background image

131

Reference Manual 

00809-0100-4107, Rev BA

Appendix A: Specifications and Reference Data

April 2013

Appendix A: Specifications and Reference Data

(3)Available in Ranges 2-5 only.
(4)Not available with Low Power output code M.
(5)Requires 0 code in Materials of Construction for Alternate Process Connection.
(6)Not valid with optional code P9 for 4500 psi Static Pressure.
(7)“Assemble-to” items are specified separately and require a completed model number.
(8)Process Flange limited to Coplanar (codes 2, 3, 5, 7, 8) or Traditional (H2, H3, H7).
(9)Not valid with optional code D9 for RC1/2 Adaptors.
(10)Not valid with optional codes DF and D9 for Adaptors.
(11)Only valid with F

OUNDATION

 fieldbus output code F.

(12)Not available with F

OUNDATION

 fieldbus output code F.

(13)Not available with Alloy C-276 isolator (3 code), tantalum isolator (5 code), all cast C-276 flanges, all plated CS flanges, all DIN 
flanges, all Level flanges, assemble-to manifolds (S5 and S6 codes), assemble-to seals (S1 and S2 codes), assemble-to primary 
elements (S3 and S4 codes), surface finish certification (Q16 code), and remote seal system report (QZ code).
(14)Only Available with HART 4-20 mA (output codes A and M).
(15)Not valid with Alternate Process Connection options S3, S4, S5, S6.
(16)Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard carbon steel conduit plug.
(17)Not available with Alternate Process Connection: DIN Flanges and Level Flanges.
(18)The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.
(19)Available with 4-20 mA HART output code A, F

OUNDATION

 fieldbus output code F, 2051C Ranges 2-5 or 2051T Ranges 1-4, SST 

diaphragms and silicone fill fluid. High Performance Option includes 0.05% Reference Accuracy, 5 year stability and improved ambient 
temperature effect specifications. See “Performance specifications” on page 99
 for details. 
(20)The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification 
codes IA and IE. 
(21)Only available with HART 4-20 mA output (output code A).
(22)NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.
(23)Configures the HART output to HART Revision 5.  The device can be field configured to HART Revision 7 if needed.
(24)Configures the HART output to HART Revision 7.  The device can be field configured to HART Revision 5 if needed.

Summary of Contents for Rosemount 2051

Page 1: ...www rosemount com Reference Manual 00809 0100 4107 Rev BA April 2013 Rosemount 2051 Pressure Transmitter with HART Revision 5 and 7 Selectable Protocol ...

Page 2: ......

Page 3: ...307 7 00 am to 7 00 pm CST Asia Pacific 65 777 8211 Europe Middle East Africa 49 8153 9390 North American Response Center Equipment service needs 1 800 654 7768 24 hours includes Canada Outside of these areas contact your local Emerson Process Management representative The products described in this document are NOT designed for nuclear qualified applications Using non nuclear qualified products i...

Page 4: ......

Page 5: ...2 3 System readiness 8 2 3 1 Confirm correct Device Driver 8 2 4 Configuration basics 9 2 4 1 Configuring on the bench 9 2 4 2 Configuration tools 10 2 4 3 Setting the loop to manual 12 2 5 Verify configuration 12 2 5 1 Verifying configuration with Field Communicator 12 2 5 2 Verifying configuration with AMS Device Manager 13 2 5 3 Verifying configuration with Local Operator Interface 13 2 5 4 Ver...

Page 6: ...ations 34 3 3 1 Installation considerations 34 3 3 2 Environmental considerations 34 3 3 3 Mechanical considerations 35 3 4 Installation procedures 35 3 4 1 Mount the transmitter 35 3 4 2 Impulse piping 42 3 4 3 Process connections 44 3 4 4 Inline process connection 45 3 5 Rosemount 305 306 and 304 Manifolds 47 3 5 1 Rosemount 305 Integral Manifold installation procedure 48 3 5 2 Rosemount 306 Int...

Page 7: ... 3 Compensating for Span line pressure effects range 4 and range 5 70 5 5 Trim the pressure signal 71 5 5 1 Sensor Trim overview 71 5 5 2 Perform a Sensor Trim 72 5 5 3 Recall Factory Trim sensor trim 73 5 6 Trim the analog output 74 5 6 1 Performing Digital to Analog Trim 4 20mA 1 5 V Output Trim 75 5 6 2 Performing Digital to Analog Trim 4 20mA 1 5 V Output Trim using other scale76 5 6 3 Recalli...

Page 8: ...ments 7 1 Safety Instrumented Systems SIS Certification 93 7 1 1 Rosemount 2051 safety certified identification 93 7 1 2 Installation in SIS applications 93 7 1 3 Configuring in SIS applications 94 7 1 4 Rosemount 2051 SIS operation and mainenance 95 7 1 5 Inspection 96 AAppendix A Specifications and Reference Data A 1 Performance specifications 99 A 1 1 Conformance to specification 3s Sigma 99 A ...

Page 9: ...s connections 109 A 3 3 Process wetted parts 110 A 3 4 Rosemount 2051L process wetted parts 110 A 3 5 Non wetted parts 111 A 3 6 Shipping weights 112 A 4 Dimensional drawings 113 Table 10 122 A 5 Ordering Information 125 A 5 1 Rosemount 2051C Coplanar Pressure Transmitter 125 A 5 2 Rosemount 2051T In Line Pressure Transmitter 132 A 5 3 Rosemount 2051CF Flowmeter Series 137 A 5 4 Rosemount 2051L Le...

Page 10: ...1 B 5 1 Factory mutual 02051 1009 181 B 5 2 Canadian standards association CSA 02051 1008 194 CAppendix C Field Communicator Menu Trees and Fast Keys C 1 Field Communicator menu trees 205 C 2 Field Communicator fast keys 210 DAppendix D Local Operator Interface D 1 LOI Menu Tree 211 D 2 LOI Menu Tree Extended Menu 212 D 3 Number entry 213 D 4 Text entry 214 ...

Page 11: ... 4 Electrical Installation contains electrical installation instructions and field upgrade options Section 5 Operation and Maintenance provides detailed information on calibrating and changing HART Revisions Section 6 Troubleshooting provides troubleshooting techniques for the most common operating problems Section 7 Safety Instrumented Systems Requirements provides identification installation con...

Page 12: ...137 9 bar 1 2 2 Rosemount 2051T in line Pressure Transmitter Measures gage absolute pressure up to 10000 psi 689 5 bar 1 2 3 Rosemount 2051L Level Transmitter Measures level and specific gravity up to 300 psi 20 7 bar 1 2 4 Rosemount 2051CF Series Flowmeter Measures flow in line sizes from 1 2 in 15mm to 96 in 2400 mm Note For Rosemount 2051 with FOUNDATION Fieldbus see Rosemount Product Manual 00...

Page 13: ...n Specifications Yes No Refer to Section 5 Operation and Maintenance Configure Security and Alarm page 59 Mount Transmitter page 40 Wire Transmitter page 63 Power Transmitter page 63 Trim the Transmitter page 74 Done Review Transmitter Configuration page 12 Confirm Transmitter Configuration page 12 Configure for Pressure Configure Scaled Variable page 23 Set Scaled Variable to PV page 23 Configure...

Page 14: ...age 5 For the Rosemount 2051 pressure is applied to the isolating diaphragm s The oil deflects the sensor which then changes its capacitance or voltage signal This signal is then changed to a digital signal by the Signal Processing The microprocessor then takes the signals from the Signal Processing and calculates the correct output of the transmitter This signal is then sent to the D A converter ...

Page 15: ... center will ask for product model and serial numbers and will provide a Return Material Authorization RMA number The center will also ask for the process material to which the product was last exposed For inquiries outside of the United States contact the nearest Emerson Process Management representative for RMA instructions To expedite the return process outside of the United States contact the ...

Page 16: ...stances 1 6 Product recycling disposal Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation regulations Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard The product being returned will require a copy of the required Material Safety ...

Page 17: ...ribed in Performing transmitter tests on page 27 Field Communicator AMS Device Manager and Local Operator Interface LOI instructions are given to perform configuration functions For convenience Field Communicator fast key sequences are labeled Fast Keys and abbreviated LOI menus are provided for each function below Full Field Communicator menu trees and fast key sequences are available in Appendix...

Page 18: ...evision and Device Revision numbers to find the correct Device Driver Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Please review the approvals section of the Rosemount 2051 reference manual for any restrictions associated with ...

Page 19: ...lock or 1 5V configuration wire as shown in Figure 2 1 on page 10 The Field communicator is connected to the terminals labeled VOUT COMM Identify Device Find Device Driver Review Instructions Review Functionality Software Release Date NAMUR Software Revision 1 1 1 NAMUR Software Revision is located on the hardware tag of the device HART Software Revision 2 2 HART Software Revision can be read usin...

Page 20: ... two interfaces available with the Field Communicator Traditional and Dashboard interfaces All steps using a Field Communicator will be described using Dashboard interfaces Figure 2 3 on page 11 shows the Device Dashboard interface As stated in Section 2 3 System readiness it is critical that the latest DD s are loaded into the Field Communicator Visit www emersonprocess com or www hartcomm org to...

Page 21: ... M4 to be ordered To activate the LOI push either configuration button Configuration buttons are located on the LCD Display must remove housing cover to access or underneath the top tag of the transmitter See Table 2 2 for configuration button functionality and Figure 2 4 for configuration button location When using the LOI for configuration several features require multiple screens for a successf...

Page 22: ...l control as a separate operation 2 5 Verify configuration It is recommended that various configuration parameters are verified prior to installation into the process The various parameters are detailed out for each configuration tool Depending on what configuration tool s are available follow the steps listed relevant to each tool 2 5 1 Verifying configuration with Field Communicator Configuratio...

Page 23: ...iguration This section describes how to verify that the correct process variables are selected Verifying process variables with a Field Communicator Verifying process variables with AMS Device Manager Right click on the device and select Overview from the menu 1 Click the All Variables button to display the primary secondary tertiary and quaternary variables From the HOME screen enter the fast key...

Page 24: ... Follow Figure 2 5 on page 14 to select desired pressure and temperature units Use the SCROLL and ENTER buttons to select desired unit Save by selecting SAVE as indicated on the LCD screen Figure 2 5 Selecting Units with LOI 2 6 2 Setting transmitter output Transfer Function The Rosemount 2051 has two output settings Linear and Square Root As shown in Figure 2 7 on page 16 activating the square ro...

Page 25: ...Setting transmitter output with a Local Operator Interface Reference Figure 2 6 on page 15 to select either linear or square root transfer function using the LOI Figure 2 6 Set output with LOI From the HOME screen enter the fast key sequence Device Dashboard Fast Keys 2 2 1 1 6 EXTENDED MENU CALIBRAT DAMPING TRANSFER FUNCT TRANSFER FUNCT SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMLAT...

