Note

The device description loaded in the host system must be at the same
revision as this device.

Figure 3-3: Commissioning Tag

A. Device revision

Note

The device description loaded in the host system must be at the same
revision as this device. The device description can be downloaded from the
host system website or 

Emerson.com/Rosemount

 by selecting 

Download

Device Drivers

 under 

Product Quick Links

. You can also visit 

Fieldbus.org

 and

select 

End User Resources

.

3.3

Setting security switch

Prerequisites

Set Simulate and Security switch configuration before installation as shown
in 

Figure 3-4

.

The simulate switch enables or disables simulated alerts and simulated
AI Block status and values. The default simulate switch position is
enabled.

The Security switch allows (unlocked symbol) or prevents (locked
symbol) any configuration of the transmitter.

Default security is off (unlocked symbol).

The security switch can be enabled or disabled in software.

Use the following procedures to change the switch configuration:

November  2019

Quick Start Guide

Quick Start Guide

9

Summary of Contents for Rosemount 2051HT

Page 1: ...Quick Start Guide 00825 0200 4591 Rev BA November 2019 Rosemount 2051HT Hygienic Pressure Transmitter with FOUNDATION Fieldbus Protocol ...

Page 2: ...Contents About this guide 3 System readiness 6 Transmitter installation 7 Product certifications 23 Quick Start Guide November 2019 2 Rosemount 2051HT ...

Page 3: ...roof or intrinsically safe I S installations CAUTION The products described in this document are NOT designed for nuclear qualified applications Using non nuclear qualified products in applications that require nuclear qualified hardware or products may cause inaccurate readings For information on Rosemount nuclear qualified products contact your local Emerson Sales Representative November 2019 Qu...

Page 4: ...ath or serious injury Avoid contact with the leads and terminals High voltage that may be present on leads can cause electrical shock Before connecting a handheld communicator in an explosive atmosphere ensure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices In an Explosion Proof Flameproof installation do not remove the transm...

Page 5: ...ts must break back plane of flange web i e bolt hole but must not contact sensor module housing Physical access Unauthorized personnel may potentially cause significant damage to and or misconfiguration of end users equipment This could be intentional or unintentional and needs to be protected against Physical security is an important part of any security program and fundamental to protecting your...

Page 6: ... Manual Document Number 2 All DD4 DD Rev 1 FieldCommGrou p org Emerson com Rosemount 2051 Pressure Transmitter Reference Manual or newer All DD5 DD Rev 1 FieldCommGrou p org Emerson AMS Device Manager V 10 5 or higher DD Rev 2 Emerson com Emerson AMS Device Manager V 8 to 10 5 DD Rev 1 Emerson com Emerson Field Communicator DD Rev 2 Easy upgrade utility 1 FOUNDATION Fieldbus device revision can be...

Page 7: ...ironmental seal for housing Thread sealing PTFE tape or paste on male threads of conduit is required to provide a water dust tight conduit seal and meets requirements of NEMA Type 4X IP66 IP68 and IP69K Consult factory if other Ingress Protection ratings are required For M20 threads install conduit plugs to full thread engagement or until mechanical resistance is met Note IP69K rating only availab...

Page 8: ... In line Protected Gage Vent Low Side Pressure Port Aluminum Polished 316 SST A A Low side pressure port atmospheric reference 3 1 4 Clamping When installing clamp follow recommended torque values provided by gasket manufacturer Note To maintain performance torquing a 1 5 Tri Clamp beyond 50 in lb is not recommended on pressure ranges below 20 psi 3 2 Commissioning paper tag To identify which devi...

Page 9: ...rg and select End User Resources 3 3 Setting security switch Prerequisites Set Simulate and Security switch configuration before installation as shown in Figure 3 4 The simulate switch enables or disables simulated alerts and simulated AI Block status and values The default simulate switch position is enabled The Security switch allows unlocked symbol or prevents locked symbol any configuration of...

Page 10: ...of requirements 3 4 Setting simulate switch The simulate switch is located on the electronics It is used in conjunction with the transmitter simulate software to simulate process variables and or alerts and alarms To simulate variables and or alerts and alarms the simulate switch must be moved to the enable position and the software enabled through the host To disable simulation the switch must be...

Page 11: ...iring to the screw terminals the use of crimped legs is recommended 2 Ensure full contact with terminal block screw and washer When using a direct wiring method wrap wire clockwise to ensure it is in place when tightening the terminal block screw No additional power is needed Note The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening ...

Page 12: ...3 5 1 Signal ground wiring Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment Grounding terminations are provided on the outside of the electronics housing and inside the terminal compartment These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations Procedure 1 Remove the field terminals housing c...

Page 13: ...Note The Rosemount 2051HT polished 316 SST housing only provides ground termination inside the terminal compartment 3 5 2 Power supply The transmitter requires between 9 and 32 Vdc 9 and 30 Vdc for intrinsic safety to operate and provide complete functionality 3 5 3 Power conditioner A Fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from ot...

Page 14: ... or configuration tool has a different way of displaying and performing configurations Some use device descriptions DD or DD methods for configuration and to display data consistently across platforms There is no requirement that a host or configuration tool support these features Use the following block examples to do basic configuration to the transmitter For more advanced configurations see the...

Page 15: ...Figure 3 6 Configuration Flowchart November 2019 Quick Start Guide Quick Start Guide 15 ...

