Analog Output Registers
MODBUS Communications • 25
7.4.
Analog Output Registers
Analog output registers are readable (using function code 03) and writable (using function code 06).
Table 7-2
- Analog Output Registers
Reg
Description
Range
Units
P.-##
2000
Alarm setpoint
75-3500
PPM
P.-02
2001
Alarm ON delay
(Alarm flag register
3000 is set to 1)
0-15
min
P.-04
2002
2003
Alarm OFF delay
0-15
min
P.-05
2004
Relay action
0=NO
1=Failsafe
none
P.-06
2005
Relay latching enable
0=Disable
1=Enable
none
P.-07
2006
Buzzer enable
0=Disable
1=Enable
none
P.-08
2007
Display mode
0=Off
1=On
none
P.-09
2008
Analog output type
0=0-5 V
1=1-4 V
2=0-10 V
3=2-10 V
4=4-20 ma
none
P.-03
2009
Baud rate
0=9600
1=19200
none
P.-13
2010
Stop bits
1 or 2
none
P.-14
2011
Gas curve number
1 to 4
(broadband
unit) or gas
type (gas
specific)
none
P.-11
2012
Analog output full scale
PPM (R/O)
100-3500
PPM
P.-16
2013
Parity
0=None
1=Odd
2=Even
none
P.-15
Buzzer mute time
0-59
min
P.-12