Page 26: ...h method is unique examine all options closely before deciding which method works best for your process Rerange by manually setting range points with a Field Communicator AMS Device Manager or Local Operator Interface Rerange with a pressure input source and a Field Communicator AMS Device Manager Local Operator Interface or local zero and span buttons Manually rerange the transmitter by entering ...

Page 27: ...he device select Configure 1 Select the Analog Output tab 2 Click Range by Applying Pressure button and follow the screen prompts range the transmitter Rerange with an applied pressure source using a Field Communicator Use Figure 2 9 to manually rerange the device using an applied pressure source with an LOI Figure 2 9 Rerange with applied pressure using LOI From the HOME screen enter the fast key...

Page 28: ...while maintaining the zero point press and hold the span button for at least two seconds and then release Note 4mA and 20mA points must maintain the minimum span defined in Appendix A Functional specifications Figure 2 10 Analog Zero and span buttons A Zero and span Buttons If the transmitter security is on adjustments to the zero and span will not be able to be made Refer to Configuring transmitt...

Page 29: ...mmunicator Enter desired Damping Value and select APPLY Damping with AMS Device Manager Right click on the device and select Configure 1 Select Manual Setup 2 Within the Pressure Setup box enter desired damping value and click Send 3 Carefully read the warning and click Yes if it is safe to apply the changes Damping with a Local Operator Interface Reference Figure 2 11 to enter damping values usin...

Page 30: ...of LCD screen Configuring LCD Display with a Field Communicator Configuring LCD Display with AMS Device Manager Right click on the device and select Configure 1 Click Manual Setup select the Display tab 2 Select desired display options and click Send Configuring LCD Display with a Local Operator Interface Refer to Figure 2 12 for LCD Display configuration using a LOI Figure 2 12 Display with LOI P...

Page 31: ...alarm on page 61 Table 2 4 Rosemount alarm and saturation values Table 2 5 NAMUR Compliant alarm and saturation values Table 2 6 Custom Alarm and Saturation Values Failure mode alarm and saturation levels can be configured using a Field Communicator AMS Device Manager and the LOI The following limitations exist for custom levels Low alarm level must be less than the low saturation level High alarm...

Page 32: ...erator Interface 2 8 2 Configuring Scaled Variable The Scaled Variable configuration allows the user to create a relationship conversion between the pressure units and user defined custom units There are two use cases for Scaled Variable The first use case is to allow custom units to be displayed on the transmitter s LCD LOI Display The second use case is to allow custom units to drive the transmi...

Page 33: ...id problems due to process noise at a low flow or no flow condition A low flow cutoff value that is practical for the flow element in the application should be entered Configuring Scaled Variable using a Field Communicator 1 Follow the screen prompts to configure Scaled Variable a When configuring for level select Linear under Select Scaled data options b When configuring for flow select Square Ro...

Page 34: ...e process variable reading is 209 4 inH2O The process variable reading is the head pressure created by fill fluid in the capillary Based on Table 2 7 on page 25 the Scaled Variable configuration would be as follows EXTENDED MENU CALIBRAT DAMPING TRANSFER FUNCT SCALED VARIAB SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMLATE HART REV BACK TO MENU EXIT MENU SCALED VARIAB VIEW SCALED CONFI...

Page 35: ... for Flow Application Note Pressure value position 1 and Scaled Variable position 1 are always set to zero for a flow application No configuration of these values is required 2 8 3 Re Mapping device variables The re mapping function allows the transmitter primary secondary tertiary and quaternary variables PV 2V 3V and 4V to be configured as desired The PV can be remapped with a Field Communicator...

Page 36: ...Carefully read the warning and click Yes if it is safe to apply the changes Re mapping using Local Operator Interface Refer to Figure 2 16 for instructions to remap the primary variable using a Local Operator Interface Figure 2 16 Re mapping with Local Operator Interface From the HOME screen enter the fast key sequence Fast Keys 2 1 1 3 VIEW CONFIG ZERO TRIM UNITS RERANGE LOOP TEST DISPLAY EXTENDE...

Page 37: ...20 mA 1 5 Vdc points in addition to alarm levels when installing repairing or replacing a transmitter The host system may provide a current measurement for the 4 20 mA 1 5 Vdc HART output If not connect a reference meter to the transmitter by either connecting the meter to the test terminals on the terminal block or shunting transmitter power through the meter at some point in the loop For 1 5V ou...

Page 38: ...ice variables is only available in HART Revision 7 mode Simulate digital signal with a Field Communicator Simulate digital signal with AMS Device Manager Right click on the device and select Service Tools 1 Click Simulate 2 Under Device Variables select a digital value to simulate a Pressure b Sensor Temperature c Scaled Variable 3 Follow the screen prompts to simulate selected digital value From ...

Page 39: ... Access to information other than dynamic transmitter data is obtained through the normal poll response method of HART communication A Field Communicator AMS Device Manager or the control system may request any of the information that is normally available while the transmitter is in burst mode Between each message sent by the transmitter a short pause allows the Field Communicator AMS Device Mana...

Page 40: ...ation requires consideration of the update rate necessary from each transmitter the combination of transmitter models and the length of the transmission line Communication with transmitters can be accomplished with HART modems and a host implementing HART protocol Each transmitter is identified by a unique address and responds to the commands defined in the HART protocol Field Communicators and AM...

Page 41: ...s the 4 20 mA analog output sending it to 4 mA It also disables the failure mode alarm signal which is controlled by the upscale downscale switch position Failure signals in multidropped transmitters are communicated through HART messages 2 11 1 Changing a transmitter address To activate multidrop communication the transmitter poll address must be assigned a number from 1 to 15 for HART Revision 5...

Page 42: ...up select the HART tab and click the Change Polling Address button 3 Carefully read the warning and click Yes if it is safe to apply the changes 2 11 2 Communicating with a multidropped transmitter To communicate with a multidrop transmitter the Field Communicator or AMS Device Manager has to be set up for Polling Communicating with a multidropped transmitter using a Field Communicator 1 Select Ut...

Page 43: ...fety of the personnel performing the operation Information that raises potential safety issues is indicated by a warning symbol Refer to the following safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and inte...

Page 44: ...emperature change The transmitter electronics temperature operating limits are 40 to 185 F 40 to 85 C Refer to Appendix A Specifications and Reference Data that lists the sensing element operating limits Mount the transmitter so that it is not susceptible to vibration and mechanical shock and does not have external contact with corrosive materials Electrical shock can result in death or serious in...

Page 45: ...ion refer to Appendix A Specifications and Reference Data on page 115 Process flange orientation Mount the process flanges with sufficient clearance for process connections For safety reasons place the drain vent valves so the process fluid is directed away from possible human contact when the vents are used In addition consider the need for a testing or calibration input Note Most transmitters ar...

Page 46: ...75 inch flange bolts Mounting bolts and bolting configurations for the Coplanar and Traditional flanges can be found on page 37 Stainless steel bolts supplied by Emerson Process Management are coated with a lubricant to ease installation Carbon steel bolts do not require lubrication No additional lubricant should be applied when installing either type of bolt Bolts supplied by Emerson Process Mana...

Page 47: ...g bolts and bolt configurations for coplanar flange A Transmitter with flange bolts B Transmitter with flange adapters and flange adapter bolts C 1 75 44 4 D 2 88 73 4 1 For Gage and Absolute Transmitters 150 38 x 2 B A C C D E F E F C D A B Description Qty Size in mm Differential Pressure Flange Bolts 4 1 75 44 Flange Adapter Bolts 4 2 88 73 Gage Absolute Pressure 1 1 Rosemount 2051T transmitters...

Page 48: ...s millimeters Figure 3 4 Mounting bracket option codes B1 B7 and BA A 3 75 95 B 1 63 41 C 4 09 104 D 2 73 69 E 4 97 126 F 2 81 71 Figure 3 5 Panel mounting bracket option codes B2 and B8 A 3 75 95 B 1 63 41 C 4 09 104 D 2 81 71 E 4 5 114 A 1 40 36 B Mounting Holes 0 375 Diameter 10 C 1 405 35 7 D 1 405 35 7 C A B D E F B C E D B A D A C ...

Page 49: ... bolts 2 Torque the bolts to the initial torque value using a crossing pattern see Table 3 4 2 for torque values 3 Torque the bolts to the final torque value using the same crossing pattern Mounting brackets Rosemount 2051 transmitters may be panel mounted or pipe mounted via an optional mounting bracket Refer to Table 3 2 for the complete offering and see Figure 3 7 through Figure 3 6 on pages 41...

Page 50: ...e 3 2 Mounting brackets Rosemount 2051 brackets Option code Process connections Mounting Materials Coplanar In line Traditional Pipe mount Panel mount Flat panel mount CS bracket SST bracket CS bolts SST bolts B4 X X X X X X X B1 X X X X B2 X X X X B3 X X X X B7 X X X X B8 X X X X B9 X X X X BA X X X X BC X X X X ...

Page 51: ... Not Supplied B 3 4 85 C 3 8 16 x 11 4 Bolts for Mounting to Transmitter D 2 8 71 Note Dimensions are in inches millimeters E 3 85 98 F 5 16 131 G 1 99 51 H 4 72 120 I 6 90 175 A B C D E G H I D F Carbon Steel CS Head Markings B7M 316 B8M F593_ Stainless Steel SST Head Markings KM 660 CL A Alloy K 500 Head Marking The last digit in the F593_ head marking may be any letter between A and M ...

Page 52: ... vent valve upward to allow gases to vent Gas measurement Place taps in the top or side of the line Mount the transmitter beside or above the taps so liquid will drain into the process line Steam measurement Place taps to the side of the line Mount the transmitter below the taps to ensure that the impulse piping will stay filled with condensate In steam service above 250 F 121 C fill impulse lines...

Page 53: ...pplications installation example A Coplanar B Inline Best practices The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements There are five possible sources of error pressure transfer leaks friction loss particularly if purging is used trapped gas in a liquid line liquid in a gas line and density variations between the legs B A A B ...

Page 54: ...n equal leg of head pressure on both legs of the impulse piping Avoid conditions that might allow process fluid to freeze within the process flange 3 4 3 Process connections Coplanar or traditional process connection Install and tighten all four flange bolts before applying pressure or process leakage will result When properly installed the flange bolts will protrude through the top of the sensor ...

Page 55: ...ote PTFE O rings should be replaced if the flange adapter is removed 3 4 4 Inline process connection Inline gage transmitter orientation The low side pressure port on the inline gage transmitter is located in the neck of the transmitter behind the housing The vent path is 360 degrees around the transmitter between the housing and sensor See Figure 3 11 Keep the vent path free of any obstruction su...

