Quick Installation Guide

00825-0100-4593, Rev BA
July 2009

Rosemount 1151

13

S

TEP

 6: T

RIM

 

THE

 T

RANSMITTER

NOTE

Transmitters are shipped fully calibrated per request or by the factory default of full scale 
(span = upper range limit).

Full Trim

A full trim is a two-point sensor calibration where two end-point pressures are applied, and 
the transmitter process variable output is adjusted to agree with the pressure input.

Using the HART Communicator

Zero Trim 

A zero trim is a single-point adjustment used for compensating mounting position effects. 
When performing a zero trim, ensure that the equalizing valve is open and all wet legs are 
filled to the correct level. If zero offset is less than 3% of true zero, follow the “Using the 
HART Communicator” instructions below. If zero offset is greater than 3% of true zero, follow 
the “Using the Transmitter Zero Adjustment Buttons” instructions.

Using the HART Communicator

HART Fast Keys

Steps

1, 2, 3, 3

1. Equalize or vent the transmitter and connect HART 

communicator.

2. At the menu, input the HART Fast Key sequence.
3. Follow the commands to perform a full trim.

HART Fast Keys

Steps

1, 2, 3, 3, 1

1. Equalize or vent the transmitter and connect HART 

communicator.

2. At the menu, input the HART Fast Key sequence.
3. Follow the commands to perform a zero trim.

4593_Rev_BA.fm  Page 13  Friday, August 7, 2009  3:38 PM

Summary of Contents for Rosemount 1151

Page 1: ...51 Step 1 Mount the Transmitter Step 2 Consider Housing Rotation Step 3 Connect the Wiring and Power Up Step 4 Set Switches Step 5 Configuration Step 6 Trim the Transmitter Product Certifications Start End Rosemount 1151 Pressure Transmitter with 4 20 mA HART Protocol P r o d u c t D i s c o n t i n u e d ...

Page 2: ... Proof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death To avoid process leaks only use the o ring designed to seal with the corresponding flange adapter Electrical shock can result in death or serious injury Avoid contact with the leads and the terminals High voltage that may be present on leads can cause electrica...

Page 3: ...Flow Applications 1 Place taps to the side of the line 2 Mount beside or below the taps Gas Flow Applications 1 Place taps in the top or side of the line 2 Mount beside or above the taps Steam Flow Applications 1 Place taps to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water Flow Flow Flow ...

Page 4: ...09 Rosemount 1151 4 STEP 1 CONTINUED B Optional Mounting Brackets When installing the transmitter to one of the optional mounting brackets torque the bracket bolts to 125 in lbs 0 9 N m Pipe Mount Panel Mount 1 1 Panel bolts are customer supplied Flat Mount ...

Page 5: ...orque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o ring Failure to install proper flange adapter O rings may cause process leaks which can result in death or serious injury The two flange adapters are distinguished by unique O ring grooves Only use the O ring that is designed for its specific flange adapter as shown below Rosemount 3051S 3051 205...

Page 6: ...using lock nut 4 If the desired position cannot be reached because the housing will not rotate further rotate the housing counterclockwise until in the desired position up to 90 from its original position 5 Tighten the housing lock nut to 420 in lb Use a sealing compound Loctite 222 Small Screw Threadlocker on the threads to ensure a watertight seal on the housing NOTE If the desired position cann...

Page 7: ...sulated from touching the transmitter housing be connected to the next shield if cable is routed through a junction box be connected to a good earth ground at the power supply end NOTE Do not connect the powered signal wiring to the test terminals Power could damage the test diode in the test connection Twisted pair cable should be used for best results In high EMI RFI environments use either tran...

Page 8: ... load is the sum of the resistance of the signal leads and the load resistance of the controller indicator and related pieces Note that the resistance of intrinsic safety barriers if used must be included Figure 2 Load Limitation Code Vmin Vmax Rmin Rmax RL at Supply Voltage VS S 1 1 A minimum of 250 is required for communication 12 45 0 1650 RL 43 5 VS 12 Rmax RL Rmin Vmin VS Vmax Operating Regio...

