9. Rosemount 2088/2090 sensor module must be securely screwed in
place to maintain the ingress protection of the enclosure.
10. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
I1
ATEX Intrinsic Safety and Dust
Certificate
BAS00ATEX1166X
Standards
EN60079-0:2012+A11:2013,EN60079-11:2012
Markings
II 1 G Ex ia IIC T4 Ga (–55 °C ≤ T
a
≤ +70 °C)
Table 4-4: Input Parameters
Parameters
HART
Voltage U
i
30 V
Current I
i
200 mA
Power P
i
0.9 W
Capacitance C
i
0.012 µF
Inductance L
i
0 mH
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the
equipment is not capable of withstanding the 500 V insulation test.
This must be taken into account during installation.
2. The enclosure may be made of aluminium alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in a Zone 0 area.
N1
ATEX Type n and Dust
Certificate
BAS00ATEX3167X; BAS01ATEX1427X
Standards
EN60079-0:2012, EN60079-15:2010, EN60079-31:2009
Markings
II 3 G Ex nA IIC T5 Gc
(–40 °C
≤ T
a
≤
+70 °C);
II 1 D Ex t
IIIC T50
°C T
500
60 °C Da
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test
that is required by EN60079-15. This must be taken into account when
installing the apparatus.
February 2019
Quick Start Guide
Quick Start Guide
29