Page 56: ... April 2013 Hardware Installation Do not apply torque directly to the sensor module Rotation between the sensor module and the process connection can damage the electronics To avoid damage apply torque only to the hex shaped process connection Sensor Module Process Connection ...

Page 57: ...d to most primary elements with mounting adapters in the market today The 306 Integral Manifold is used with the Rosemount 2051T in line transmitters to provide block and bleed valve capabilities of up to 10000 psi 690 bar Figure 3 12 Manifolds The 304 conventional manifold combines a traditional flange and manifold that can be mounted to most primary elements ROSEMOUNT 2051C AND 305 INTEGRAL COPL...

Page 58: ...module Use the four 2 25 in manifold bolts for alignment Finger tighten the bolts then tighten the bolts incrementally in a cross pattern as seen in Figure 3 13 to final torque value See Flange bolts on page 36 for complete bolt installation information and torque values When fully tightened the bolts should extend through the top of the sensor module housing Figure 3 13 Bolt tightening pattern 3 ...

Page 59: ... Leak check assembly to maximum pressure range of transmitter 3 5 4 Manifold operation Improper installation or operation of manifolds may result in process leaks which may cause death or serious injury Always perform a zero trim on the transmitter manifold assembly after installation to eliminate any shift due to mounting effects See Sensor Trim Overview on page 10 Three and five valve configurat...

Page 60: ...n both sides of the transmitter The manifold valves are now in the proper configuration for zeroing the transmitter Drain Vent Valve Drain Vent Valve Equalize closed Process Isolate closed Isolate open H L 3 After zeroing the transmitter close the equalizing valve Drain Vent Valve Drain Vent Valve Equalize closed Process Isolate open Isolate open H L 4 Open the block valve on the low pressure side...

Page 61: ...lock valves between the process and instrument ports will be open and the equalizing valves will be closed Process Equalize closed Drain Vent closed Test Plugged Test Plugged Equalize closed Process Isolate closed Isolate open H L 1 To zero the Rosemount 2051 first close the block valve on the low pressure downstream side of the transmitter Process Equalize closed Drain Vent closed Test Plugged Te...

Page 62: ...Plugged Equalize closed Process Isolate closed Isolate open H L 4 After zeroing the transmitter close the equalize valve on the low pressure downstream side of the transmitter Process Equalize open Drain Vent closed 5 Close the equalize valve on the high pressure upstream side Test Plugged Test Plugged Equalize closed Process Isolate closed Isolate open H L Process Equalize closed Drain Vent close...

Page 63: ...section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Refer to the following safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be i...

Page 64: ...he display and electronics board are not compatible Figure 4 1 LOI Display assembly A LCD LOI Display B Extended cover 4 3 1 Rotating LCD LOI Display 1 Secure the loop to manual control and remove power to transmitter 2 Remove transmitter housing cover 3 Remove screws form the LCD LOI Display and rotate to desired orientation a Insert 10 pin connector into the display board for the correct orienta...

Page 65: ...to prevent changes to the transmitter configuration data If the security switch is set to the locked location any transmitter configuration requests sent via HART LOI or local configuration buttons will be rejected by the transmitter and the transmitter configuration data will not be modified Reference Figure 4 2 for the location of the security switch Follow the steps below to enable the security...

Page 66: ... 3 Click Lock Unlock button under HART Lock Software and follow the screen prompts 4 4 3 Configuration Button lock The configuration button lock disables all local button functionality Changes to the transmitter configuration from the LOI and local buttons will be rejected Local external keys can be locked via HART communication only Configuring configuration button lock using a Field Communicator...

Page 67: ...e Security tab 3 Within the Local Operator Interface click the Configure Password button and follow the screen prompts Configuring LOI password using Local Operator Interface Figure 4 3 Local Operator Interface password 4 5 Setting Transmitter alarm On the electronics board is an alarm switch reference Figure 4 2 on page 55 for switch location Follow the steps below to change the alarm switch loca...

Page 68: ...ation diagrams A Possible conduit line positions B Sealing compound Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment If all connections are not sealed excess moisture accumulation can damage the transmitter Make sure to mount the transmitter with the electrical housing positioned downward for drainage To avoid moisture accumulation in the housi...

Page 69: ... and the load resistance of the controller indicator I S Barriers and related pieces If intrinsic safety barriers are used the resistance and voltage drop must be included 1 5 Vdc Low Power HART output code M Low power transmitters operate on 9 28 Vdc The dc power supply should provide power with less than 2 percent ripple The Vout load should be 100 k or greater 4 6 3 Wiring the transmitter Note ...

Page 70: ...n explosive atmospheres when the circuit is live Signal wiring supplies all power to the transmitter 2 For 4 20 mA HART output connect the positive lead to the terminal marked pwr comm and the negative lead to the terminal marked pwr comm Do not connect the powered signal wiring to the test terminals Power could damage the test diode a For 1 5 Vdc HART Output connect the positive lead to PWR and t...

Page 71: ... Cover 2 Connect the signal wire pair at the field terminals as indicated in Figure 4 6 3 At the field terminals the cable shield and shield drain wire should be trimmed close and insulated from transmitter housing 4 Reattach the Field Terminals Housing Cover cover must be fully engaged to comply with explosion proof requirements 5 At terminations outside the transmitter housing the cable shield d...

Page 72: ...de the FIELD TERMINALS side of the electronics housing This screw is identified by a ground symbol The ground connection screw is standard on all Rosemount 2051 transmitters Refer to Figure 4 9 on page 62 External ground connection The external ground connection is located on the exterior of the transmitter housing Refer to Figure 4 10 on page 62 This connection is only available with option V5 an...

Page 73: ...nsmitter The transient protection terminal block can be ordered as an installed option Option Code T1 or as a spare part to retrofit existing Rosemount 2051 transmitters in the field See Spare parts on page 171 for part numbers The lightning bolt symbol shown in Figure 4 11 on page 63 identifies the transient protection terminal block Figure 4 11 Transient protection Terminal Block A Lightning bol...

Page 74: ...64 Reference Manual 00809 0100 4107 Rev BA Section 4 Electrical Installation April 2013 Electrical Installation ...

Page 75: ...messages before performing an operation preceded by this symbol 5 2 1 Warnings Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Please review the approvals section of the Rosemount 2051 reference manual for any restrictions associa...

Page 76: ...s accurate pressure standards sources to provide a full calibration Like the Sensor Calibration the analog output can be calibrated to match the user measurement system The Analog Output Trim 4 20mA 1 5 VOutput Trim will calibrate the loop at the 4mA 1 V and 20mA 5 V points Absolute pressure transmitters Rosemount 2051CA and Rosemount 2051TA are calibrated at the factory Trimming adjusts the posit...

Page 77: ...on page 51 allow the differential transmitter to be zeroed using the zero trim function Both 3 valve and 5 valve manifolds are discussed This field calibration will eliminate any pressure offsets caused by mounting effects head effect of the oil fill and static pressure effects of the process Determine the necessary trims with the following steps 1 Apply Pressure 2 Check digital pressure if the di...

Page 78: ...on performance requirements and process conditions Use the following procedure to determine calibration frequency that meets the needs of your application 1 Determine the performance required for your application 2 Determine the operating conditions 3 Calculate the Total Probable Error TPE 4 Calculate the stability per month 5 Calculate the calibration frequency Sample calculation for Rosemount 20...

Page 79: ...rmance 0 30 of span Transmitter 2051CD Range 2 URL 250 inH2O 623 mbar Calibrated Span 150 inH2O 374 mbar Ambient Temperature Change 50 F 28 C Line Pressure 500 psig 34 5 bar TPE 0 117 of span Where Reference Accuracy 0 05 of span Ambient Temperature Effect Span Static Pressure Effect 1 1 Zero static pressure effect removed by zero trimming at line pressure ReferenceAccuracy 2 TemperatureEffect 2 S...

Page 80: ...ressures from 0 to 3626 psi 0 to 250 bar Use the following example to compute correct input values Example A range 4 differential pressure HART transmitter Rosemount 2051CD4 will be used in an application with a static line pressure of 1200 psi 83 bar The transmitter output is ranged with 4mA at 500 inH20 1 2 bar and 20mA at 1500 inH20 3 7 bar To correct for systematic error caused by high static ...

Page 81: ...ince this correction maintains the slope of the characterization curve it should not be used in place of a Sensor Trim over the full sensor range When performing a zero trim ensure that the equalizing valve is open and all wet legs are filled to the correct levels Line pressure should be applied to the transmitter during a zero trim to eliminate line pressure errors Refer to Manifold operation on ...

Page 82: ...ming a Sensor Trim with a Field Communicator From the HOME screen enter the fast key sequence and follow the steps within the Field Communicator to complete the Sensor Trim To calibrate the sensor with a Field Communicator using the Sensor Trim function perform the following procedure 1 Select Lower Sensor Trim Note Select pressure points so that lower and upper values are equal to or outside the ...

Page 83: ...tter is at zero pressure If the transmitter is not close enough to zero when the button is pushed the command may fail due to excess correction If ordered a Digital Zero Trim can be performed by utilizing external configuration buttons located underneath the top tag of the transmitter see Figure 5 1 on page 68 for DZ button location 1 Loosen the top tag of the transmitter to expose buttons 2 Press...

Page 84: ...r Trim Figure 5 4 Recall Factory Trim Sensor Trim with Local Operator Interface 5 6 Trim the analog output The Analog Output Trim commands allow you to adjust the transmitter s current output at the 4 and 20 mA points to match the plant standards This trim is performed after the digital to analog conversion so only the 4 20mA analog signal will be affected Figure 5 5 graphically shows the two ways...

Page 85: ...sistance Refer to Power supply for 4 20 mA HART on page 63 Performing a 4 20 mA 1 5 V output trim with a Field Communicator From the HOME screen enter the fast key sequence and follow the steps within the Field Communicator to complete the 4 20 mA output trim Performing a 4 20 mA 1 5 V output trim with AMS Device Manager Right click on the device and under the Method drop down menu move cursor ove...

Page 86: ...utput Trim procedure Performing a 4 20 1 5 V mA output trim using other scale with a Field Communicator From the HOME screen enter the fast key sequence and follow the steps within the Field Communicator to complete the 4 20 mA output trim using other scale Performing a 4 20 mA 1 5 V output trim using other scale with AMS Device Manager Right click on the device and under the Method drop down menu...

Page 87: ...der the Method drop down menu move cursor over Calibrate and select Restore Factory Calibration 1 Click Next to set the control loop to manual 2 Select Analog Output Trim under Select trim to recall and click Next 3 Follow screen prompts to recall analog output trim Recalling Factory Trim analog output with Local Operator Interface Reference Figure 5 7 for LOI instructions Figure 5 7 Recall Factor...

