background image

2

WARNING: 

To avoid fire, shock, and serious personal injury, follow these

instructions.

Safety Instructions

1. Read your owner’s manual carefully and keep it for future reference.
2. Before servicing or cleaning unit, switch power off at service panel and lock

service panel disconnecting means to prevent power from being switched on
accidentally. When the service disconnecting means cannot be locked,
securely fasten a warning device, such as a tag, to the service panel.

3. Be careful of the fan and blades when cleaning, painting, or working near the

fan. Always turn off the power to the ceiling fan before servicing.

4. Do not put anything into the fan blades while they are turning.
5. Do not operate reversing switch until fan blades have come to a complete stop.

Additional Safety Instructions for Installation

1. To avoid possible shock, be sure electricity is turned off at the fuse box before

wiring, and do not operate fan without blades.

2. The installation is to be in accordance with the National Electrical Code,

ANSI/NFPA 70-1999 and Local Codes. Use the National Electrical Code if Local
Codes do not exist. The ceiling fan must be grounded as a precaution against
possible electrical shock. Electrical installation should be made or approved
by a licensed electrician.

3. The outlet box and joist must be securely mounted and capable of reliably

supporting at least 50 pounds. Use only U.L. outlet boxes listed as
“Acceptable for Fan Support”, and use the mounting screws provided with the
outlet box. Most outlet boxes commonly used for support of light fixtures are
not acceptable for fan support and may need to be replaced. Consult a
qualified electrician if in doubt.

4. The downrod furnished with the fan provides the minimum recommended floor

to fan blade clearance for a 9 foot ceiling. This fan should NOT be mounted on
an 8 foot ceiling.

5. The fan must be mounted with the fan blades at least 7 feet from the floor to

prevent accidental contact with the fan blades.

6. Follow the recommended instructions for the proper method of wiring your

ceiling fan. If you do not know enough about electrical wiring, have your fan
installed by a licensed electrician.

WARNING: 

To reduce the risk of fire or electric shock, this fan should only be

used with fan speed control Model No. UC7067RC, manufactured by Rhine
Electric Co., Ltd.

NOTE:

This fan is suitable for use with solid-state speed controls.

WARNING:

This product is designed to use only those parts supplied with this

product and/or any accessories designated specifically for use with this product
by Emerson Electric Co. Substitution of parts or accessories not designated for
use with this product by Emerson Electric Co. could result in personal injury or
property damage.

WARNING: 

To reduce the risk of personal injury, do not bend the blade flange

when installing the blade flanges, balancing the blades or cleaning the fan. Do not
insert foreign objects in between rotating fan blades.

WARNING: 

To reduce the risk of electrical shock, this fan must be installed with

an isolating wall control/switch.

!

WARNING

DATE CODE:
The date code of this fan may be found on the box, stamped in ink on a white label.
You should record this data above and keep it in a safe place for future use.

BP7306 Nottingham  6/19/06  1:00 PM  Page 2

Summary of Contents for NOTTINGHAM CF4600GLZ00

Page 1: ...horized service center Your Emerson Air Comfort Ceiling Fan should be properly packed to avoid damage in transit since we will not be responsible for any such damage What Is Not Covered The glass globes and light bulbs of your ceiling fan are not covered by this warranty This warranty also does not cover any defects malfunctions or failures caused by Repairs by persons not authorized by Emerson El...

Page 2: ...r support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified electrician if in doubt 4 The downrod furnished with the fan provides the minimum recommended floor to fan blade clearance for a 9 foot ceiling This fan should NOT be mounted on an 8 foot ceiling 5 The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accid...

Page 3: ...ize A W G Up to 50 ft 14 50 100 ft 12 Before assembling your ceiling fan refer to section on proper method of wiring your fan page 10 If you feel you do not have enough wiring knowledge or experience have your fan installed by a licensed electrician WARNING Unpacking Instructions For your convenience check off boxes are provided next to each step As each step is completed place a check mark in the...

Page 4: ...an to outlet box marked Acceptable for Fan Support and use screws supplied with outlet box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified electrician if in doubt WARNING If your fan is to replace an existing ceiling light fixture turn electricity off at the main fuse or circuit breaker box at this tim...

Page 5: ...must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock WARNING IMPORTANT Before assembling your ceiling fan refer to sections Setting Operating Frequency of Wall Control and Receiver and Installation of Wall Control page 13 These sections instruct you how to a Set the operating frequency of the fan light w...

Page 6: ...ng the screws be sure there are no wires pinched between the switch cup adapter and switch cup assembly 6 5 32 x 9 16 PAN HEAD SCREWS 2 MOUNTING HUB BLADE FLANGE Figure 2 SWITCH CUP ASSEMBLY CONNECTORS REMOVE AND RETAIN FOUR PAN HEAD SCREWS SWITCH CUP ADAPTER Figure 3 SWITCH CUP ASSEMBLY REINSTALL FOUR PAN HEAD SCREWS Figure 4 6 Carefully place the partially assembled ceiling fan on the lower styr...

