Reference Manual
00809-0100-4801, Rev FA
October 2010
Rosemount 3051S Series
7-20
POWER ADVISORY
Introduction
The Power Advisory diagnostic provides a means to detect issues that may
jeopardize the integrity of the electrical loop. Some examples are: water
entering the wiring compartment and makes contact with the terminals, an
unstable power supply nearing end of life, or heavy corrosion on the
terminals.
This technology is based on the premise that once a transmitter is installed
and powered up, the electrical loop has a baseline characteristic that reflects
the proper installation. If the transmitter terminal voltage deviates from the
baseline and outside the user configured threshold, the 3051S can generate a
HART alert or analog alarm.
To make use of this diagnostic, the user must first create a baseline
characteristic for the electrical loop after the transmitter has been installed.
The loop is automatically characterized with the push of a button. This creates
a linear relationship for expected terminal voltage values along the operating
region from 4 – 20 mA, see Figure 7-16.
Figure 7-16. Baseline operating
region
SPM diagnostic will not leave verifying
mode
Process is unstable. Increase learning sensitivity
checks (Verification Criteria screen). If this does
not correct the issue, increase the learning
verification period to match or exceed the cycle
time of the instability of the process. If maximum
time does not correct the problem, process is not
a candidate for SPM diagnostic. Correct stability
issue or turn off diagnostic.
SPM diagnostic does not detect a known
condition
With the condition present, but the process
operating, go to the SPM Status or Operational
Values screen and note the current statistical
values and compare to the baseline and
threshold values. Adjust the sensitivity values
until a trip of the diagnostic occurs.
SPM diagnostic indicates “High Variation
Detected” when no diagnostic event has
occurred
The most likely cause is a fast change in the
value of the process variable. Direction of the
change is not important. Increase the
learning/monitoring period to better filter out
increases in standard deviation.
Table 7-7. Possible SPM issues and resolutions
SPM Diagnostic Issue
Action
Volts
4 mA
20 mA
Output Current
T
e
rminal V
o
lt
age
Summary of Contents for Rosemount 3051S Series
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series TOC 6 ...
Page 14: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series 1 4 ...
Page 74: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series 3 32 ...
Page 90: ...Reference Manual 00809 0100 4801 Rev FA October 2010 4 16 Rosemount 3051S Series ...
Page 98: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series 5 8 ...
Page 194: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series A 46 ...
Page 205: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 11 Rosemount 3051S Series ...
Page 206: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 12 ...
Page 207: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 13 Rosemount 3051S Series ...
Page 208: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 14 ...
Page 209: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 15 Rosemount 3051S Series ...
Page 210: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 16 ...
Page 211: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 17 Rosemount 3051S Series ...
Page 212: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 18 ...
Page 213: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 19 Rosemount 3051S Series ...
Page 214: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 20 ...
Page 215: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 21 Rosemount 3051S Series ...
Page 216: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 22 ...
Page 217: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 23 Rosemount 3051S Series ...
Page 218: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 24 ...
Page 219: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 25 Rosemount 3051S Series ...
Page 221: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 27 Rosemount 3051S Series ...
Page 222: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 28 ...
Page 223: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 29 Rosemount 3051S Series ...
Page 224: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 30 ...
Page 225: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 31 Rosemount 3051S Series ...
Page 226: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 32 ...
Page 227: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 33 Rosemount 3051S Series ...
Page 228: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 34 ...
Page 229: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 35 Rosemount 3051S Series ...
Page 230: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 36 ...
Page 231: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 37 Rosemount 3051S Series ...
Page 232: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 38 ...
Page 233: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 39 Rosemount 3051S Series KEMA ...
Page 234: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 40 ...
Page 235: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 41 Rosemount 3051S Series ...
Page 236: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 42 ...
Page 239: ......