Page 88: ...hange to HART Revision 5 Enter HART5 in the message field b To change to HART Revision 7 Enter HART7 in the message field 5 7 2 Switching HART Revision with Field Communicator From the HOME screen enter the fast key sequence and follow steps within the Field Communicator to complete the HART revision change 5 7 3 Switching HART Revision with AMS Device Manager 1 Click on Manual Setup and select HA...

Page 89: ...enance Figure 5 8 Change HART revision with Local Operator Interface EXTENDED MENU CALIBRAT DAMPING TRANSFER FUNCT SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMULATE HART REV HART REV BACK TO MENU EXIT MENU VIEW CONFIG ZERO TRIM UNITS RERANGE LOOP TEST DISPLAY EXTENDED MENU EXTENDED MENU EXIT MENU ...

Page 90: ...80 Reference Manual 00809 0100 4107 Rev BA Section 5 Operation and Maintenance April 2013 Operation and Maintenance ...

Page 91: ...e most common operating problems If you suspect malfunction despite the absence of any diagnostic messages on the Field Communicator display consider using Section 6 3 on page 84 to identify any potential problem 6 2 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises pot...

Page 92: ... associated with a safe installation Before connecting a Field Communicator in an explosive atmosphere ensure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices In an Explosion Proof Flameproof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death Insta...

Page 93: ... not in alarm condition Perform analog trim Check that power wires are connected to the correct signal terminals positive to positive negative to negative and not the test terminal Transmitter will not respond to changes in applied pressure Check impulse piping or manifold for blockage Verify applied pressure is between the 4 and 20 mA points Verify the output is not in alarm condition Verify tran...

Page 94: ...Replace the pressure sensor Electronics Board Failure FAIL BOARD FAIL BOARD A failure has been detected in the electronics circuit board 1 Replace the electronics board Critical Sensor Data Error MEMRY ERROR MEMORY ERROR A user written parameter does not match the expected value 1 Confirm and correct all parameters listed in Device Information 2 Perform a Device Reset 3 Replace sensor module Criti...

Page 95: ... the pressure sensor Sensor Temperature Beyond Limits TEMP LIMITS TEMP OUT LIMITS The sensor temperature has exceeded its safe operating range 1 Check the process and ambient conditions are within 85 to 194 F 65 to 90 C 2 Replace the pressure sensor Electronics Temperature Beyond Limits The temperature of the electronics has exceeded its safe operating range 1 Confirm electronics temperature is wi...

Page 96: ...ics board Configuration Changed none none A recent change has been made the device by a secondary HART master such as a handheld device 1 Verify that the configuration change of the device was intended and expected 2 Clear this alert by selecting Clear Configuration Changed Status 3 Connect a HART master such as AMS Device Manager or similar which will automatically clear it Analog Output Fixed AN...

Page 97: ...051T transmitter is attached to the process by a single hex nut process connection Loosen the hex nut to separate the transmitter from the process Do not wrench on neck of transmitter See warning in Inline process connection on page 49 6 Do not scratch puncture or depress the isolating diaphragms 7 Clean isolating diaphragms with a soft rag and a mild cleaning solution and rinse with clear water 8...

Page 98: ...re 4 3 LCD Display for screw locations The two screws anchor the LCD LOI Display to the electronics board and the electronics board to the housing Note The electronics board is electrostatically sensitive observe handling precautions for static sensitive components 3 Using the two captive screws slowly pull the electronics board out of the housing The sensor module ribbon cable holds the electroni...

Page 99: ...k cap 4 Turn the module clockwise into the housing Important Make sure the sensor ribbon cable and internal black cap remain completely free of the housing as you rotate it Damage can occur to the cable if the internal black cap and ribbon cable become hung up and rotate with the housing 5 Thread the housing completely onto the sensor module The housing must be no more than one full turn from flus...

Page 100: ...installing the two alignment screws to finger tightness screws are not pressure retaining Do not overtighten as this will affect module to flange alignment Install the four 1 75 in flange bolts by finger tightening them to the flange b Coplanar Process Flange with Flange Adapters Hold the process flange in place by installing the two alignment screws to finger tightness screws are not pressure ret...

Page 101: ...r two hours before calibration 6 5 4 Installing drain vent valve 1 Apply sealing tape to the threads on the seat Starting at the base of the valve with the threaded end pointing toward the installer apply five clockwise turns of sealing tape 2 Tighten the drain vent valve seat to 250 in lb 28 25 N m 3 Take care to place the opening on the valve so that process fluid will drain toward the ground an...

Page 102: ...92 Reference Manual 00809 0100 4107 Rev BA Section 6 Troubleshooting April 2013 Troubleshooting ...

Page 103: ...identified as safety certified before installing into SIS systems To identify a safety certified Rosemount 2051C Rosemount 2051T Rosemount 2051L 1 Check Namur Software Revision located on the metal device tag SW _ _ _ 2 Transmitter Output Code A 4 20 mA HART 7 1 2 Installation in SIS applications Installations are to be performed by qualified personnel No special installation is required in additi...

Page 104: ...ect the transmitters ability to respond to changes in the applied process The damping value response time must not exceed the loop requirements Reference Damping on page 19 to change damping value Alarm and saturation levels DCS or safety logic solver should be configured to match transmitter configuration Figure 7 1 identifies the three alarm levels available and their operation values Figure 7 1...

Page 105: ...EDA Report for percent of possible DU failures in the device FMEDA report can be found at www rosemount com safety Required tools Field Communicator and mA meter 1 Bypass the safety function and take appropriate action to avoid a false trip 2 Use HART communications to retrieve any diagnostics and take appropriate action 3 Send a HART command to the transmitter to go to the high alarm current outp...

Page 106: ...erwise restore the normal operation 7 Place the Security switch in the position Note The user determines the proof test requirements for impulse piping Automatic diagnostics are defined for the corrected DU The tests performed internally by the device during runtime without requiring enabling or programming by the user Calculation of average probability of failure on demand PFDAVG PFDAVG calculati...

Page 107: ...ence Data Failure rate data The FMEDA report includes failure rates and common cause Beta factor estimates The report is available at www rosemount com safety Failure values Product life 50 years based on worst case component wear out mechanisms not based on wear out of process wetted materials Report any safety related product information at http rosemount d1asia ph rosemount safety ReportAFailur...

Page 108: ...98 Reference Manual 00809 0100 4107 Rev BA Section 7 Safety Instrumented Systems Requirements April 2013 Safety Instrumented Systems Requirements ...

Page 109: ...hysical specifications page 109 Dimensional drawings page 113 Ordering Information page 125 Options page 159 Spare parts page 164 A 1 Performance specifications A 1 1 Conformance to specification 3 Sigma Technology leadership advanced manufacturing techniques and statistical process control ensure specification conformance to at least 3 A 1 2 Reference accuracy Stated reference accuracy equations ...

Page 110: ...2051L Ranges 2 4 0 075 of span For spans less than 10 1 accuracy 2051CFA Annubar Flowmeter Ranges 2 3 2 00 of Flow Rate at 5 1 flow turndown 2051CFC Compact Orifice Flowmeter Conditioning Option C Ranges 2 3 0 4 2 25 of Flow Rate at 5 1 flow turndown 0 65 2 45 of Flow Rate at 5 1 flow turndown 2051CFC Compact Orifice Flowmeter Orifice Type Option P 1 1 For smaller line sizes see Rosemount Compact ...

Page 111: ...me Td 60 ms nominal 97 ms Update Rate 22 times per second 22 times per second 1 Dead time and update rate apply to all models and ranges analog output only 2 Nominal total response time at 75 F 24 C reference conditions 3 Transducer block response time Analog Input block execution time not included For line pressures above 2000 psi 13 7 MPa and Ranges 4 5 see user manual Document number 00809 0100...

Page 112: ...RL 0 25 span from 5 1 to 100 1 0 0125 URL 0 0625 span from 1 1 to 5 1 0 025 URL 0 125 span from 5 1 to 100 1 Range 1 0 1 URL 0 25 span from 1 1 to 30 1 2051T Range 2 4 0 05 URL 0 25 span from 1 1 to 30 1 0 07 URL 0 25 span from 30 1 to 100 1 0 025 URL 0 125 span from 1 1 to 30 1 0 035 URL 0 125 span from 30 1 to 100 1 Range 1 0 05 URL 0 25 span from 1 1 to 10 1 0 10 URL 0 25 span from 10 1 to 100 ...

Page 113: ...bar 250 inH2O 0 62 bar 250 inH2O 0 62 bar 3 10 inH2O 24 9 mbar 1000 inH2O 2 49 bar 1000 inH2O 2 49 bar 393 inH2O 979 mbar 1000 inH2O 2 49 bar 393 inH2O 979 mbar 4 3 psi 0 207 bar 300 psi 20 6 bar 300 psi 20 6 bar 14 2 psig 979 mbar 300 psi 20 7 bar 14 2 psig 979 mbar 5 20 psi 1 38 bar 2000 psi 137 9 bar 2000 psi 137 9 bar 14 2 psig 979 mbar N A N A Table 2 Range and Sensor Limits Range 2051T Minim...

Page 114: ...able 1 and Table 2 Span must be greater than or equal to the minimum span stated in Table 1 and Table 2 Output 2051 Digital communications based on HART Revision 5 protocol 2051 with Selectable HART The 2051 with Selectable HART comes with Selectable HART Revisions Digital communications based on HART Revision 5 default or Revision 7 option code HR7 protocol can be selected The HART revision can b...

Page 115: ... Selectable HART The 2051 with Selectable HART comes with Selectable HART Revisions Digital communications based on HART Revision 5 default or Revision 7 option code HR7 protocol can be selected The HART revision can be switched in the field using any HART based configuration tool or the optional local operator interface LOI Local Operator Interface The LOI utilizes a 2 button menu with internal a...

Page 116: ...psia to the flange rating or sensor rating whichever is lower A 2 6 Static pressure limit Rosemount 2051CD 2051CF Operates within specifications between static line pressures of 14 2 psig 0 034 bar and 3 626 psig 250 bar For Option Code P9 4 500 psig 310 3 bar Range 1 0 5 psia to 2 000 psig 34 mbar and 137 9 bar Table 3 Rosemount 2051L flange rating Standard Type CS Rating SST Rating ANSI ASME Cla...

Page 117: ...ves its output in failure mode depend on whether it is factory configured to standard NAMUR compliant or custom levels see Alarm Configuration below The values for each are as follows A 2 9 Temperature limits Process At atmospheric pressures and above See Table 4 High alarm Low alarm Default 21 75 mA 3 75 mA NAMUR compliant 1 1 Analog output levels are compliant with NAMUR recommendation NE 43 see...