Page 16: ...onfiguration flow chart 3 6 2 Before you begin See Figure 3 6 to graphically view the step by step process for basic device configuration Before beginning configuration you may need to verify the Device Tag or deactivate hardware or software write protection on the transmitter To do this perform this task Otherwise continue at navigating to AI block configuration Quick Start Guide November 2019 16...

Page 17: ...Place the control loop in Manual mode before beginning AI block configuration Note Place the control loop in Manual mode before beginning analog input block configuration 3 6 3 AI block configuration Procedure 1 To use guided setup a Navigate to Configure Guided Setup b Select AI Block Unit Setup Note Guided setup will automatically go through each step in the proper order 2 To use manual setup a ...

Page 18: ...E Direct for pressure measurements using the device default units b Select L_TYPE Indirect for other pressure or level units c Select L_TYPE Indirect Square Root for flow units 4 To set XD_SCALE to the 0 and 100 scale points the transmitter range a Select the XD_SCALE_UNITS from the drop down menu b Enter the XD_SCALE 0 point This may be elevated or suppressed for level applications c Enter the XD...

Page 19: ...p Process Variable and select Change Damping Enter the desired damping value in seconds The permitted range of values is 0 4 to 60 seconds 7 Configure LCD display if installed a To use guided setup Navigate to Configure Guided Setup and select Local Display Setup Note Guided setup will automatically go through each step in the proper order Check the box next to each parameter to be displayed to a ...

Page 20: ...e Note If hardware or software write protection is not needed step 10 can be skipped 9 Set switches and software write lock a Check switches see Figure 3 4 Note The write lock switch can be left in the locked or unlocked position The simulate enable disable switch may be in either position for normal device operation Enable software write lock Procedure 1 Navigate from the Overview screen a Select...

Page 21: ... Pressure example Parameters Enter data Channel 1 L_Type Direct XD_Scale See list of supported engineering units Note Select only the units that are supported by the device Out_Scale Set values outside operating range 3 6 4 Display pressure on the LCD display Select the Pressure check box on the Display Configuration screen 3 7 Zero trim the transmitter Note Transmitters are shipped fully calibrat...

Page 22: ...ing and Indirect L_Type which are part of the AI Block Procedure 1 To use guided setup a Navigate to Configure Guided Setup and select Zero Trim b The method will execute the zero trim 2 To use manual setup a Navigate to Overview Calibration Sensor Trim and select Zero Trim b The method will execute the zero trim Quick Start Guide November 2019 22 Rosemount 2051HT ...

Page 23: ...ment in Divisions The markings must be suitable for the area classification gas and temperature class This information is clearly defined in the respective codes 4 4 Hazardous Locations Certifications Note Device ambient temperature ratings and electrical parameters may be limited to the levels dictated by the hazardous location certificate parameters 4 5 North America 4 5 1 I5 USA Intrinsic Safet...

Page 24: ... 2 No 213 M1987 CSA Std C22 2 No 157 92 CSA Std C22 2 No 213 M1987 ANSI ISA 12 27 01 2003 CAN CSA E60079 0 07 CAN CSA E60079 11 02 Markings Intrinsically safe for Class I Division 1 Groups A B C and D when connected in accordance with Rosemount drawing 02051 1008 Ex ia IIC T3C Single Seal Enclosure Type 4X 4 6 Europe 4 6 1 I1 ATEX Intrinsic Safety Certificate Baseefa08ATEX0129X Standards EN60079 0...

Page 25: ...IBUS Voltage Ui 30 V 30 V Current Ii 200 mA 300 mA Power Pi 1 W 1 3 W Capacitance Ci 0 012 μF 0 μF Inductance Li 0 mH 0 mH Specific Conditions of Safe Use X 1 If the equipment is fitted with an optional 90 V transient suppressor it is incapable of withstanding the 500 V isolation from earth test and this must be taken into account during installation 2 The enclosure may be made of aluminum alloy a...

Page 26: ... by selecting option code QA EHEDG All Rosemount 2051HT transmitters with the following connections are EHEDG approved and labeled T32 1 in Tri Clamp T42 2 in Tri Clamp If process connection B11 is selected please reference the ordering table of the Rosemount 1199 Diaphragm Seal Product Data Sheet for availability of EHEDG certifications An EHEDG certificate of compliance is available by selecting...

Page 27: ...4 9 Rosemount 2051HT Declaration of Conformity November 2019 Quick Start Guide Quick Start Guide 27 ...

Page 28: ...Quick Start Guide November 2019 28 Rosemount 2051HT ...

Page 29: ...November 2019 Quick Start Guide Quick Start Guide 29 ...

Page 30: ...O O O O O Րᝏಘ㓴Ԧ Sensor Assembly X O O O O O ᵜ㺘Ṭ ᦞ SJ T11364Ⲵ㿴ᇊ㘼ࡦ This table is proposed in accordance with the provision of SJ T11364 O Ѫ䈕䜘ԦⲴᡰᴹ 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿 վҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 O Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X Ѫ 䈕䜘Ԧᡰ Ⲵᡰᴹ 䍘ᶀᯉ䟼ˈ㠣ቁᴹа 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿儈ҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 X Indicate that said hazardous s...

Page 31: ...November 2019 Quick Start Guide Quick Start Guide 31 ...

Page 32: ...ox 1046 CH 6340 Baar Switzerland 41 0 41 768 6111 41 0 41 768 6300 RFQ RMD RCC Emerson com Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 65 6777 8211 65 6777 0947 Enquiries AP Emerson com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 97...

Reviews: