MODEL MGS-314L SERIES LEVEL CONTROL SWITCH

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Use suitably certified safety

barriers for Ex iα IIC

MODEL

MGS-314-A

MGS-314L-A

or ½ MGS-314D-A

MAG. SWITCH

NO or NC

TB1

COM

Vmax = 40Vdc

Imax = 150mA

C

i

 = 0nF

L

i

 = 0mH

Use suitably certified safety

barriers for Ex iα IIC

TWO-WIRE ENTITY CONTROL DRAWING

THREE-WIRE ENTITY CONTROL DRAWING

Hazardous area

Hazardous area

Non-hazardous area

Non-hazardous area

OR

INTRINSIC 

SAFETY 

BARRIER

INTRINSIC 

SAFETY 

BARRIER

MULTIPLE 

CHANNEL

User wiring

Cleads

Lleads

Cleads

Lleads

Case 

ground

blue

red

black

green

Unused NO or NC lead shall be blind terminated and insulated.

The intrinsic safety barrier parameters must meet the following 

requirements:

Voc < 40V or Isc < 150mA; Ca > Cleads; La > Lleads

One multiple channel intrinsic safety barrier must be used.

The barrier parameters must meet the following requirements:

Vt < 40V or It < 150mA; Ca > Cleads; La > Lleads

Installation shall confirm to the manufacturer's instructions supplied 

with the intrinsic safety barrier as well as the National Electric Code 

and ANSI/ISA-RP 12.6 or CSA C22 "Installation of intrinsically safe 

instrument systems in hazardous (classified) locations."

Maximum non-hazardous area voltage must not exceed 250 Vrms or Vdc.

For I.S. installation, temperature shall not exceed 225°F (107°C).

FIGURE 5
Control drawing ATEX/IECEx certified intrinsically safe for MGS-314L (7E742-010)

R < 1Ω

R < 1Ω

MODEL

MGS-314-A

MGS-314L-A

or ½ MGS-314D-A

MAG. SWITCH

NO

TB1

   NC 
COM

Vmax = 40Vdc

Imax = 150mA

C

i

 = 0nF

L

i

 = 0mH

User wiring

MGS-314D-A Connections

white

blue

black
green

violet

orange

Case 

ground

red

NO

1

NO

2

NC

1

NC

2

C

1

C

2

MGS-314-A and MGS-314L-A Connections

Summary of Contents for PENBERTHY MGS-314L Series

Page 1: ...epairing or replacing the product at its expense Emerson shall not be liable for loss damage or expenses directly or indirectly related to the installation or use of its products or from any other cause or for consequential damages It is expressly understood that Emerson is not responsible for damage or injury caused to other products building property or persons by reason of the installation or u...

Page 2: ...rawing 7E742 008 Figure 3 MGS 314L A ATEX and IECEx approved by CSA Flame proof for Ex db IIB T5 Gb 1 A Max or 150Vdc Max Must use suitably certified minimum Ex db IIB conduit seal When installed in accordance with control drawing 7E741 010 Figure 4 MGS 314L A ATEX and IECEx approved by CSA Intrinsically safe for Ex ia IIC T5 Ga When installed in accordance with control drawing 7E742 010 Figure 5 ...

Page 3: ...he indication range This will insure sufficient float movement to operate the switch 7 If more than one switch is used on a single magnetic gauge the minimum recommended distance between mounting bands is 2 inches 51 mm 8 Adjust the position of the indicating scale so that the distance from the tip of the scale to the top of the communicating chamber is the same as in step 1 Tighten the clamps hol...

Page 4: ... occur Sound maintenance practices require periodic inspection of the instrument to ensure it is in good working order SAFETY INSTRUCTIONS Do not apply power to the switch while performing these tests 6 2 Switch test With the switch at position A use an ohmmeter to verify the conditions in Section 5 1 Using a magnet move the switch to position B If the switch still doesn t change state it is defec...

Page 5: ...IV I GROUP B C D CONTROL DRAWING Hazardous area Non hazardous area A flame path seal off shall be installed within 18 in of enclosure Wiring to be in accordance with National Electrical Code NEC Pertinent parts of the 500 Series of Article 5 or local codes as applicable FIGURE 2 Control drawing CSA approved explosion proof for MGS 314L 7E741 008 18 ...

Page 6: ...sc 150mA Ca Cleads La Lleads THREE WIRE ENTITY CONTROL DRAWING Non hazardous area Hazardous area User wiring INTRINSIC SAFETY BARRIER MULTIPLE CHANNEL Cleads Lleads Use CSA certified safety barriers rated for Class I DIV 1 Group A B C D One multiple channel intrinsic safety barrier must be used The barrier parameters must meet the following requirements Vt 40V or It 150mA Ca Cleads La Lleads MODEL...

Page 7: ...us area A flame path seal off shall be installed directly to threaded entry of enclosure Wiring to be in accordance with National Electrical Code NEC Pertinent parts of the 500 Series of Article 5 or local codes as applicable FIGURE 4 Control drawing ATEX IECEx certified explosion proof for MGS 314L 7E741 010 MGS 314 A MGS 314D A MGS 314L A EX D IIB ...

Page 8: ...oc 40V or Isc 150mA Ca Cleads La Lleads One multiple channel intrinsic safety barrier must be used The barrier parameters must meet the following requirements Vt 40V or It 150mA Ca Cleads La Lleads Installation shall confirm to the manufacturer s instructions supplied with the intrinsic safety barrier as well as the National Electric Code and ANSI ISA RP 12 6 or CSA C22 Installation of intrinsical...

Page 9: ...rson logo are trademarks and service marks of Emerson Electric Co All other marks are the property of their respective owners The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or th...

Reviews: