Installation distances with adjustment
A1: 0.39 in (10 mm)
A2: 0.79 in (20 mm)
A3: 0.79 in (20 mm) to tank structures (B) 1.97
in (50 mm) to other transmitters type LR
D: ø 1.18 in (30 mm) if installed in a connection
piece
Installation distances without adjustment
A1: 0.39 in (10 mm)
A2: 1.97 in (50 mm)
A3: 1.97 in (50 mm) to tank structures (B) 1.97
in (50 mm) to other transmitters type LR
D: No connection piece allowed (see above
image)
2.1.2
Installation in pipes
If installing the level transmitter in a pipe, the conditions must meet these requirements.
•
Hygienic requirements
•
Install only in metal pipes
•
The internal diameter of the pipe (d) must meet these requirements:
With adjustment
Without adjustment
d
ø 1.18 in (30 mm)
ø 3.94 in (100 mm) with [MEdI] =
[HIGH]
ø 7.87 in (250 mm) with [MEdI] =
[MId]
For more information, see
.
Note
Using a centering piece can prevent damage caused by turbulent media by stabilizing the
probe.
Installation
Quick Start Guide
January 2019
00825-0100-4326
14
Quick Start Guide
Summary of Contents for Rosemount 326L
Page 1: ...Quick Start Guide 00825 0100 4326 Rev 01 January 2019 Rosemount 326L Level Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4326 4 Quick Start Guide ...
Page 12: ...Introduction Quick Start Guide January 2019 00825 0100 4326 12 Quick Start Guide ...
Page 24: ...Installation Quick Start Guide January 2019 00825 0100 4326 24 Quick Start Guide ...
Page 42: ...Operation Quick Start Guide January 2019 00825 0100 4326 42 Quick Start Guide ...
Page 48: ...Setting ranges Quick Start Guide January 2019 00825 0100 4326 48 Quick Start Guide ...
Page 50: ...Product certifications Quick Start Guide January 2019 00825 0100 4326 50 Quick Start Guide ...