3.6
Fault conditions
The Net Safety ST3 sensor provides a number of fault conditions that the Net Safety
Millennium II transmitter translates into an analog or fault relay output. These fault
conditions are outlined in
Table 3-1: Fault Conditions
Fault condition
Analog output
Fault relay output
Sensor zero drift
2.5 mA
Fault
Memory fault
2.5 mA
Fault
Sensor nearing end of life
Alternating 2.5 mA for 10
seconds and normal level for 50
seconds
Alternating 2.5 mA for 10
seconds and normal level for 50
seconds
Calibrate sensor
2.5 mA
Fault
Operate
Reference Manual
November 2020
00809-0100-4303
22
Emerson.com/FlameGasDetection