring and power up on page 13 1 2 Configuration tools There are several tools that can be used to configure the Rosemount 520 The Field Communicator is a portable ha...

Page 4: ...3 0 Mount the transmitter Note All installation methods described in the following sections are grounded If a different installation method is used the transmitter must be grounded to meet EMC and hazardous location requirements 3 1 Internal mounting 1 Secure the bracket to the tank wall 2 Secure the transmitter by use of the provided spring The spring is fitted into the two holes in the bracket T...

Page 5: ...n Drawing A Optional junction box B Optional bulkhead fitting C Dead zone D Lowest tank bottom E Transmitter F Mounting bracket G Mounting spring A B C D F E G 38 Ø 12 55 125 160 50 41 194 5 00825 0100 4520_RevAC fm Page 5 Thursday February 7 2019 10 16 AM ...

Page 6: ...nut and gasket The recommended torque is 20 N m Figure 2 Installation Drawing A Optional junction box B Tank top C Dead zone D Lowest tank bottom E Transmitter F Pipe max length 2000 mm yard supply G Gasket H Welding nipple for pole length 40 mm I 1 in end cap A B C D F E H I G 34 26 40 30 193 24 26 41 00825 0100 4520_RevAC fm Page 6 Thursday February 7 2019 10 16 AM ...

Page 7: ...pe by use of the provided nut and gasket The recommended torque is 20 N m Figure 3 Installation Drawing A Optional junction box B Tank top C Dead zone D Tank bottom E Vent pipe F Gasket G Nut H Nipple pipe length 80 mm I Transmitter J Ball valve yard supply A B C D E F J H G I 34 26 30 25 55 80 193 24 26 41 00825 0100 4520_RevAC fm Page 7 Thursday February 7 2019 10 16 AM ...

Page 8: ...d torque is 20 N m Note Emerson recommends installing a ball valve between the tank wall and transmitter to facilitate transmitter service and maintenance Figure 4 Installation Drawing A Optional junction box B Refer to Table 1 C Tank top D Refer to Table 1 E Dead zone F Tank bottom G Vent pipe H Flange I Gasket J Transmitter K Refer to Table 1 L Nipple pipe connector C A G F E I D K B H L J d 008...

Page 9: ...andard D mm B mm K mm d x n mm DN25 PN16 115 16 85 14 x 4 DN40 PN16 150 18 110 18 x 4 JIS25A 16K 125 14 90 19 x 4 JIS40A 16K 140 16 105 19 x 4 1 in ANSI 150 108 16 79 16 x 4 11 2 in ANSI 150 127 17 5 98 6 16 x 4 00825 0100 4520_RevAC fm Page 9 Thursday February 7 2019 10 16 AM ...

Page 10: ... 5 Installation Drawing A Optional junction box B Refer to Table 2 C Tank top D Refer to Table 2 E Dead zone F Tank bottom G Vent pipe H Flange I 1 in ball valve J 1 in nipple pipe connector 1 to 1 in K Refer to Table 2 L Gasket M 1 in nut N Transmitter Table 2 Flange Size for Flange with 1 in Ball Valve Standard D mm B mm K mm d x n mm DN25 PN16 115 16 85 14 x 4 JIS25A 16K 125 14 90 19 x 4 1 in A...

Page 11: ...gure 6 Installation Drawing A Optional junction box B Refer to Table 3 C Tank top D Refer to Table 3 E Dead zone F Lowest tank bottom G Transmitter H Washer I Tightening clip J Rubber tube K Refer to Table 3 L Flange M Cable gland PG11 DIN 89280 Table 3 Flange Size for Flexible Rubber Tube and PTFE Tube Standard D mm B mm K mm d x n mm DN50 PN16 165 19 125 18 x 4 JIS50A 16K 155 20 120 19 x 4 2 in ...

Page 12: ... recommended minimum tube bending radius is 130 mm Figure 7 Installation Drawing A Optional junction box B Refer to Table 3 C Tank top D Refer to Table 3 E Dead zone F Lowest tank bottom G Transmitter H Spacer I HY Lok nut and ferrules J HY Lok fitting with nut and ferrules K Refer to Table 3 L Hydraline SV 1 2 in PTFE hose braided with stainless steel M Hydraline SB hose jacket N Hose fitting wit...

