Emerson Rosemount 3051D Quick Start Manual Download Page 1

Quick Start Guide

00825-0100-5007, Rev CB

February 2019

Rosemount

 3051 Pressure Transmitter

Summary of Contents for Rosemount 3051D

Page 1: ...Quick Start Guide 00825 0100 5007 Rev CB February 2019 Rosemount 3051 Pressure Transmitter ...

Page 2: ...th intrinsically safe or non incendive field wiring practices In an explosion proof flameproof installation do not remove the transmitter covers when power is applied to the unit WARNING Process leaks Process leaks may cause harm or result in death To avoid process leaks only use the O ring designed to seal with the corresponding flange adapter Electrical shock Electrical shock can result in death...

Page 3: ...t Emerson com or Fieldcommgroup org Rosemount 3051 device revisions and drivers Table 1 1 provides the information necessary to ensure you have the correct device driver and documentation for your device Table 1 1 Rosemount 3051 with 4 20mA HART Protocol Device Revisions and Files Release date Device identification Device Driver identification Review Instructions Review Functio nality NAMUR hardwa...

Page 4: ...hanges signified above by xx represent minor product changes as defined per NE53 Compatibility and functionality are preserved and product can be used interchangeably 3 HART Software Revision can be read using a HART capable configuration tool Value shown is minimum revision that could correspond to NAMUR Revisions 4 Device Driver file names use Device and DD Revision e g 10_01 HART Protocol is de...

Page 5: ... beside or below the taps 3 Mount the transmitter so that the drain vent valves are oriented upward Figure 2 1 Coplanar and In line Liquid Applications A Coplanar B In line 2 1 2 Gas applications Procedure 1 Place taps in the top or side of the line 2 Mount beside or above the taps February 2019 Quick Start Guide Quick Start Guide 5 ...

Page 6: ...s Applications A Flow A Coplanar B In line 2 1 3 Steam applications Procedure 1 Place taps to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water Quick Start Guide February 2019 6 Emerson com Rosemount ...

Page 7: ...e 2 3 Coplanar and In line Steam Applications A B Flow A Coplanar B In line Figure 2 4 Panel and pipe mounting 1 5 6 x 1 panel bolts are customer supplied February 2019 Quick Start Guide Quick Start Guide 7 ...

Page 8: ... flange and optional flange adapters D Transmitter with coplanar flange and optional manifold and flange adapters Bolts are typically carbon steel CS or stainless steel SST Confirm the material by viewing the markings on the head of the bolt and referencing Table 2 1 If bolt material is not shown in Table 2 1 contact a local Emerson representative for more information Use the following bolt instal...

Page 9: ...0 in lb SST 316 316 316 SW 316 STM 316 R B8M 150 in lb 300 in lb 2 1 5 In line gage transmitter orientation The low side pressure port atmospheric reference on the in line gage transmitter is located in the neck of the transmitter behind the housing The vent path is 360 around the transmitter between the housing and sensor See Figure 2 6 Keep the vent path free of any obstruction including but not...

Page 10: ...rn the housing left or right maximum up to 180 from its original position 1 Note Over rotating can damage the transmitter 3 Re tighten the housing rotation set screw to no more than 7 in lb when desired location is reached Figure 2 7 Housing Rotation Set Screw A A Housing rotation set screw 5 64 in 1 Rosemount 3051D original position aligns with H side Rosemount 3051G original position is the oppo...

Page 11: ...ocked symbol Use the following procedure to change the switch configuration 6 If the transmitter is installed secure the loop and remove power 7 Remove the housing cover opposite the field terminal side Do not remove the instrument cover in explosive atmospheres when the circuit is live 8 Slide the security and alarm switches into the preferred position using a small screwdriver 9 Reattach the tra...

Page 12: ...ter optional Shielded twisted pair cable should be used for best results Use 24 AWG or larger wire that does not exceed 5 000 ft 1500 m in length If applicable install wiring with a drip loop Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing Quick Start Guide February 2019 12 Emerson com Rosemount ...

Page 13: ... TERMINALS side 2 Connect the positive lead to the terminal PWR COMM and the negative lead to the terminal 3 Ground housing to fulfill local grounding regulations 4 Ensure proper grounding It is important that the instrument cable shield be a Trimmed close and insulated from touching the transmitter housing b Connected to the next shield if cable is routed through a junction box c Connected to a g...

Page 14: ... follow Connect the wiring and power up through step 7 When the transmitter is properly wired refer to Figure 2 10 for internal and external transient grounding locations 2 4 Verifying configuration Verify the configuration using any HART capable configuration tool Configuration instructions for a Field Communicator are included in this step See Rosemount 3051 Reference Manual for configuration in...