Page 7: ... to make sure the clevis pin is properly installed WARNING It is critical that the clevis pin in the motor coupling is properly installed and the setscrew securely tightened Failure to verify that the pin and setscrew are properly installed as shown in Figure 6 could result in the fan falling 10 Install the 5 16 18 x 1 4 setscrew supplied in the motor coupling Figure 6 While pulling up on the down...

Page 8: ...n the lower housing flange Figure 9 After the glass is properly seated tighten the setscrew in the upper housing CAUTION Be sure there are no wires pinched between the glass and the lower housing flange 8 DOWNROD SETSCREW UPPER HOUSING GLASS LOWER HOUSING FLANGE Figure 9 LOCKWASHER 2 KNURLED KNOB 2 COUPLING COVER 7 WATT MAXIMUM CANDELABRA BULB 6 MOTOR COUPLING SOCKET 1 THREADED STUD 2 Figure 7 UPP...

Page 9: ...with hanging and wiring your fan How to Hang Your Ceiling Fan The fan must be hung with at least 7 of clearance from floor to blades Figure 11 Do NOT hang this fan on an 8 ceiling a 9 ceiling is required to maintain the 7 clearance WARNING CEILING AT LEAST 7 FLOOR 19 Reinstall the hanger ball on the downrod Figure 10 as follows Route the motor leads through the hanger ball and slide the hanger bal...

Page 10: ...ng fan must be properly grounded as a precaution against possible electrical shock WARNING To reduce the risk of fire electric shock or personal injury mount fan to outlet box marked Acceptable for Fan Support and use screws supplied with outlet box Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced Consult a qualified elect...

Page 11: ...d and that no bare wire is visible at the wire connectors except for the ground wire Do not operate fan until blades are in place Noise and fan damage could result WARNING b Securely connect the supply white neutral wire to the receiver white AC IN N wire c Securely connect the supply black wire hot wire to the receiver black AC IN L wire d Securely connect the fan motor white wire to the receiver...

Page 12: ...igure 16 Tighten the knurled knobs securely until the ceiling cover fits snugly against the ceiling CEILING COVER LOCKWASHER 2 KNURLED KNOB 2 1 1 4 THREADED STUD 2 12 To avoid possible fire or shock make sure that the electrical wires are completely inside the outlet box and not pinched between the ceiling cover and the ceiling WARNING Figure 16 7 Your ceiling fan is now installed and wired and re...

Page 13: ...on of Wall Control SINGLE POLE INSTALLATION Figure 18 1 Disconnect power at circuit breaker or remove fuse 2 Remove faceplate and screws from existing wall control Pull control out from the wall box Determine the hot wire and the load wire and disconnect these wires from control Do not attempt to disconnect any wires not already connected to existing control 3 Before installing wall control place ...

Page 14: ...onnect one black wire of the wall control to both remaining traveler wires in the wall box and secure with wire connector supplied NOTE Retrofit 3 way installations are likely to include two traveler wires between the two wall boxes In new construction only one traveler wire Is required 3 WAY WIRlNG DIAGRAM NEW CONSTRUCTION 6 Place wall control into wall box Screw in place and install decorator st...

Page 15: ...n the ON position 2 To set the desired fan speed press the HI MED or LOW buttons to operate your fan on high medium or low speed Figure 22 3 To turn your fan off press the OFF button 4 To set the level of housing light brightness press and hold the LIGHT button The light brightness will continue to increase then decrease while the button is held down When the light is at the desired brightness rel...

Page 16: ...ply circuit before installing the fan and optional light kit and or remote control receiver To install an optional Emerson light kit remove the four screws securing the switch cup assembly to the switch cup adapter Remove the finial nut from the switch cup and install the light kit in accordance with the light kit Owner s Manual To avoid possible electrical shock be sure electricity is turned off ...

Page 17: ...radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna In...

Page 18: ...packaging material be certain all parts have been removed HOW TO ORDER REPAIR PARTS WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION PART NUMBER NAME OF ITEM PART DESCRIPTION MODEL NUMBER The model number of your Fan will be found on a label attached to the top housing For repair parts phone 1 800 654 3545 18 BP7306 Nottingham 6 19 06 1 00 PM Page 18 ...

Page 19: ...7 Cover Ceiling 762972 GLZ 762972 WB 18 Cover Upper 762973 GLZ 762973 WB 19 Trim Housing 762977 GLZ 762977 WB 20 Glass Upper 762975 762975 21 Flange Set full set for one fan 762980 GLZ 762980 WB 22 Blade Set full set for one fan 762985 762985 23 Cup Assembly Switch 762988 GLZ 762988 WB 24 Nut Finial 762989 GLZ 762989 WB 25 Harness Assembly Housing Lights 762992 762992 26 Harness Assembly Reversing...

Page 20: ...g screws in motor housing are snug not over tight 3 Fan wobbles 1 Setscrew in motor coupling 1 Raise upper housing glass and excessively is not tightened securely coupling cover then tighten setscrew securely 2 Setscrew in the hanger ball 2 Tighten the setscrew in the downrod assembly is loose hanger ball downrod assembly 3 Screws securing fan blade 3 Check to be sure screws flanges to mounting hu...

Reviews: