52 • RLDS I&O Manual
026-1309 Rev 8
11 Main Screens
11.1. Home Screen (F1
Screen)
Press
F1
at any point to save changes and display the
Home screen:
The HHT is used to display the following on the
Home screen:
•
RLDS GW-810-3760
: Model information
•
1.10B04
: Version number
•
FAIL: I/O NET
: Displays the operation mode
on the third line of the HHT screen. This
indicates which type of area controller the
RLDS Gateway is attached to. The dip switch 8
is set to ON or OFF.
ON = REFLECS, OFF = E2, Einstein. If a
failure condition exists with the RLDS
Gateway, this line shows one of the following
failure messages:
FAIL: I/O NET
indicates that no communication
with the I/O Net exists, and that communication
between the controllers is down.
FAIL: FLASH/CLK
indicates the hardware is bad
and the Gateway should be replaced.
FAIL: USER CFG
indicates that no RLDS units
have been found on the network, and have not been
configured by the user.
FAIL: RLDS CTRL
indicates that one or more
RLDS controllers are down.
•
PRESS DOWN ARROW
indicates what to do
next.
11.2. RLDS Enable Screen
The second screen will show whether a particular unit
is enabled, disabled, or unknown. When the RLDS
Gateway first powers up it will show
UNKOWN
for all units. It will then start scanning for
each unit. If it finds a unit, it marks it as
ENABLED
.
If an RLDS is not present on the network, the user can
mark that RLDS as
DISABLED
to prevent the Gate-
way from scanning for that unit. When the unit is dis-
abled, the Gateway stops trying to access the RLDS
controller and does not respond to the
association request on the I/O Network.
Press the down arrow to go to the next screen:
11.3. SELECT RLDS Screen (F2
Screen)
Press
F2
at any point to save changes and display the
SELECT RLDS screen:
The F2 screen allows you to select the desired RLDS.
The F2 screen shows the general
ONLINE
or
OF-
FLINE
status for the enabled RLDS controllers.
ON-
LINE
means the Gateway is successfully
communicating with an enabled RLDS controller. If it
is unknown whether an RLDS is present on the
network, the screen will display
UNKNOWN
.
RLDS GW-810-3760
VER: 1.10B04
FAIL: I/O NET
(PRESS DOWN ARROW)
NOTE: Pressing the down arrow scrolls you to
the next screen.
RLDS LIST:
RLDS1: ENABLED
RLDS2: DISABLED
RLDS3: DISABLED
SELECT RLDS: 1
LDS1: ONLINE
RLDS2: DISABLED
RLDS3: DISABLED
NOTE: SELECT RLDS: 1 defaults to 1.
Summary of Contents for RLDS
Page 1: ...Refrigerant Leak Detection System RLDS Installation and Operation Manual 026 1309 Rev 8 ...
Page 2: ......
Page 4: ......
Page 49: ...Service Mode General Operation of RLDS UI 43 RLDS Setup Screens System Map ...
Page 76: ......
Page 81: ......