34
PACMotion VFD AC Variable Speed Drive User Guide
GFK-3111A
EMC Compliant Installation
Figure 26: Recommended Installation for EMC Compliance
Control cables
Twisted-Pair shielded
cables for analog
control and motor
feedback signals.
Cable shield exposed
and 360° clamped to
grounded metal plate or PE
bar. All other 360° bonding
methods are acceptable.
Motor cable
3-phase and PE shielded cable.
Maintain shield as far as
possible along the cable
Control cables
Mains - supply
Mounting plate
with conductive
service
≥ 100mm
Fuse /
MCB
L1
L2
L3
L1
L2
L3
PE
U V W PE
For Best-Practice
use 360° bonding
EMC cable gland
shielded to
motor chassis.
Table 20: Recommended Cable Types by EMC Category
Number of
Input Phases
Rated Supply
Voltage
Frame Size
IP rating
Maximum Motor Cable Length to Achieve
C1
1, 2, 5, 6, 8
C2
3, 5, 6, 8
C3
4, 7, 8
1
230
2
IP20, IP66
1 (5)
5 (25)
25 (100)
3
230
2, 3
IP20, IP66
1 (5)
5 (25)
25 (100)
4, 5
IP20, IP55
1 (5)
5 (25)
25 (100)
4,5
IP55
-
-
25 (100)
6A, 6B
IP20
-
100
100
6, 7
IP55
-
-
25 (100)
3
400
2, 3
IP20, IP66
1 (5)
5 (25)
25 (100)
4, 5
IP20, IP55
1 (5)
5 (25)
25 (100)
4,5
IP55
-
-
25 (100)
6A, 6B
IP20
-
100
100
6, 7
IP55
-
-
25 (100)
8
IP20
-
-
25
NOTE
• Data in brackets shows permissible cable length with additional external EMC filter.
• The 500 – 600 V drives are not equipped with the internal EMC filter and are intended for use on second
environment only.