Page 13: ...itter cable The vent tube must be directed to an area with atmospheric pressure If the transmitter cable terminates in an area with overpressure or negative pressure relative to the atmospheric pressure in the tank the vent tube must be directed to an area with atmospheric pressure equal to the pressure inside the tank 4 3 Power supply The power supply and load limitations are described in Figure ...

Page 14: ...on requires a minimum loop resistance of 250 ohm 4 4 Wiring diagrams Figure 9 Point to Point A Field Communicator or PC with HART modem B Rosemount 520 Table 5 Load Resistance and Voltage Supply Limits Parameter Limit R1 250 R2 1130 Vmin V 10 V1 V 15 75 V2 V 36 A B 00825 0100 4520_RevAC fm Page 14 Thursday February 7 2019 10 16 AM ...

Page 15: ...Quick Start Guide 15 February 2019 Figure 10 Multidrop A Field Communicator or PC with HART modem B Rosemount 520 A B B B 00825 0100 4520_RevAC fm Page 15 Thursday February 7 2019 10 16 AM ...

Page 16: ...re information Fast Key sequences for the latest DD are shown below in Table 6 A check indicates the basic configuration parameters At minimum these parameters should be verified as part of configuration and startup Table 6 Fast Key Sequences Device Revision 2 DD Revision 1 Function Fast Key sequence Alarm and Saturation Levels 2 2 2 5 7 Damping 2 2 1 1 5 Range Values 2 2 2 Tag 2 2 6 1 1 Units 2 2...

Page 17: ...nsate for mounting position When performing a zero trim ensure the vent tube is vented to atmospheric pressure 6 1 Zero trim using the Field Communicator 1 Connect the Field Communicator see Connect wiring and power up on page 13 for instructions 2 At the main menu input the 3 4 1 3 Fast Key sequence 3 Follow the commands to perform a zero trim 00825 0100 4520_RevAC fm Page 17 Thursday February 7 ...

Page 18: ...he free ends of the cable must be afforded a degree of protection of at least IP20 3 The optional polyester junction box present a potential electrostatic ignition risk and must not be rubbed or cleaned with a dry cloth Installation in Hazardous Locations When installing the Rosemount 520 in hazardous areas to reduce the risk of electrostatic charges the resistance of the titanium transducer to ea...

Page 19: ...can Bureau of Shipping ABS Type Approval Certificate 15 HS1462157 PDA Intended Use Marine Offshore Applications Pressure transmitter used for determining tank levels SBV Bureau Veritas BV Type Approval Certificate 43940 Requirements Bureau Veritas Rules for the Classification of Steel Ships Application Class notations AUT UMS AUT CCS AUT PORT and AUT IMS Pressure transmitter type 520 cannot be ins...

Page 20: ... MN 55317 9685 USA to which this declaration relates is in conformity with the provisions of the European Union Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of the harmonized standards and when applicable or required a European Union notified body certification as shown in the attached schedule signature Vice Pres...

Page 21: ...il 19 April 2016 ATEX Directive 2014 34 EU This directive is valid from 20 April 2016 Baseefa15ATEX0075X Intrinsic Safety Equipment Group II Category 1 G Ex ia IIC T4 Ga Harmonized Standards EN60079 0 2012 A11 2013 EN60079 11 2012 ATEX Notified Bodies SGS FIMCO OY Notified Body Number 0598 P O Box 30 Särkiniementie 3 00211 HELSINKI Finland ATEX Notified Body for Quality Assurance SGS FIMCO OY Noti...

Page 22: ...warranties or guarantees expressed or implied regarding the products or services described herein or their use or applicability Standard Terms and Conditions of Sale can be issued by contacting Damcos A S We reserve the right to modify or improve the designs and specifications of our products at any time without notice Emerson Automation Solutions Damcos A S Aaderupvej 41 DK 4700 Naestved Denmark ...