minimize the number of weld passes. These best practices will decrease heat input
and help mitigate distortion.
3. Position the weld spud in the vessel hole, place heat sink and tack the housing in
place using the welding sequence shown in
wet cloth before proceeding to the next section.
WARNING
Do not place the seal in the lower housing prior to welding. Do not nick the inner
angled sealing surfaces of the weld spud where the gasket sits, shown in
, as any irregularities may cause leaks.
4. Weld the housing in place using 0.030- to 0.045-in. (0,762 to 1,143 mm) stainless
steel rod as filler in the beveled area. Using between 100 and 125 A, adjust the
amperage for 0.080-in. (2,032 mm) penetration. Allow time to cool between weld
sections. Weld should be cooled to 350 °F (177 °C) or less after each pass while
being cool to the touch is preferred. Use of a damp cloth or compressed air is
allowed if rapid cooling is desired. Repeat procedure on the outside of the tank.
Note
The number of weld passes should be kept to a minimum while maintaining tank
weld standards and process requirements. Additional weld passes are a significant
contributor to spud distortion due to additional heat input and added filler material
in beveled area of hole.
Figure 3-34: Installing the Weld Spud
Preparing the vessel hole
Welding sequence
C
D
E
A
B
1.32
(34)
1
3
5
7
2
4
6
8
A. 100 to 125 A recommended
B. Heat isolation grooves
C. Weld spud
D. Bevelled edge
E. Process vessel
Dimensions are in inches (millimeters).
CAUTION
Excessive heat will distort the weld spud. Allow adequate cooling time between
passes.
Installation
Reference Manual
May 2020
00809-0100-4002
68
Rosemount DP Level
Summary of Contents for Rosemount 1199
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual May 2020 00809 0100 4002 8 Rosemount DP Level ...
Page 22: ...Remote Seal Systems Reference Manual May 2020 00809 0100 4002 22 Rosemount DP Level ...
Page 74: ...Installation Reference Manual May 2020 00809 0100 4002 74 Rosemount DP Level ...
Page 92: ...Fill Fluids Reference Manual May 2020 00809 0100 4002 92 Rosemount DP Level ...