Page 118: ...4 C forpressuresbelow 0 5 psia with Traditional Flange 40 to 300 F 40 to 149 C 2 3 with Level Flange 40 to 300 F 40 to 149 C 2 with 305 Integral Manifold 40 to 300 F 40 to 149 C 2 Inert Fill Sensor 1 40 to 185 F 40 to 85 C 3 3 160 F 71 C limit in vacuum service 2051T Process Fill Fluid Silicone Fill Sensor 1 40 to 250 F 40 to 121 C 2 Inert Fill Sensor 1 22 to 250 F 30 to 121 C 2 2051L Low Side Tem...

Page 119: ...nections Rosemount 2051C 1 4 18 NPT on 21 8 in centers 1 2 14 NPT and RC 1 2 on 2 in 50 8 mm 2 1 8 in 54 0 mm or 2 1 4 in 57 2 mm centers process adapters Rosemount 2051L High pressure side 2 in 50 8 mm 3 in 72 mm or 4 in 102 mm ASME B 16 5 ANSI Class 150 or 300 flange 50 80 or 100 mm DIN 2501 PN 40 or 10 16 flange Low pressure side 1 4 18 NPT on flange 1 2 14 NPT on process adapter Rosemount 2051...

Page 120: ...ed PTFE or Graphite filled PTFE Process isolating diaphragms A 3 4 Rosemount 2051L process wetted parts Flanged process connection transmitter high side Process Diaphragms including Process Gasket surface 316L SST Alloy C 276 or Tantalum Extension CF 3M Cast version of 316L SST material per ASTM A743 or Alloy C 276 Fits schedule 40 and 80 pipe Mounting flange Zinc cobalt plated CS or SST Reference...

Page 121: ...IP 65 IP 66 IP 68 Coplanar sensor module housing CF 3M Cast version of 316L SST material per ASTM A743 Bolts ASTM A449 Type 1 zinc cobalt plated carbon steel ASTM F593G Condition CW1 Austenitic 316 SST ASTM A193 Grade B7M zinc plated alloy steel Alloy K 500 Sensor module fill fluid Silicone or inert halocarbon In line series uses Fluorinert FC 43 Process fill fluid Rosemount 2051L only Syltherm XL...

Page 122: ...4 27 2 12 3 28 2 12 8 29 2 13 2 DN 50 PN 40 13 8 6 2 DN 80 PN 40 19 5 8 8 21 5 9 7 22 5 10 2 23 5 10 6 DN 100 PN 10 16 17 8 8 1 19 8 9 0 20 8 9 5 21 8 9 9 DN 100 PN 40 23 2 10 5 25 2 11 5 26 2 11 9 27 2 12 3 Table 7 Transmitter Options Weights Code Option Add lb kg J K L M Stainless Steel Housing 3 9 1 8 M5 LCD display for Aluminum Housing 0 5 0 2 B4 SST Mounting Bracket for Coplanar Flange 1 0 0 ...

Page 123: ...tation Set Screw 180 Maximum Housing Rotation without Further Disassembly Flange Alignment Screw Not Pressure Retaining Flange Bolts Flange Adapters Drain Vent Valve Coplanar Flange Flange Adapter O Ring Process O Ring Local Configuration Buttons 1 Nameplate 1 Span and Zero Adjustment Buttons are optional with 4 20 mA and 1 5 Vdc HART protocol Local Operator Interface buttons are optional for PROF...

Page 124: ... 3 Valve Coplanar Integral Manifold Dimensions are in inches millimeters 3 85 98 7 03 179 6 40 163 4 36 111 5 20 132 5 66 144 Terminal Connections Fieldbus Display Cover HART Display Cover Transmitter Circuitry 3 85 98 7 44 189 Drain Vent Valve 5 00 127 Max Open 6 19 157 9 20 234 Max Open 4 36 111 5 20 132 5 66 144 Terminal Connections Fieldbus Display Cover HART Display Cover Transmitter Circuitr...

Page 125: ...e Mounting Configurations with Optional Bracket B4 for 2 in Pipe or Panel Mounting PANEL MOUNTING PIPE MOUNTING Dimensions are in inches millimeters 4 36 111 2 82 72 7 03 178 2 8 4 73 120 6 15 156 2 18 55 5 16 11 2 Bolts for Panel Mounting Not Supplied 3 8 16 11 4 Bolts for Mounting to Transmitter 2 8 71 3 4 85 6 22 158 3 51 89 2 inch U Bolt for Pipe Mounting ...

Page 126: ...6 197 3 40 86 1 10 28 1 2 14 NPT Flange Adapter optional Drain Vent Valve 1 05 27 1 626 41 3 2 13 54 4 36 111 5 20 132 5 66 144 Terminal Connections Fieldbus Display Cover HART Display Cover Transmitter Circuitry 3 85 98 1 2 14 NPT Flange Adapter optional Drain Vent Valve 3 50 89 1 05 27 1 10 28 3 75 95 Max Open 6 19 157 2 126 54 6 20 158 Max Open 8 90 226 Max Open 2 70 69 Max Open 1 626 71 4 36 1...

Page 127: ...g Configurations with Optional Brackets for 2 in Pipe or Panel Mounting Panel Mount Bracket Option B2 B8 Pipe Mount Bracket Option B3 B9 BC Pipe Mount Bracket Option B1 B7 BA Dimensions are in inches millimeters 9 18 233 2 62 67 6 19 157 5 32 135 1 94 49 3 50 89 1 10 28 3 56 90 Max Open 4 85 123 6 19 157 11 51 292 6 76 172 3 56 90 MAX OPEN 1 10 28 3 50 89 2 62 67 0 93 24 ...

Page 128: ...T with Rosemount 306 2 Valve Integral Manifold Dimensions are in inches millimeters 3 85 98 7 15 182 4 36 111 5 20 132 5 66 144 Terminal Connections Fieldbus Display Cover HART Display Cover Transmitter Circuitry 3 85 98 7 15 182 4 85 123 6 25 159 Max Open 4 40 112 4 36 111 5 20 132 5 66 144 Terminal Connections Fieldbus Display Cover HART Display Cover Transmitter Circuitry ...

Page 129: ... Pak Lok Annubar model is available up to 600 ANSI 1 440 psig at 100 F 99 bar at 38 C Front View Side View Top View Table 8 2051CFA Pak Lok Annubar Flowmeter Dimensional Data Sensor Size A Max B Max C Max D Max 1 8 50 215 9 14 55 369 6 9 00 228 6 6 00 152 4 2 11 00 279 4 16 30 414 0 9 00 228 6 6 00 152 4 3 12 00 304 8 19 05 483 9 9 00 228 6 6 00 152 4 Dimensions are in inches millimeters B A D C ...

Page 130: ...ifice Plate Front View Orifice Plate Top View Compact Orifice Plate Primary Element Type code P Conditioning Orifice Plate Primary Element Type code C Table 9 2051CFC Dimensional Drawings Primary Element Type A B Transmitter Height C D Type P and C 5 62 143 Transmitter Height A 6 27 159 7 75 197 closed 8 25 210 open 6 00 152 closed 6 25 159 open Dimensions are in inches millimeters 1 13 in 28 7 mm...

Page 131: ...8 52 724 4 J RF 150 weld neck 14 37 364 9 22 37 568 1 30 82 782 9 J RF 300 weld neck 14 56 369 8 22 63 574 7 31 06 789 0 J RF 600 weld neck 14 81 376 0 22 88 581 0 31 38 797 1 K Beveled Threaded pipe ends 5 74 145 7 8 75 222 2 11 91 302 6 K RF slip on RTJ slip on RF DIN slip on 1 5 82 147 8 8 83 224 2 11 99 304 6 K RF 150 weld neck 7 57 192 3 10 88 276 3 14 29 363 1 K RF 300 weld neck 7 76 197 1 1...

Page 132: ...Specifications and Reference Data April 2013 Appendix A Specifications and Reference Data 2051L Liquid Level 2 in Flange Configuration Flush Mount Only 3 and 4 in Flange Configuration 3 85 98 A H 3 85 98 D A H 2 in 4 in or 6 in Extension 50 8 101 6 152 4 E ...

Page 133: ... 0 88 22 7 5 191 9 0 229 8 0 75 19 3 5 89 6 2 158 ASME B16 5 ANSI 300 2 51 0 82 21 5 0 127 6 5 165 8 0 75 19 NA 3 6 92 3 76 1 06 27 6 62 168 8 25 210 8 0 88 22 2 58 66 5 0 127 4 102 1 19 30 7 88 200 10 0 254 8 0 88 22 3 5 89 6 2 158 ASME B16 5 ANSI 600 2 51 1 00 25 5 0 127 6 5 165 8 0 75 19 NA 3 6 92 3 76 1 25 32 6 62 168 8 25 210 8 0 88 22 2 58 66 5 0 127 DIN 2501 PN 10 40 DN 50 20 mm 125 mm 165 ...

Page 134: ... 76 3 6 91 0 97 25 1 31 33 5 65 143 4 102 3 6 91 0 97 25 1 31 33 5 65 143 ASME B16 5 ANSI 300 2 51 2 12 54 0 97 25 1 31 33 5 65 143 3 76 3 6 91 0 97 25 1 31 33 5 65 143 4 102 3 6 91 0 97 25 1 31 33 5 65 143 ASME B16 5 ANSI 600 2 51 2 12 54 0 97 25 1 31 33 7 65 194 3 76 3 6 91 0 97 25 1 31 33 7 65 194 DIN 2501 PN 10 40 DN 50 2 4 61 0 97 25 1 31 33 5 65 143 DIN 2501 PN 25 40 DN 80 3 6 91 0 97 25 1 3...

Page 135: ...ransmitters Ordering Information The Standard offering represents the most common options The starred options should be selected for best delivery __The Expanded offering is subject to additional delivery lead time Model Transmitter Type 2051C Coplanar Pressure Transmitter Measurement Type Standard Standard D Differential G Gage Pressure Range Standard Standard 2051CD 2051CG 1 25 to 25 inH2O 62 2 ...

Page 136: ...ntalum O ring Standard Standard A Glass filled PTFE B Graphite filled PTFE Sensor Fill Fluid Standard Standard 1 Silicone 2 Inert Housing Material Conduit Entry Size Standard Standard A Aluminum 14 NPT B Aluminum M20 1 5 J SST 14 NPT K 4 SST M20 1 5 Expanded D Aluminum G M 4 SST G Options Include with selected model number PlantWeb Control Functionality Standard Standard A01 FOUNDATION fieldbus Ad...

Page 137: ...305 Integral Manifold S6 Assemble to Rosemount 304 Manifold or Connection System Integral Mount Primary Element 6 7 Standard Standard S4 8 Assemble to Rosemount Annubar Flowmeter or Rosemount 1195 Integral Orifice S3 Assemble to Rosemount 405 Primary Element Seal Assemblies 7 Standard Standard S1 9 Assemble to one Rosemount 1199 diaphragm seal S2 10 Assemble to two Rosemount 1199 diaphragm seals M...

