77
Reference Manual
00809-0100-4107, Rev BA
Section 5: Operation and Maintenance
April 2013
5.6.3
Recalling Factory Trim—analog output
The Recall Factory Trim—Analog Output command allows the restoration of the as-shipped
factory settings of the analog output trim. This command can be useful for recovering from an
inadvertent trim, incorrect Plant Standard or faulty meter.
Recalling Factory Trim - analog output with a Field
Communicator
From the
HOME
screen, enter the fast key sequence and follow the steps within the Field
Communicator to complete the digital to analog trim using other scale.
Recalling Factory Trim - analog output with AMS Device
Manager
Right click on the device and, under the
Method
drop down menu, move cursor over
Calibrate
and select
Restore Factory Calibration
.
1.
Click
Next
to set the control loop to manual.
2.
Select
Analog Output Trim
under
Select trim to recall
and click
Next
.
3.
Follow screen prompts to recall analog output trim.
Recalling Factory Trim - analog output with Local Operator
Interface
Reference
for LOI instructions.
Figure 5-7. Recall Factory Trim – analog output with Local Operator Interface
Device Dashboard Fast Keys
3, 4, 3
EXTENDED MENU
CALIBRAT
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
FACTORY RECALL
BACK TO MENU
EXIT MENU
FACTORY RECALL
SENSOR RECALL
ANALOG RECALL
ANALOG RECALL
BACK TO MENU
EXIT MENU