Page 15: ... Alarm and Saturation Levels 2 2 2 5 7 2 2 2 5 7 P Damping 2 2 1 1 5 2 2 1 1 5 P Range Values 2 2 2 2 2 2 P Tag 2 2 7 1 1 2 2 7 1 1 P Transfer Function 2 2 1 1 6 2 2 1 1 6 P Units 2 2 1 1 4 2 2 1 1 4 Burst Mode 2 2 5 3 2 2 5 3 Custom Display Configuration 2 2 4 2 2 4 Date 2 2 7 1 4 2 2 7 1 3 Descriptor 2 2 7 1 5 2 2 7 1 4 Digital to Analog Trim 4 20 mA output 3 4 2 3 4 2 Disable Configuration Butt...

Page 16: ...rify configuration with LOI The optional LOI can be used for commissioning the device The LOI is a two button design with internal and external buttons The internal buttons are located on the display of the transmitter while the external buttons are located underneath the top metal tag To activate the LOI push any button LOI button functionality is shown on the bottom corners of the display See Ta...

Page 17: ...h HART Revision 7 the Rosemount 3051 will load a generic menu with limited capability The following procedures will switch the HART revision mode from the generic menu Procedure Manual Setup Device Information Identification Message a To change to HART Revision 5 Enter HART5 in the Message field b To change to HART Revision 7 Enter HART7 in the Message field February 2019 Quick Start Guide Quick S...

Page 18: ...og zero trim Sets the analog output to 4 mA 2 Also referred to as a rerange it sets the lower range value LRV equal to the measured pressure 3 The display and digital HART output remains unchanged a Digital zero trim Recalibrates the sensor zero 4 The LRV is unaffected The pressure value will be zero on display and HART output 4 mA point may not be at zero 5 This requires that the factory calibrat...

Page 19: ...ero and span C Digital zero D Configuration buttons Use the following procedures to perform a zero trim Perform trim with LOI option M4 3 Set the transmitter pressure 4 See Figure 2 12 for the operating menu a Perform an analog zero trim by selecting Rerange b Perform a digital zero trim by selecting Zero Trim February 2019 Quick Start Guide Quick Start Guide 19 ...

Page 20: ...ety instrumented systems installation For safety certified installations refer to Reference Manual for installation procedure and system requirements Quick Start Guide February 2019 20 Emerson com Rosemount ...

Page 21: ...C Ta 85 C V max 42 4 Vdc Table 4 1 Process Temperature Temperature class Process temperature Ambient temperature T6 50 to 65 C T5 50 to 70 C Special Conditions for Safe Use X 1 This device contains a thin wall diaphragm less than 1mm thickness that forms a boundary between zone 0 process connection and zone 1 all other parts of the equipment The model code and datasheet are to be consulted for det...

Page 22: ...able of withstanding the 500 V insulation test required by clause 6 3 13 of EN60079 11 2012 This must be taken into account when installing the equipment 2 The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish however care should be taken to protect it from impact or abrasion if located in Zone 0 3 Some variants of the equipment have reduced markings on the n...

Page 23: ...ontains a thin wall diaphragm less than 1mm thickness that forms a boundary between zone 0 process connection and zone 1 all other parts of the equipment The model code and datasheet are to be consulted for details of the diaphragm material Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions ...

Page 24: ... or abrasion if located in Zone 0 N7 IECEx Type n Certificate IECEx BAS 12 0108X Standards IEC60079 0 2011 IEC60079 15 2010 Markings Ex nA IIC T5 Gc 40 C Ta 70 C Special Condition for Safe Use X 1 The apparatus is not capable of withstanding the 500 V insulation test required by IEC60079 15 This must be taken into account when installing the apparatus China E3 China Flameproof Certificate GYJ18 10...

Page 25: ...ctrical apparatus for explosive gas atmospheres Part 15 Electrical installations in hazardous area other than mines GB3836 16 2006 Electrical apparatus for explosive gas atmospheres Part 16 Inspection and maintenance of electrical installation other than mines GB50257 2014 Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment install...

Page 26: ... and fire protection requirements by a nationally recognized test laboratory NRTL as accredited by the Federal Occupational Safety and Health Administration OSHA North America Certificate E5 USA Explosionproof XP and Dust Ignitionproof DIP Certificate 0T2H0 AE Standards FM Class 3600 2011 FM Class 3615 2006 FM Class 3616 2011 FM Class 3810 2005 ANSI NEMA 250 2008 Markings XP CL I DIV 1 GP B C D DI...

Page 27: ...on 1 Intrinsically Safe Class I Division 1 Groups A B C D when connected in accordance with Rosemount drawing 03031 1024 Temperature Code T3C Suitable for Class I Zone 0 Class I Division 2 Groups A B C and D T5 Suitable for Class I Zone 2 Group IIC Type 4X Factory Sealed Single Seal See drawing 03031 1053 E6 Canada Explosionproof Dust Ignitionproof and Division 2 Certificate 1053834 Standards ANSI...

Page 28: ...static discharge Avoid installations that could cause electrostatic build up on painted surfaces and only clean the painted surfaces with a damp cloth If paint is ordered through a special option code contact the manufacturer for more information 4 Appropriate cable glands and plugs need to be suitable for a temperature of 5 C greater than maximum specified temperature for location where installed...

Page 29: ...nt suppression terminal block the equipment is not capable of withstanding the 500 V insulation test This must be taken into account during installation 2 The enclosure may be made of aluminium alloy and given a protective polyurethane paint finish however care should be taken to protect it from impact or abrasion if located in a Zone 0 area N1 ATEX Type n and Dust Certificate BAS00ATEX3167X BAS01...

Page 30: ...n maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime 2 Flameproof joints are not intended for repair 3 Non standard paint options may cause risk from electrostatic discharge Avoid installations that...

Page 31: ...Ex Type n Certificate IECEx BAS 12 0072X Standards IEC60079 0 2011 IEC60079 15 2010 Markings Ex nA IIC T5 Gc 40 C Ta 70 C Special Conditions for Safe Use X 1 When fitted with a transient suppression terminal block the Rosemount 2088 is incapable of passing the 500 V isolation test This must be taken into account when installing the apparatus Brazil E2 INMETRO Flameproof Certificate UL BR 15 0728X ...

Page 32: ...The earth connection facility in the enclosure should be connected reliably 3 During installation there should be no mixture harmful to housing 4 During installation in hazardous location Cable glands and blanking plugs certified by state appointed inspection bodies with Ex d IIC Gb type of protection should be used Redundant cable entries should be blocked with blanking plugs 5 During installatio...

Page 33: ... this apparatus is not capable of withstanding the 500V r m s insulation test required by Clause 6 3 12 of GB3836 4 2010 N3 China Type n Certificate GYJ13 1305X Standards GB3836 1 2010 GB3836 8 2003 Markings Ex nA IIC T5 Gc 40 C Ta 70 C Special Conditions for Safe Use X 1 When transient protection board is chosen option code T1 this apparatus is not capable of withstanding the 500 V r m s insulati...

Page 34: ...14 NPT 14 NPT 14 NPT Female thread Identification mark M20 x 1 5 6H M20 14 NPT 14 NPT G G Special Conditions for Safe Use X 1 When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety e the entry thread shall be suitably sealed in order to maintain the ingress protection rating IP of the enclosure 2 The blanking plug shall not be used with an adapter...

Page 35: ...to which this declaration relates is in conformity with the provisions of the European Community Directives including the latest amendments as shown in the attached schedule Assumption of conformity is based on the application of the harmonized standards and when applicable or required a European Community notified body certification as shown in the attached schedule signature Vice President of Gl...

Page 36: ...E HOU DNV All other model 3051D and 3051G Pressure Transmitters Sound Engineering Practice Transmitter Attachments Diaphragm Seal Process Flange Manifold Sound Engineering Practice ATEX Directive 2014 34 EU Model 3051D Pressure Transmitter Baseefa12ATEX0189X Intrinsic Safety Certificate Equipment Group II Category 1 G Ex ia IIC T4 Ga 60 C Ta 70 C Ex ia IIC T5 Ga 60 C Ta 40 C Harmonized Standards U...

Page 37: ...rtificate Equipment Group II Category 1 G Ex ia IIC T5 Ga 55 C Ta 40 C Ex ia IIC T4 Ga 55 C Ta 70 C Harmonized Standards Used EN60079 0 2012 A11 2013 EN60079 11 2012 BAS00ATEX3167X Type n Certificate Equipment Group II Category 3 G Ex nA IIC T5 Gc 40 C Ta 70 C Harmonized Standards Used EN60079 0 2012 A11 2013 EN60079 15 2010 BAS01ATEX1427 Dust Certificate Equipment Group II Category 1 D Ex t IIIC ...

Page 38: ...lows Det Norske Veritas DNV Notified Body Number 0575 Veritasveien 1 N 1322 Hovik Norway ATEX Notified Bodies for EC Type Examination Certificate DEKRA Notified Body Number 0344 Meander 1051 6825 MJ Arnhem P O Box 5185 6802 ED Arnhem The Netherlands Postbank 6794687 SGS FIMCO OY Notified Body Number 0598 P O Box 30 Särkiniementie 3 00211 HELSINKI Finland ATEX Notified Body for Quality Assurance SG...

Page 39: ...O O X O O Րᝏಘ㓴Ԧ Sensor Assembly X O O X O O ᵜ㺘Ṭ ᦞ SJ T11364Ⲵ㿴ᇊ㘼ࡦ This table is proposed in accordance with the provision of SJ T11364 O Ѫ䈕䜘ԦⲴᡰᴹ 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿 վҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 O Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X Ѫ 䈕䜘Ԧᡰ Ⲵᡰᴹ 䍘ᶀᯉ䟼ˈ㠣ቁᴹа 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿儈ҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 X Indicate that said hazardous s...

Page 40: ... Baar Switzerland 41 0 41 768 6111 41 0 41 768 6300 RFQ RMD RCC Emerson com Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 65 6777 8211 65 6777 0947 Enquiries AP Emerson com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 971 4 8865465 RFQ...