Page 138: ...rinsic Safety K5 FM Explosion proof Dust Ignition proof Intrinsically Safe Division 2 K6 CSA Explosion proof Dust Ignition proof Intrinsically Safe Division 2 K7 4 IECEx Flameproof Intrinsic Safety Type n and Dust KA 4 ATEX and CSA Flameproof Intrinsically Safe Division 2 KB FM and CSA Explosion proof Dust Ignition proof Intrinsically Safe Division 2 KC 4 FM and ATEX Explosion proof Intrinsically ...

Page 139: ...V5 18 External Ground Screw Assembly Performance Standard Standard P8 19 High Performance Option Transient Protection Standard Standard T1 20 Transient Protection Terminal Block Software Configuration Standard Standard C1 21 Custom Software Configuration Completed CDS 00806 0100 4101 required with order Alarm Limit Standard Standard C4 14 22 NAMUR alarm and saturation levels high alarm CN 14 22 NA...

Page 140: ...olkit Total System Performance Reports Standard Standard QZ Remote Seal System Performance Calculation Report Conduit Electrical Connection Standard Standard GE M12 4 pin Male Connector eurorast GM A size Mini 4 pin Male Connector minifast HART Revision Configuration Standard Standard HR5 14 23 Configured for HART Revision 5 HR7 14 24 Configured for HART Revision 7 Typical Model Number 2051C D 2 A...

Page 141: ...ailable with HART 4 20 mA output codes A and M 15 Not valid with Alternate Process Connection options S3 S4 S5 S6 16 Transmitter is shipped with 316 SST conduit plug uninstalled in place of standard carbon steel conduit plug 17 Not available with Alternate Process Connection DIN Flanges and Level Flanges 18 The V5 option is not needed with the T1 option external ground screw assembly is included w...

Page 142: ...sure Transmitter Ordering Information The Standard offering represents the most common options The starred options should be selected for best delivery __The Expanded offering is subject to additional delivery lead time Model Transmitter Type Standard Standard 2051T In Line Pressure Transmitter Pressure Type Standard Standard G Gage A Absolute Pressure Range Standard Standard 2051TG 2051TA 1 14 7 ...

Page 143: ...ard Standard A Aluminum 14 NPT B Aluminum M20 1 5 J SST 14 NPT K 3 SST M20 1 5 Expanded D Aluminum G M 3 SST G Options Include with selected model number PlantWeb Control Functionality Standard Standard A01 FOUNDATION fieldbus Advanced Control Function Block Suite Manifold Assemblies Standard Standard S5 4 Assemble to Rosemount 306 Integral Manifold Seal Assemblies Standard Standard S1 4 Assemble ...

Page 144: ...FM Explosion proof Dust Ignition proof Intrinsically Safe Division 2 K6 CSA Explosion proof Dust Ignition proof Intrinsically Safe Division 2 K7 3 IECEx Flameproof Intrinsic Safety Type n and Dust KA 3 ATEX and CSA Flameproof Intrinsically Safe Division 2 KB FM and CSA Explosion proof Dust Ignition proof Intrinsically Safe Division 2 KC 3 FM and ATEX Explosion proof Intrinsically Safe Division 2 K...

Page 145: ... Compliant with NAMUR Recommendation NE 43 Alarm High CN 7 13 Analog Output Levels Compliant with NAMUR Recommendation NE 43 Alarm Low CR 7 Custom Alarm and saturation signal levels high alarm requires C1 and Configuration Data Sheet CS 7 Custom Alarm and saturation signal levels low alarm requires C1 and Configuration Data Sheet CT 7 Low Alarm standard Rosemount alarm and saturation levels Pressu...

Page 146: ...ompleted model number 5 Not available with coned and threaded connection 2F code assemble to manifold S5 code assemble to seal S1 code surface finish certification Q16 code remote seal system report QZ code 6 Not available with FOUNDATION fieldbus output code F 7 Only Available with HART 4 20 mA output codes A and M 8 Transmitter is shipped with 316 SST conduit plug uninstalled in place of standar...

Page 147: ...Fluid Type Standard Standard L Liquid G Gas S Steam Line Size Standard Standard 020 2 in 50 mm 025 21 2 in 63 5 mm 030 3 in 80 mm 035 31 2 in 89 mm 040 4 in 100 mm 050 5 in 125 mm 060 6 in 150 mm 070 7 in 175 mm 080 8 in 200 mm 100 10 in 250 mm 120 12 in 300 mm Pipe I D Range Standard Standard C Range C from the Pipe I D table D Range D from the Pipe I D table This ordering table contains the foll...

Page 148: ...6 Stainless Steel Sensor Size Standard Standard 1 Sensor size 1 Line sizes 2 in 50 mm to 8 in 200 mm 2 Sensor size 2 Line sizes 6 in 150 mm to 96 in 2400 mm 3 Sensor size 3 Line sizes greater than 12 in 300 mm Mounting Type Standard Standard T1 Compression or Threaded Connection A1 150 RF ANSI A3 300 RF ANSI A6 600 RF ANSI D1 DN PN16 Flange D3 DN PN40 Flange D6 DN PN100 Flange Expanded R1 150 RTJ ...

Page 149: ...mbar 3 0 to 1000 in H2O 0 to 2 5 bar Transmitter Output Standard Standard A 2 4 20 mA with digital signal based on HART Protocol F FOUNDATION fieldbus Protocol W PROFIBUS PA Protocol Expanded M Low Power 1 5 Vdc with Digital Signal Based on HART Protocol Transmitter Housing Material Conduit Entry Size Standard Standard A Aluminum 1 2 14 NPT B Aluminum M20 x 1 5 J SST 1 2 14 NPT K 3 SST M20 x 1 5 E...

Page 150: ...d Standard J6 European Pressure Directive PED Expanded J1 Canadian Registration Instrument Connections for Remote Mount Options Standard Standard G2 Needle Valves Stainless Steel G6 OS Y Gate Valve Stainless Steel Expanded G1 Needle Valves Carbon Steel G3 Needle Valves Alloy C 276 G5 OS Y Gate Valve Carbon Steel G7 OS Y Gate Valve Alloy C 276 Special Shipment Standard Standard Y1 Mounting Hardware...

Page 151: ... ATEX Explosion proof Intrinsically Safe combination of E5 I5 E6 I6 E1 and I1 N1 3 ATEX Type n N7 3 IECEx Type n ND 3 ATEX Dust Sensor Fill Fluid and O ring Options Standard Standard L1 Inert Sensor Fill Fluid L2 Graphite Filled PTFE O ring LA Inert Sensor Fill Fluid and Graphite Filled PTFE O ring Display and Interface Options Standard Standard M4 8 LCD Display with Local Operator Interface M5 LC...

Page 152: ... Mount Options and Isolation Valves for Flo tap Models are not included in the Material Traceability Certification 6 Materials of Construction comply with metallurgical requirements within NACE MR0175 ISO for sour oil field production environments Environmental limits apply to certain materials Consult latest standard for details Selected materials also conform to NACE MR0103 for sour refining env...

Page 153: ...ogy Standard Standard C Conditioning Orifice Plate P Orifice Plate Material Type Standard Standard S 316 SST Line Size Standard Standard 005 1 1 2 in 15 mm 010 1 1 in 25 mm 015 1 11 2 in 40 mm 020 2 in 50 mm 030 3 in 80 mm 040 4 in 100 mm 060 6 in 150 mm 080 8 in 200 mm 100 10 in 250 mm 120 12 in 300 mm Primary Element Style Standard Standard N Square Edged Primary Element Type Standard Standard 0...

Page 154: ...e with selected model number Installation Accessories Standard Standard AB ANSI Alignment Ring 150 Only required for 10 in 250 mm and 12 in 300 mm line sizes AC ANSI Alignment Ring 300 Only required for 10 in 250 mm and 12 in 300 mm line sizes AD ANSI Alignment Ring 600 Only required for 10 in 250 mm and 12 in 300 mm line sizes DG DIN Alignment Ring PN16 DH DIN Alignment Ring PN40 DJ DIN Alignment...

Page 155: ...NSI ASME B31 1 J3 ANSI ASME B31 3 J4 ANSI ASME B31 8 Materials Conformance Expanded J5 7 NACE MR 0175 ISO 15156 Country Certification Expanded J1 Canadian Registration Product Certifications Standard Standard E1 3 ATEX Flameproof E2 INMETRO Flameproof E3 3 China Flameproof E4 3 TIIS Flameproof E5 FM Explosion proof Dust Ignition proof E6 CSA Explosion proof Dust Ignition proof Division 2 E7 IECEx ...

Page 156: ...l Operator Interface M5 LCD Display Transient Protection Standard Standard T1 9 Transient terminal block Manifold for Remote Mount Option Standard Standard F2 3 Valve Manifold Stainless Steel F6 5 Valve Manifold Stainless Steel Alarm Limit Standard Standard C4 10 11 NAMUR Alarm and Saturation Levels High Alarm CN 10 11 NAMUR Alarm and Saturation Levels Low Alarm CR 10 Custom Alarm and saturation s...

Page 157: ...eld production environments Environmental limits apply to certain materials Consult latest standard for details Selected materials also conform to NACE MR0103 for sour refining environments 8 Only valid with FOUNDATION fieldbus Output Code F 9 Not available with Housing code 00 5A or 7J The T1 option is not needed with FISCO Product Certifications transient protection is included with the FISCO Pr...

Page 158: ...on Standard Standard T1 NPT Female Body Not Available with Remote Thermowell and RTD S1 1 Socket Weld Body Not Available with Remote Thermowell and RTD P1 Pipe Ends NPT Threaded P2 Pipe ends Beveled D1 Pipe Ends Flanged DIN PN16 slip on D2 Pipe Ends Flanged DIN PN40 slip on D3 Pipe Ends Flanged DIN PN100 slip on W1 Pipe Ends Flanged RF ANSI Class 150 weld neck W3 Pipe Ends Flanged RF ANSI Class 30...

Page 159: ... 25 mm for 1 2 in Pipe 0014 0 014 in 0 36 mm for 1 2 in Pipe 0020 0 020 in 0 51 mm for 1 2 in Pipe 0034 0 034 in 0 86 mm for 1 2 in Pipe Transmitter Connection Platform Standard Standard D3 Direct mount 3 Valve Manifold SST D5 Direct mount 5 Valve Manifold SST R3 Remote mount 3 Valve Manifold SST R5 Remote mount 5 Valve Manifold SST Differential Pressure Ranges Standard Standard 1 0 to 25 in H2O 0...

