Reference Manual
Operation
MAN-0091, Revision 8
June 2016
Operation
13
3.4
Millennium II Basic transmitter configuration
When using the SC311 sensor with the Millennium II Basic transmitter, DIP switch on the transmitter
should be set up as follows:
Table 3-1 Millennium II Basic transmitter DIP switch 2 positions
Position 1
Position 2
Position 3
Position 4
Gas Curve
OFF
OFF
OFF
OFF
Methane (0)
ON
OFF
OFF
OFF
Propane (1)*
OFF
ON
OFF
OFF
n-Butane (2)*
ON
ON
OFF
OFF
Iso-Pentane (3)*
OFF
OFF
ON
OFF
n-Pentane (4)*
ON
OFF
ON
OFF
Ethane (5)
OFF
ON
ON
OFF
Iso-Butane (6)*
ON
ON
ON
OFF
Ethylene (7)
OFF
OFF
OFF
ON
Hexane (8)*
ON
OFF
OFF
ON
Propylene (9)*
*Indicates gases are not third party performance verified
3.5
Fault conditions
The SC311 sensor will provide a number of fault conditions that the Millennium II transmitter will
translate into an analog or fault relay output. These fault conditions are outlined in the following table.
Table 3-2 Fault conditions
Fault condition
Analog output (mA)
Fault relay output
Span calibration failure
2.5
Fault
Zero calibration failure
2.5
Fault
Sensor over-range
2.5
Fault
Low temperature
2.5
Fault
High temperature
2.5
Fault
Low voltage
2.5
Fault
High voltage
2.5
Fault
Replace sensor (during calibration cycle)
Momentary 2.5
Momentary Fault
Memory fault
2.5
Fault
Power supply fault
2.5
Fault