16 • MultiFlex RTU Operator’s Guide
026-1706 Rev 3
4.3. Analog Outputs
The MultiFlex RTU analog outputs are
+0-+10VDC points used for controlling
variable-position economizers and variable-
speed fans. The maximum output current for
each point is 10 milliamps.
Unlike most of the RTU inputs and outputs, the
two analog points are not pre-defined. To enable
them for use in economization or fan control,
they must be assigned in the RTU.
shows the location of the analog outputs.
4.3.1. Wiring the RTU Analog
Output Points
The analog outputs have no hardware-based fail-
safe settings (fail-safes are set in the board
firmware by setting either “fan speed on failure”
or “economizer% on failure”). All that is
required to connect a device to an analog point is
to connect the “+” terminal to the positive wire
on the device and the “-” terminal to the negative
(or ground) wire of the device.
Figure 4-8
- MultiFlex RTU Analog Output Locations
Summary of Contents for MultiFlex RTU