Page 160: ...am Material Examination Expanded V2 Radiographic Examination Flow Calibration Expanded WD 6 Discharge Coefficient Verification Special Inspection Standard Standard QC1 Visual Dimensional Inspection with Certificate QC7 Inspection and Performance Certificate Material Traceability Certification Standard Standard Q8 Material Traceability Certification per EN 10204 2004 3 1 Code Conformance Expanded J...

Page 161: ...O Intrinsically Safe K1 3 ATEX Flameproof Intrinsic Safety Type n Dust K2 3 INMETRO Flameproof and Intrinsic Safety K5 FM Explosion proof Dust Ignition proof Intrinsically Safe Division 2 combination of E5 and I5 K6 CSA Explosion proof Dust Ignition proof Intrinsically Safe Division 2 combination of E6 and I6 K7 3 IECEx Flameproof Dust Ignition proof Intrinsic Safety Type n combination of E7 I7 an...

Page 162: ... Revision 7 factory configured add option code HR7 3 Not available with Low Power Output Code M 4 Thermowell Material is the same as the body material 5 Does not apply to Process Connection codes T1 and S1 6 Not available for bore sizes 0010 0014 0020 or 0034 7 Not available with DIN Process Connection codes D1 D2 or D3 8 Materials of Construction comply with metallurgical requirements within NACE...

Page 163: ...the following new option codes DA0 M4 QT DZ CR CS CT HR5 HR7 A FOUNDATION fieldbus F Profibus W Table 17 Rosemount 2051L Liquid Level Transmitter Ordering Information The Standard offering represents the most common options The starred options should be selected for best delivery __The Expanded offering is subject to additional delivery lead time Model Transmitter Type Standard Standard 2051L Liqu...

Page 164: ...ard Standard M 2 in ANSI ASME B16 5 Class 150 CS A 3 in ANSI ASME B16 5 Class 150 CS B 4 in ANSI ASME B16 5 Class 150 CS N 2 in ANSI ASME B16 5 Class 300 CS C 3 in ANSI ASME B16 5 Class 300 CS D 4 in ANSI ASME B16 5 Class 300 CS X 2 2 in ANSI ASME B16 5 Class 150 SST F 2 3 in ANSI ASME B16 5 Class 150 SST G 2 4 in ANSI ASME B16 5 Class 150 SST Y 2 Displayed ANSI ASME B16 5 Class 300 SST H 2 3 in A...

Page 165: ...nsor Module Diaphragm Material Sensor Fill Fluid Low Side Diaphragm Material Sensor Fill Fluid Standard Standard 1 2 316L SST Silicone 2 2 Alloy C 276 SST Valve Seat Silicone 7 2 Alloy C 276 Alloy C 276 Valve Seat Silicone A 2 316L SST Inert Halocarbon B 2 Alloy C 276 SST Valve Seat Inert Halocarbon G 2 Alloy C 276 Alloy C 276 Valve Seat Inert Halocarbon O ring Standard Standard A Glass filled PTF...

Page 166: ... Safety K5 FM Explosion proof Dust Ignition proof Intrinsically Safe Division 2 K6 CSA Explosion proof Dust Ignition proof Intrinsically Safe Division 2 K7 4 IECEx Flameproof Intrinsic Safety Type n and Dust KA 4 ATEX and CSA Flameproof Intrinsically Safe Division 2 KB FM and CSA Explosion proof Dust Ignition proof Intrinsically Safe Division 2 KC 4 FM and ATEX Explosion proof Intrinsically Safe D...

Page 167: ...nal levels low alarm requires C1 and Configuration Data Sheet CT 8 Low Alarm standard Rosemount alarm and saturation levels Calibration Certification Standard Standard Q4 Calibration Certificate QG Calibration Certificate and GOST Verification Certificate GP Calibration Certificate and tamper evident seal Material Traceability Certification Standard Standard Q8 Material Traceability Certification ...

Page 168: ...ires option code S1 4 Not available with Low Power output code M 5 Only valid with FOUNDATION fieldbus output code F 6 Assemble to items are specified separately and require a completed model number 7 Not valid with FOUNDATION fieldbus output code F 8 Only available with 4 20 mA HART output codes A and M 9 Not available with Remote Mount Seal Assembly option S1 10 Transmitter is shipped with 316 S...

Page 169: ... 0100 4107 Tagging 3 options available Standard SST hardware tag is wired to the transmitter Tag character height is 0 125 in 3 18 mm 56 characters maximum Tag may be permanently stamped on transmitter nameplate upon request 56 characters maximum Tag may be stored in transmitter memory Character limit is dependent on protocol HART Revision 5 8 characters HART Revision 7 32 characters Engineering u...

Page 170: ... messages for local troubleshooting and have 90 degree rotation capability for easy viewing M4 1 Digital Display with Local Operator Interface LOI Commission the device with internal and external Local Configuration Buttons 1 M5 Digital Display 2 Line 5 Digit LCD for 4 20 mA HART Configuration buttons Enhanced Rosemount 2051 requires option D4 Analog Zero and Span DZ Digital Zero or M4 LOI for loc...

Page 171: ...h the standard Coplanar flange configuration Bracket for mounting of transmitter on 2 in pipe or panel Stainless steel construction with stainless steel bolts Rosemount 2051C Traditional Flange bracket options B1 Bracket for 2 in Pipe Mounting For use with the traditional flange option Bracket for mounting on 2 in pipe Carbon steel construction with carbon steel bolts Coated with polyurethane pain...

Page 172: ...in stainless steel with Series 300 stainless steel bolts Shipping weights Table 18 Transmitter weights without options Table 19 Rosemount 2051L weights without options Transmitter Add weight In lb kg Rosemount 2051C 6 0 2 7 Rosemount 2051L Table 19 Rosemount 2051T 3 0 1 4 Flange Flush lb kg 2 in Ext lb kg 4 in Ext lb kg 6 in Ext lb kg 2 in 150 12 5 5 7 3 in 150 17 5 7 9 19 5 8 8 20 5 9 3 21 5 9 7 ...

Page 173: ... 1 25 0 6 B4 SST Mounting Bracket for Coplanar Flange 1 0 0 5 B1 B2 B3 Mounting Bracket for Traditional Flange 2 3 1 0 B7 B8 B9 Mounting Bracket for Traditional Flange 2 3 1 0 BA BC SST Bracket for Traditional Flange 2 3 1 0 H2 Traditional Flange 2 4 1 1 H3 Traditional Flange 2 7 1 2 H4 Traditional Flange 2 6 1 2 H7 Traditional Flange 2 5 1 1 FC Level Flange 3 in 150 10 8 4 9 FD Level Flange 3 in ...

Page 174: ...LOI 02021 0020 2139 Rosemount 2051 LCD LOI Display Part Number LCD Display Only LCD Display is only compatible with enhanced Rosemount 2051 electronics 4 20mA HART Aluminum 03031 0199 0012 4 20 mA HART 316 SST 03031 0199 0022 Terminal Block HART Part Number 4 20 mA HART Output Standard terminal block assembly 02051 9005 0001 Transient terminal block assembly option T1 02051 9005 0002 1 5 Vdc HART ...

Page 175: ...9010 0002 Zero and Span Kit for 4 20 mA HART NAMUR Compliant C4 CN option 5 Zero and Span Kit for Aluminum Housing 02051 9010 1001 Zero and Span Kit for SST Housing 02051 9010 1002 Zero and Span Kit for 1 5 Vdc HART Low Power 5 Zero and Span Kit for Aluminum Housing 02051 9010 1001 Zero and Span Kit for SST Housing 02051 9010 1002 O Ring Packages package of 12 Part Number Electronic housing cover ...

Page 176: ... class 300 SST 03031 0393 0222 3 in class 150 SST 03031 0393 0231 3 in class 300 SST 03031 0393 0232 DIN DN 50 PN 40 03031 0393 1002 DIN DN 80 PN 40 03031 0393 1012 Flange Adapter Part Number Nickel plated carbon steel 02024 0069 0005 316 SST 02024 0069 0002 Cast C 276 02024 0069 0003 Drain Vent Valve Kits each kit contains parts for one transmitter Part Number Differential Drain Vent Kits 316 SST...

Page 177: ...44 mm 1 75 in Set of 4 Carbon steel 03031 0312 0001 316 SST 03031 0312 0002 ASTM A 193 Grade B7M 03031 0312 0003 ASTM A 193 Class 2 Grade B8M 03031 0312 0005 Flange Adapter Bolt Kit 73 mm 2 88 in Set of 4 Carbon steel 03031 0306 0001 316 SST 03031 0306 0002 ASTM A 193 Grade B7M 03031 0306 0003 ASTM A 193 Class 2 Grade B8M 03031 0306 0005 Manifold Flange Kit 57 mm 2 25 in Set of 4 Carbon steel 0303...

Page 178: ...1 0292 0001 1 SST field terminal cover o ring 03031 0292 0002 1 Aluminum HART electronics cover cover o ring 03031 0292 0001 1 316 SST HART electronics cover cover o ring 03031 0292 0002 1 Aluminum Electronics LCD Display Cover Assembly cover o ring 03031 0193 0002 SST Electronics LCD Display Cover Assembly cover o ring 03031 0193 0012 Miscellaneous External ground screw assembly option V5 03031 0...

Page 179: ...ment LTDA Sorocaba Brazil Emerson Process Management India Pvt Ltd Daman India B 2 European Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www rosemount com A hard copy may be obtained by contacting an Emerson Process Management representative B 2 1 Ordinary Location Certification for Factory M...

Page 180: ...ns 1 Groups E F and G Class III Division 1 Class I Zone 0 AEx ia IIC Nonincendive for use in Class I Division 2 Groups A B C and D in accordance with Control Drawing 02051 1009 Enclosure Type 4X Temperature Code T4 Ta 50 C to 70 C Enclosure Type 4X For input parameters see control drawing 02051 1009 Special Conditions for Safe Use 1 The Model 2051 transmitter housing contains aluminum and is consi...

Page 181: ...l Enclosure Type 4X European Certifications I1 ATEX Intrinsic Safety Certificate No Baseefa08ATEX0129X Applicable Standards EN60079 0 2012 EN60079 11 2012 Markings II 1 G Ex ia IIC T4 Ga 60 C Ta 70 C IP66 IP68 1180 Special Conditions for Safe Use X When the optional transient protection terminal block is installed the apparatus is not capable of withstanding the 500 V insulation test required by C...

Page 182: ...n case of repair Contact Emerson Process Management for information on the dimensions of flameproof joints ND ATEX Dust Certification No Baseefa08ATEX0182X Applicable Standards EN60079 0 2012 EN 60079 31 2009 Markings II 1 D Ex t IIIC T50 C T500 60 C Da IP66 IP68 Ui 42 4 Vdc 1180 Special Conditions for Safe Use X If the equipment is fitted with an optional 90 V transient suppressor it is incapable...