Page 9: ...ward HI To set the failure mode to low alarm position the switch to LO 4 Replace the housing cover Write Protect Switch In the ON position the write protect switch prevents changes to the configuration data 1 Remove the housing cover 2 Move the write protect switch to the OFF 3 Verify transmitter configuration see Verify Transmitter Configuration 4 Move the write protect switch to the ON 5 Replace...

Page 10: ... 1 Descriptor 1 3 4 2 Digital to Analog Trim 4 20 mA Output 1 2 3 2 1 Field Device Information 1 4 4 1 Full Trim 1 2 3 3 Keypad Input 1 2 3 1 1 Loop Test 1 2 2 Lower Range Value 4 1 Lower Sensor Trim 1 2 3 3 2 Message 1 3 4 3 Meter Type 1 3 4 5 Number of Requested Preambles 1 4 3 4 2 Percent Range 1 1 2 Poll Address 1 4 3 4 1 Pressure 2 Range Values 1 3 3 Rerange 1 2 3 1 Scaled D A Trim 4 20 mA Ou...

Page 11: ...e the LCD Display cover Table 2 LCD Display Modes NOTE The meter displays for approximately 7 5 seconds while the information is being stored Options Relationship between Input Signal and Digital Display L in Linear L in F Linear with five second filter Srt Square root SrtF Square root with five second filter Square root function relates to the digital display The bar graph output remains linear w...

Page 12: ...s both configuration buttons simultaneously for two seconds 5 Replace the LCD display cover Set the Display Equivalent to a 20 mA Signal 1 Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover 2 Press the right button for two seconds 3 To decrement the display numbers press the left configuration button on the display and to increment the numbers press the right configurati...

Page 13: ...ts When performing a zero trim ensure that the equalizing valve is open and all wet legs are filled to the correct level If zero offset is less than 3 of true zero follow the Using the HART Communicator instructions below If zero offset is greater than 3 of true zero follow the Using the Transmitter Zero Adjustment Buttons instructions Using the HART Communicator HART Fast Keys Steps 1 2 3 3 1 Equ...

Page 14: ...the controls 3 Press the zero button for five seconds to set the 4 mA point Verify that the output is 4 mA 4 Apply a pressure equivalent to the higher calibrated value to the high side of the transmitter 5 Press the span button for five seconds to set the 20 mA point Verify that the output is 20 mA 4 20 mA Output Trim A 4 20 mA output trim adjusts the transmitter milliampere output to match plant ...

Page 15: ...r 1151 Pressure Transmitters Sound Engineering Practice Transmitter Attachments Diaphragm Seal Process Flange Manifold Sound Engineering Practice Electro Magnetic Compatibility EMC 2004 108 EC All models EN 61326 1 2006 EN61326 2 3 2006 Hazardous Locations Certifications North American Certifications Factory Mutual FM Approvals FM Explosion Proof tag is standard Appropriate tag will be substituted...

Page 16: ...ada Approvals C5 Accuracy Approval to the Electricity and Gas Inspection Act for the purchase and sale of natural gas European Certifications E8 ATEX Flameproof Certification Number CESI03ATEX037 ATEX Marking II 1 2 G EEx d IIC T6 40 C Tamb 40 C EEx d IIC T4 40 C Tamb 80 C 1180 V 60 Vdc maximum I1 ATEX Intrinsic Safety and Combustible Dust Certification Certification Number BAS99ATEX1294X ATEX Mar...

Page 17: ...ansmitters having NPT PG or G cable entry threads an appropriate flameproof thread adaptor shall be used to facilitate application of certified flameproof cable glands or conduit system I7 Intrinsic Safety Certificate Number Aus Ex 122X Ex ia I IIB T4 Ta 60 C T5 IP66 Special Conditions for Safe Use x 1 It is a condition of safe use that the following parameters shall be taken into account during i...

Page 18: ...metallic housing shall be bonded to the system earth Combination Certifications Stainless steel certification tag is provided when optional approval is specified Once a device labeled with multiple approval types is installed it should not be reinstalled using any other approval types Permanently mark the approval label to distinguish it from unused approval types C6 Combination of I6 and E6 CSA E...

Page 19: ...Quick Installation Guide 00825 0100 4593 Rev BA July 2009 Rosemount 1151 19 DoC ...