Page 183: ...d in detail to assure safety during its expected lifetime 3 In case of repair Contact Emerson Process Management for information on the dimensions of flameproof joints N7 IECEx Type n Certification No IECExBAS08 0046X Applicable Standards IEC60079 0 2011 IEC60079 15 2010 Ex nA IIC T4 Gc 40 C Ta 70 C Ui 42 4 Vdc max Special Conditions for Safe Use X When the optional transient protection terminal b...

Page 184: ...insic Safety Ex ia IIC T4 EW Flame Proof Ex d IIC T5 Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified Once a device labeled with multiple approval types is installed it should not be reinstalled using any other approval types Permanently mark the approval label to distinguish it from unused approval types K1 E1 I1 N1 and ND combinatio...

Page 185: ...emperature Code T4 Ta 50 C to 60 C Enclosure Type 4X For input parameters see control drawing 02051 1009 Canadian Standards Association CSA All CSA hazardous approved transmitters are certified per ANSI ISA 12 27 01 2003 E6 Explosion Proof Dust Ignition Proof Certificate No 2041384 Applicable Standards CSA Std C22 2 No 142 M1987 CSA Std C22 2 No 30 M1986 CSA Std C22 2 No 213 M1987 CAN CSA E60079 0...

Page 186: ...Ga 60 C Ta 60 C IP66 IP68 1180 Special Conditions for Safe Use X When the optional transient protection terminal block is installed the apparatus is not capable of withstanding the 500 V insulation test required by Clause 6 3 12 of EN60079 11 This must be taken into account when installing the apparatus N1 ATEX Type n Certification No Baseefa08ATEX0130X Applicable Standards EN60079 0 2012 EN60079 ...

Page 187: ...ty during its expected lifetime 3 In case of repair Contact Emerson Process Management for information on the dimensions of flameproof joints ND ATEX Dust Certification No Baseefa08ATEX0182X Applicable Standards EN60079 0 2012 EN 60079 31 2009 Markings II 1 D Ex t IIIC T50 C T500 60 C Da IP66 IP68 Ui 42 4 Vdc 1180 Special Conditions for Safe Use X If the equipment is fitted with an optional 90 V t...

Page 188: ...cable glands and wiring needs to be suitable for a temperature of 90 C This device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime In case of repair Contact Emerson Pro...

Page 189: ... C T5 T6 T5 50 C Ta 80 C T6 50 C Ta 65 C I3 Intrinsic Safety NEPSI Certificate No GYJ101320X Applicable Standards GB3836 1 2000 GB3836 4 2000 Markings Ex ia IIC T4 T4 60 C Ta 70 C Inmetro Certifications E2 Flameproof Certificate No CEPEL 09 1767X Ex d IIC T Ga Gb IP66 T6 50 C Tamb 65 C T5 50 C Tamb 80 C I2 Intrinsic Safety Certificate No CEPEL 09 1768X Ex ia IIC T4 Ga IP66 IB FISCO Intrinsic Safet...

Page 190: ... with multiple approval types is installed it should not be reinstalled using any other approval types Permanently mark the approval label to distinguish it from unused approval types K1 E1 I1 N1 and ND combination K2 E2 and I2 combination K5 E5 and I5 combination K6 E6 and I6 combination K7 E7 I7 and N7 combination KA E1 I1 E6 and I6 combination KB E5 I5 E6 and I6 combination KC E1 I1 E5 and I5 c...

Page 191: ...anual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications B 5 Approval drawings B 5 1 Factory mutual 02051 1009 ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 192: ...182 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 193: ...183 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 194: ...184 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 195: ...185 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 196: ...186 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 197: ...187 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 198: ...188 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 199: ...189 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 200: ...190 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 201: ...191 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 202: ...192 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 203: ...193 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 204: ...Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications B 5 2 Canadian standards association CSA 02051 1008 ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 205: ...195 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 206: ...196 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 207: ...197 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 208: ...198 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 209: ...199 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 210: ...200 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 211: ...201 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 212: ...202 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ElectronicMaster PRINTEDCOPIESAREUNCONTROLLED RosemountProprietary ...

Page 213: ...203 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ...

Page 214: ...204 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ...

Page 215: ...ent Material Comm Status Polled 1 Communication Change HART Lock 1 Device Lock LOI Password Protection 1 Password Protection Remote Seal Info 1 Num of Remote Seals 2 Seal Type 3 Fill Fluid 4 Diaphragm Material Alarm Levels 1 Alarm Direction 2 High Alarm 3 High Saturation 4 Low Saturation 5 Low Alarm Active Alerts 1 Refresh Alerts 2 Active Alert 1 3 Active Alert 2 4 Etc Sensor Module Info 1 Serial ...

Page 216: ... Units of Measure Damping 3 Variable Mapping 4 Analog Output 5 Alarm Saturation Values Device Tagging 1 Tag 2 Long Tag 3 Description 4 Message 5 Date Guided Setup 1 Basic Setup 2 Zero Trim 3 Configure Display 4 Scaled Variable 5 Configure Burst Mode Configure Display 1 Pressure 2 Scaled Variable 3 Sensor Temperature 4 Percent of Range 5 Analog Output 6 Review Parameters at Start up Variable Mappin...

Page 217: ...tion 1 Tag 2 Long Tag 3 Model 3 Serial Number 4 Date 5 Description 6 Message 7 Model Numbers 8 Manufacturer LOI Password 1 Password Protection 2 Configure Password HART Lock 1 Lock Status 2 Lock Unlock Variable Mapping 1 Primary Variable 2 Second Variable 3 Third Variable 4 Fourth Variable Communication Settings 1 Polling Address 2 Change Polling Address 3 Universal Revision 4 Change HART Revision...

Page 218: ...sion 5 DD Home 1 Overview 2 Configure 3 Service Tools Configure 1 Guided Setup 2 Manual Setup 3 Alert Setup Alert Setup 1 Pressure Alert 2 Temperature Alert 3 Alarm Saturation Levels Alarm Saturation Levels 1 Alarm Direction 2 High Alarm 3 High Saturation 4 Low Saturation 5 Low Alarm 6 Config Alarm Sat Levels Temperature Alert 1 Configure Alert 2 Alert Mode 3 High Alert Value 4 Low Alert Value 5 T...

Page 219: ...bration 4 Security 5 Locate Device 6 Device Reset Pressure Calibration 1 Upper Sensor Trim 2 Lower Sensor Trim 3 Zero Trim 4 Damping 5 AO Transfer Function 6 Last Calibration Points 7 Sensor Limits AO Transfer Function 1 Upper Calibration Points 2 Lower Calibration Points LOI Password Protection 1 Password Protection 2 Configure Password HART Lock 1 Device Lock 2 Lock Unlock Sensor Limits 1 PV Upp...

Page 220: ... 2 5 1 1 Range Values 2 2 2 1 2 2 2 1 Tag 2 2 7 1 1 2 2 7 1 1 Transfer Function 2 2 1 1 6 2 2 1 1 6 Pressure Units 2 2 1 1 4 2 2 1 1 4 Date 2 2 7 1 5 2 2 7 1 4 Descriptor 2 2 7 1 6 2 2 7 1 5 Digital to Analog Trim 4 20 mA 1 5 V Output 3 4 2 1 3 4 2 1 Digital Zero Trim 3 4 1 3 3 4 1 3 Display Configuration 2 2 4 2 2 4 LOI Password Protection 2 2 6 5 2 2 6 4 Loop Test 3 5 1 3 5 1 Lower Sensor Trim 3...

Page 221: ...ENU EXIT MENU LOOP TEST SET 4MA SET 20MA SET CUSTOM END LOOP TEST BACK TO MENU EXIT MENU DISPLAY PRESS on off SCALED on off TEMP on off RANGE on off STARTUP on off BACK TO MENU EXIT MENU EXTENDED MENU CALIBRAT DAMPING TRANSFER FUNCT SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMULATE HART REV BACK TO MENU EXIT MENU VIEW CONFIG TAG PV PRESS UNITS TEMP UNITS URV LRV TRANSFER FUNCTION DAMP...

Page 222: ...ECALL BACK TO MENU EXIT MENU TRANSFER FUNCT LINEAR TRANSFER FUNCTION SQR ROOT TRANSFER FUNCTION BACK TO MENU EXIT MENU SCALED VARIAB VIEW SCALED CONFIG SCALED BACK TO MENU EXIT MENU ASSIGN PV PRESSURE SET PV SCALED SET PV BACK TO MENU EXIT MENU ALARM SAT VALUES ROSEMOUNT VALUES NAMUR VALUES OTHER VALUES BACK TO MENU EXIT MENU PASSWORD ENABLE PASSWORD CHANGE PASSWORD BACK TO MENU EXIT MENU SIMULATE...

Page 223: ...o select 0 for the third digit The fourth digit from the left will now be blinking 00000022 6 Press the enter button to select 0 for the fourth digit The fifth digit from the left will now be blinking 00000022 7 Press scroll to navigate through the numbers until the 1 is on the screen 00001022 8 Press the enter button to select the 1 for the fifth digit The sixth digit from the left will now be bl...

Page 224: ...umbers can be entered in scientific notation by placing an E in the 7th position D 4 Text entry 1 Text can be entered with the LOI Depending on the edited item up to eight locations on the top line can be used for text entry Text entry follows the same rules as the number entry rules in LOI Menu Tree on page 211 except the following characters are available in all locations A Z 0 9 space Usage not...

Page 225: ...gital to analog trim 75 Other scale 76 Disassembly Before disassembling 87 Remove electronics board 88 Remove from service 87 Sensor module 88 Disassembly procedures 87 Drawings Approval 181 Canadian Standards Association 194 Factory Mutual 181 E Electronics board 55 F Features 6 Foundation fieldbus 2 Full trim 72 H Hazardous Locations 49 Housing Remove 88 I Impulse piping 42 Installation 36 Bolts...

Page 226: ...nsor body 90 Recall factory trim Analog output 77 Sensor trim 73 Rerange HART Communicator only 16 Pressure input source With HART Communicator 17 With local zero and span 18 Returning products and materials 91 S Sensor Module Installing 89 Removing 88 Sensor trim 72 Service Support 5 Spare parts list 164 Support 5 T Terminal block Installing 90 Terminal Side 36 Trim Analog output 71 Digital to An...

Page 227: ......

Page 228: ...l Inc HART is a registered trademark of the HART Communication Foundation FOUNDATION fieldbus is a registered trademark of the Fieldbus Foundation All other marks are the property of their respective owners April 2013 Rosemount Inc All rights reserved Emerson Process Management GmbH Co Argelsrieder Feld 3 82234 Wessling Germany Tel 49 8153 9390 Fax 49 8153 939172 Emerson Process Management Asia Pa...